Skip to main content

Circutor SGE-PLC1000 CVE-2025-11787

| EUVDEUVD-2025-200229 HIGH
OS Command Injection (CWE-78)
2025-12-02 cve-coordination@incibe.es
8.5
CVSS 4.0 · Vendor: incibe
View

Attack ChainAIDerived

Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain

  1. Access
    Authenticate to device management interface
  2. Delivery
    Access network diagnostic function (GetDNS/CheckPing/TraceRoute)
  3. Exploit
    Inject shell metacharacters into diagnostic parameter
  4. Execution
    Execute arbitrary OS commands on device
  5. Impact
    Full compromise of grid concentrator

Vulnerability Assessment

Weakness
CWE
OWASP Top 10:2025
A05:2025 - Injection
ASVS 5.0
V1 - Encoding and Sanitization OS command sanitization, avoid shell exec
MITRE ATT&CK

2 techniques across 1 tactic: Execution

The technique list with ATT&CK links and the kill-chain view is part of the Basic plan and up.

Exploitation Conditions

Requires an authenticated low-privilege session on the Circutor SGE-PLC1000/SGE-PLC50 v9.0.2 management interface, then invocation of the built-in network diagnostic features backed by the GetDNS(), CheckPing() or TraceRoute() functions, into which shell metacharacters are injected. Limiting factors: authentication is mandatory (PR:L), the specific firmware version 9.0.2 must be running, the affected diagnostic functionality must be reachable, and the vendor's CVSS 4.0 marks user interaction as required (UI:A) - reducing realistic risk below the raw network-vector score. Exposure is further bounded by the ICS deployment context, where these devices are typically on segmented operational networks rather than the open internet.

Impact

This is a genuine but access-gated flaw. The CVSS 4.0 vector (AV:N/AC:L/PR:L/UI:A/VC:H/VI:H/VA:H) scores 8.5 and describes network-reachable, low-complexity OS command injection yielding full compromise of the device OS - but two factors temper it: PR:L means an authenticated (albeit low-privilege) session is required, and the vendor asserts UI:A (active user interaction). EPSS is low at 0.29% (52nd percentile), there is no CISA KEV listing and no public exploit identified at time of analysis, so exploitation is not currently probable or observed. The residual risk is driven less by mass-exploitation likelihood and more by the device class: these are ICS/OT smart-grid data concentrators where any authenticated OS command execution is high-consequence. Note a signal tension worth flagging: the CVSS 4.0 UI:A (interaction required) is questionable for a classic self-service command-injection where an authenticated operator submits the payload directly into a diagnostic function they themselves invoke - verify with the INCIBE advisory whether a second user is genuinely in the loop.

Exploit ScenarioDerived

An attacker with low-privilege authenticated access to the SGE-PLC1000/SGE-PLC50 web/management interface enters shell metacharacters into the DNS, ping, or traceroute diagnostic input (GetDNS/CheckPing/TraceRoute), which are passed unsanitized to an OS shell, executing arbitrary commands on the device. No public proof-of-concept was identified at time of analysis; exploitation follows a well-understood diagnostic-function command-injection pattern.

This Week Schedule remediation this week. Why: HIGH severity (CVSS 7.0-8.9).
No patch listed yet 0.3% exploitation probability (EPSS)

Get an e-mail when this CVE is exploited, patched or re-scored. Free account.

Alert me

AnalysisAIv2 – Sep 26, 2026

Authenticated command injection in Circutor SGE-PLC1000 and SGE-PLC50 gateways running firmware 9.0.2 lets a low-privilege user of the management interface run arbitrary operating-system commands through the GetDNS(), CheckPing() and TraceRoute() diagnostic functions, which pass unsanitized input to the underlying shell. The vendor scores this 8.5 under CVSS 4.0 with PR:L and UI:A, and our independent CVSS 3.1 assessment agrees on high confidentiality, integrity and availability impact while emphasizing that exploitation is gated behind a valid authenticated session and the ICS deployment context. EPSS is low at 0.29% (52nd percentile), the CVE is not in CISA KEV, and no public exploit code was identified at time of analysis, so this is a genuine but access-gated flaw rather than an internet-exposed, unauthenticated remote compromise.

