Attack ChainAIDerived
Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain
-
AccessGain adjacent-network access to concentrator
-
DeliveryAuthenticate with low-privilege credentials
-
ExploitSend oversized 'meter' parameter to ShowMeterDatabase()
-
ExecutionOverflow fixed stack buffer via sprintf()
-
PersistCorrupt stack / crash device
-
ImpactAchieve code execution or DoS on grid gateway
Vulnerability Assessment
| Weakness |
CWE
OWASP Top 10:2025
A06:2021 - Vulnerable and Outdated Components
ASVS 5.0
V15 - Secure Coding and Architecture Stack buffer bounds checking
MITRE ATT&CK
1 technique across 1 tactic: Execution The technique list with ATT&CK links and the kill-chain view is part of the Basic plan and up. |
| Exploitation Conditions | Exploitation requires adjacent-network reach to the SGE-PLC1000/SGE-PLC50 management interface (AV:A - same LAN/OT segment, not internet-facing) plus low-privilege authenticated access (PR:L) to invoke the ShowMeterDatabase() function. The concrete trigger is supplying an excessively long value for the 'meter' parameter, which GetParameter(meter) passes unvalidated into a fixed-size stack buffer via sprintf(). Affected firmware is confirmed as v9.0.2 for both models. Limiting factors: the attacker must already be on the adjacent network and possess valid low-tier credentials, and no default-config unauthenticated remote path is indicated; this substantially narrows realistic exposure versus the raw base score. |
| Impact | This is a stack-based buffer overflow (CWE-121) in Circutor SGE-PLC1000/SGE-PLC50 smart-grid PLC concentrators reached through an unbounded sprintf() on the 'meter' parameter. The vendor CVSS 4.0 vector (AV:A/AC:L/AT:N/PR:L/UI:N, VC:H/VI:L/VA:H, subsequent SC:H/SI:L/SA:H, base 8.5) frames it as an adjacent-network, low-privilege attack with high confidentiality/availability impact and a scope change onto downstream systems - consistent with memory corruption on an embedded metering gateway. Countervailing signals lower the real-world urgency: EPSS is only 0.07% (22nd percentile), there is no CISA KEV listing, and no public proof-of-concept is referenced, so exploitation is neither observed nor demonstrated. The AV:A choice materially constrains reach - an attacker must already be on the adjacent (local/utility segment) network AND hold low-privilege credentials (PR:L), not the internet-wide unauthenticated posture a raw 8.5 might suggest. Net: a genuinely serious memory-safety flaw in a niche ICS/OT device, but current exploitation likelihood is low and access-gated; prioritize for utilities running these concentrators, not as a broad emergency. |
| Exploit ScenarioDerived | An attacker with low-privilege access on the same network segment as an SGE-PLC1000/SGE-PLC50 concentrator submits an over-long 'meter' value to the ShowMeterDatabase() handler, which copies it via sprintf() into a fixed-size stack buffer, overflowing it. This can crash the device (availability loss) or, with a tailored payload, corrupt the stack toward code execution on the OT gateway. No public exploit code is currently referenced, so this remains a theoretical-but-credible path. |
Get an e-mail when this CVE is exploited, patched or re-scored. Free account.
Alert meAnalysisAIv2 – Sep 26, 2026
Stack-based buffer overflow in Circutor SGE-PLC1000 and SGE-PLC50 smart-grid PLC concentrators running firmware v9.0.2 allows an attacker to corrupt memory and potentially achieve code execution or a denial-of-service condition by supplying an excessively long 'meter' parameter that is copied into a fixed-size stack buffer via sprintf() inside the ShowMeterDatabase() function. Exploitation requires the attacker to already reside on the adjacent network (same LAN/OT segment) and to hold valid low-privilege credentials, since the parameter is reached through an authenticated management function; the CVE carries a base CVSS of 8.5, though our independent assessment (CVSS 3.1 AV:A/PR:L/S:C/C:H/I:L/A:H) confirms that reachability and authentication prerequisites meaningfully narrow practical exposure. EPSS is very low at 0.07% (22nd percentile), no public exploit code has been identified at time of analysis, and the vulnerability is not listed in CISA KEV, so there is no indication of active exploitation.
Earlier versions of this analysis (1)
RemediationAI
No vendor-released patch or fixed firmware version is identified in the available data at the time of analysis, so administrators should track the INCIBE-CERT advisory (https://www.incibe.es/en/incibe-cert/notices/aviso-sci/multiple-vulnerabilities-circutor-products-0) and Circutor's own security communications for an updated firmware release, applying it as soon as it is published. Until a patch exists, the most effective compensating control is strict network segmentation: keep SGE-PLC1000/SGE-PLC50 management interfaces off routable or internet-facing networks and confine them to isolated OT VLANs with firewall rules that permit access only from dedicated engineering workstations, since the attack path is adjacent-network (AV:A) rather than remote-internet. Complement this by auditing and aggressively minimizing the accounts that can invoke ShowMeterDatabase() and other parameter-driven diagnostic functions, enforcing least privilege and strong unique credentials to remove the low-privilege authenticated foothold the exploit requires; the trade-off is added administrative overhead and possible friction for legitimate maintenance workflows. Where the interface supports it, restrict management access to allowlisted source IPs and, if the function is not operationally required, disable or block access to the meter-database/diagnostic endpoint entirely - accepting the loss of that troubleshooting capability. Monitor device logs for malformed or abnormally long 'meter' parameter values and for unexpected process restarts as an early indicator of attempted exploitation, and validate any firmware update against the vendor's signed release before deployment in live grid environments.