Earlier versions of this analysis (1)
v1 Mar 15, 2026 - 14:04 CVSS 8.8

RemediationAI

No patched firmware version is identified in the available data, so remediation should begin by consulting the Circutor/INCIBE advisory at https://www.incibe.es/en/incibe-cert/notices/aviso-sci/multiple-vulnerabilities-circutor-products-0 for an updated firmware release and applying it as soon as Circutor publishes one. Until a fixed build is available, compensating controls are necessary: place the management interface of the SGE-PLC1000/SGE-PLC50 on a dedicated, tightly firewalled OT management VLAN and block HTTP/HTTPS access from user, corporate IT and internet-facing networks, accepting the trade-off that remote administration must be performed from a jump host inside the trusted segment; restrict and audit all accounts that can reach the diagnostics pages, since even low-privilege authenticated users can exploit this flaw, and remove or disable unused accounts to reduce the attack surface; if the diagnostic pages are not operationally required, restrict access to them or disable the affected GetDNS/CheckPing/TraceRoute functionality where the firmware allows it, with the trade-off of losing built-in network troubleshooting and possibly requiring alternative diagnostic tooling; and monitor device logs and network traffic for shell metacharacter patterns or unexpected outbound connections from the gateway as a detection measure. Because the vulnerability is not in CISA KEV and no public exploit has been observed, these steps should be prioritized according to the exposure of the management interface and the criticality of the affected energy-sector process.

Affected VersionsENISA

Circutor 9.0.2

Affected Packages

euvd circutor no fix

Source: OSV (Open Source Vulnerabilities)

Affects your stack

Affects 1 package in euvd

Checking this CVE against your own stacks and servers is part of the Basic plan and up.

Technical ContextAI · show details

This is a classic OS command injection (CWE-78, improper neutralization of special elements used in an OS command) in the firmware's network diagnostic tooling. The CPE strings cpe:2.3:o:circutor:sge-plc1000_firmware:9.0.2 and cpe:2.3:o:circutor:sge-plc50_firmware:9.0.2 identify the affected code base, and the vulnerable functions GetDNS(), CheckPing() and TraceRoute() are the diagnostic wrappers that most likely shell out to utilities such as nslookup, ping and traceroute without sanitizing user-supplied hostnames or addresses, allowing shell metacharacters to be interpreted by the OS. The vendor's CVSS 4.0 vector (AV:N/AC:L/AT:N/PR:L/UI:A, with VC:H/VI:H/VA:H but SC:N/SI:N/SA:N) shows high impact confined to the device itself rather than a subsequent-system blast radius, and our independent CVSS 3.1 assessment (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H) reaches a similar high-severity conclusion. Because these are power-line communication gateways used in energy/ICS environments, the practical reachability of the management interface depends heavily on network segmentation between IT and OT zones.

Know when Sge Plc1000 Firmware gets its next vulnerability

  • Watch products and get an email when something new is published
  • Check this CVE against your own stack and servers
  • Exploit and PoC references, threat intelligence from 22 sources

No credit card · 7-day full trial

Severity by source

Vendor (incibe) PRIMARY 8.5 HIGH
CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
vuln.today AI 8.8 HIGH

Network-reachable diagnostic feature requiring a low-privilege authenticated session (PR:L); attacker submits their own injection so UI:N, and OS command execution gives full C/I/A on the device.

3.1 AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
4.0 AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N

Primary rating from Vendor (incibe).

CVSS VectorVendor: incibe

Attack Vector
Network
Attack Complexity
Low
Attack Requirements
None
Privileges Required
Low
User Interaction
Active
Vulnerable system: Confidentiality
High
Vulnerable system: Integrity
High
Vulnerable system: Availability
High
Subsequent system: Confidentiality
None
Subsequent system: Integrity
None
Subsequent system: Availability
None

Lifecycle Timeline

3
CVSS changed
Sep 26, 2026 - 00:22 NVD
8.8 (HIGH) 8.5 (HIGH)
CVE Published
Dec 02, 2025 - 13:15 cve.org
HIGH 8.5
CVE Published
Dec 02, 2025 - 13:15 nvd
HIGH 8.8

DescriptionCVE.org

Command injection vulnerability in the operating system in Circutor SGE-PLC1000/SGE-PLC50 v9.0.2 through the 'GetDNS()', 'CheckPing()' and 'TraceRoute()' functions.

Executive ViewAI

Why It Matters

A critical command injection vulnerability affects Circutor SGE-PLC1000/SGE-PLC50 devices running version 9.0.2, allowing attackers to execute arbitrary commands on affected industrial control systems. Organizations using these programmable logic controllers face immediate risk of system compromise, operational disruption, and potential safety incidents until a vendor patch becomes available.