Affected VersionsENISA
Affected Packages
Source: OSV (Open Source Vulnerabilities)
Affects your stack
Affects 1 package in euvd
Checking this CVE against your own stacks and servers is part of the Basic plan and up.
Technical ContextAI · show details
The flaw is a classic stack-based buffer overflow (CWE-121) rooted in an unbounded string copy. In firmware v9.0.2 of the Circutor SGE-PLC1000 and SGE-PLC50 - PLC concentrators used in smart-grid/energy distribution environments - the ShowMeterDatabase() routine reads a user-supplied 'meter' parameter via GetParameter(meter) and then formats it into a fixed-size stack buffer using sprintf() without any length validation. Because sprintf() does not bound its output, an oversized 'meter' value overflows adjacent stack memory, which can overwrite saved registers and the return address, leading to memory corruption, control-flow hijack, process crash, or arbitrary code execution depending on payload and platform mitigations. The affected CPEs are cpe:2.3:o:circutor:sge-plc1000_firmware:9.0.2 and cpe:2.3:o:circutor:sge-plc50_firmware:9.0.2, confirming both device models at exactly that firmware revision. The CVSS 4.0 vector reflects adjacent-network access (AV:A), low privileges (PR:L), high confidentiality and availability impact with low integrity impact, and scope change (S:C), consistent with the 3.1 assessment that rates confidentiality and availability H and integrity L.
Know when Sge Plc1000 Firmware gets its next vulnerability
- Watch products and get an email when something new is published
- Check this CVE against your own stack and servers
- Exploit and PoC references, threat intelligence from 22 sources
No credit card · 7-day full trial
Severity by source
CVSS:4.0/AV:A/AC:L/AT:N/PR:L/UI:N/VC:H/VI:L/VA:H/SC:H/SI:L/SA:H
Adjacent access and low-privilege auth are required (AV:A/PR:L); the memory corruption crosses into managed grid systems (S:C) with high confidentiality/availability but limited integrity impact, mirroring the vendor 4.0 profile.
Primary rating from Vendor (incibe).
CVSS VectorVendor: incibe
Lifecycle Timeline
4DescriptionCVE.org
Stack-based buffer overflow vulnerability in Circutor SGE-PLC1000/SGE-PLC50 v9.0.2. In the 'ShowMeterDatabase()' function, there is an unlimited user input that is copied to a fixed-size buffer via 'sprintf()'. The 'GetParameter(meter)' function retrieves the user input, which is directly incorporated into a buffer without size validation. An attacker can provide an excessively large input for the 'meter' parameter.
Executive ViewAI
A critical stack-based buffer overflow vulnerability (CVE-2025-11784) affects Circutor SGE-PLC1000/SGE-PLC50 devices running version 9.0.2, with no patch currently available. Organizations using these industrial control systems face immediate risk of remote code execution and potential operational disruption.
Implement network segmentation to restrict access to SGE-PLC devices to trusted administrative networks only; deploy WAF rules to block oversized meter parameter inputs to the device interface; disable the ShowMeterDatabase() function if operationally feasible; enforce strict input validation at network boundary; implement comprehensive monitoring for exploitation attempts; maintain offline backups of critical configurations; establish incident response procedures for potential code execution.
Threat Intelligence Overview
How this decision was reached
The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.
What every action level means
SSVC AssessmentENISA
Priority Score
Attack Technique
A buffer overflow occurs when a program writes more data to a memory buffer than it was allocated to hold, causing the excess data to spill into adjacent memory regions.
A stack-based buffer overflow occurs when a program writes more data to a buffer located on the stack than it was allocated to hold.
More in Sge Plc1000 Firmware
View allStack-based buffer overflow vulnerability in Circutor SGE-PLC1000/SGE-PLC50 v9.0.2. In the 'ShowMeterPasswords()' functi
Stack-based buffer overflow in Circutor SGE-PLC1000/SGE-PLC50 v0.9.2. This vulnerability allows an attacker to remotely
Stack-based buffer overflow vulnerability in Circutor SGE-PLC1000/SGE-PLC50 v9.0.2. In the 'showMeterReport()' function,
SGE-PLC1000 device, in its 0.9.2b firmware version, does not handle some requests correctly, allowing a remote attacker
Stack-based buffer overflow in the Circutor SGE-PLC1000 and SGE-PLC50 power line communication devices running firmware
Improper Authentication vulnerability in the cookie parameter of Circutor SGE-PLC1000 firmware version 0.9.2b allows an
Hardcoded cryptographic key exposure in Circutor SGE-PLC1000 and SGE-PLC50 firmware v9.0.2 lets an attacker who has loca
Authenticated command injection in Circutor SGE-PLC1000 and SGE-PLC50 gateways running firmware 9.0.2 lets a low-privile
A stack-based buffer overflow in the AddEvent() function of Circutor SGE-PLC1000 and SGE-PLC50 power-line communication
Authenticated adjacent-network attackers can execute arbitrary shell commands on Circutor SGE-PLC1000 and SGE-PLC50 devi
Stack-based buffer overflow in Circutor SGE-PLC1000 and SGE-PLC50 firmware v9.0.2 allows authenticated attackers on an a
Heap-based buffer overflow in the management interface of Circutor SGE-PLC1000 and SGE-PLC50 concentrators running firmw
EUVD-2025-200232
NVD
CVE.org
EPSS
VulDB
GitHub PoC
Exploit-DB