Business Impact: High
Compensating Controls

Implement network segmentation and restrict access to affected devices using firewall rules and VLANs; disable or restrict the vulnerable functions (GetDNS, CheckPing, TraceRoute) at the application level if possible; monitor network traffic to these devices for suspicious command patterns; implement strict input validation at any interface communicating with these PLCs; establish 24/7 monitoring for indicators of compromise; prepare incident response procedures for potential exploitation.

Threat Intelligence Overview

EPSS Score
0.3%
Top 48% exploitable
Prevalence
Low
niche industry-specific ICS/smart-grid PLC data concentrator, no broad footprint
Data Quality
4 sources
Confidence: Medium

How this decision was reached

The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.

SignalValue
Severity HIGH
CISA KEV No
Public POC No
EPSS 0.3%
Patch available No
Active threat No
Deciding rule
HIGH severity (CVSS 7.0-8.9)
What every action level means
Emergency Immediate action required. Criteria: CRITICAL + in CISA KEV (actively exploited) without patch, OR CRITICAL + EPSS > 30% without patch, OR CRITICAL + active threat signals without patch.
Act Now Prioritize within 24-48h. Criteria: in KEV with patch available, OR CRITICAL + public POC, OR HIGH + EPSS > 10%, OR CRITICAL + active threat, OR any CRITICAL severity.
This Week Schedule remediation this week. Criteria: HIGH severity (CVSS 7.0-8.9). Patch within normal change window.
This Month Plan within 30 days. Criteria: MEDIUM severity (CVSS 4.0-6.9), lower exploitation probability. Include in regular patch cycle.
Monitor Track and reassess. Criteria: LOW severity (CVSS 0.1-3.9), minimal exploitation risk. No immediate action needed.

SSVC AssessmentENISA

SSVC Decision· derived
Scheduled
Exploitation· derived
None
System Exposure· derived
Open
Automatable· derived
No
Human Impact
High

Priority Score

42
Low Medium High Critical
KEV: 0
EPSS: 0
CVSS: +42
PoC: 0
Weaponized: 0
Threat intel: 0
Gov advisory: 0

Attack Technique

OS command injection occurs when an application passes unsanitized user input directly into system shell commands.

CVE-2025-11785 CRITICAL
9.8 Dec 02

Stack-based buffer overflow vulnerability in Circutor SGE-PLC1000/SGE-PLC50 v9.0.2. In the 'ShowMeterPasswords()' functi

CVE-2025-11778 CRITICAL
9.8 Dec 02

Stack-based buffer overflow in Circutor SGE-PLC1000/SGE-PLC50 v0.9.2. This vulnerability allows an attacker to remotely

CVE-2025-11780 CRITICAL
9.8 Dec 02

Stack-based buffer overflow vulnerability in Circutor SGE-PLC1000/SGE-PLC50 v9.0.2. In the 'showMeterReport()' function,

CVE-2021-33841 CRITICAL
9.8 Jun 09

SGE-PLC1000 device, in its 0.9.2b firmware version, does not handle some requests correctly, allowing a remote attacker

CVE-2025-11779 CRITICAL
9.4 Dec 02

Stack-based buffer overflow in the Circutor SGE-PLC1000 and SGE-PLC50 power line communication devices running firmware

CVE-2021-33842 HIGH
8.8 Jun 09

Improper Authentication vulnerability in the cookie parameter of Circutor SGE-PLC1000 firmware version 0.9.2b allows an

CVE-2025-11781 HIGH
8.6 Dec 02

Hardcoded cryptographic key exposure in Circutor SGE-PLC1000 and SGE-PLC50 firmware v9.0.2 lets an attacker who has loca

CVE-2025-11783 HIGH
8.5 Dec 02

A stack-based buffer overflow in the AddEvent() function of Circutor SGE-PLC1000 and SGE-PLC50 power-line communication

CVE-2025-11786 HIGH
8.5 Dec 02

Authenticated adjacent-network attackers can execute arbitrary shell commands on Circutor SGE-PLC1000 and SGE-PLC50 devi

CVE-2025-11784 HIGH
8.5 Dec 02

Stack-based buffer overflow in Circutor SGE-PLC1000 and SGE-PLC50 smart-grid PLC concentrators running firmware v9.0.2 a

CVE-2025-11782 HIGH
8.5 Dec 02

Stack-based buffer overflow in Circutor SGE-PLC1000 and SGE-PLC50 firmware v9.0.2 allows authenticated attackers on an a

CVE-2025-11788 HIGH
8.5 Dec 02

Heap-based buffer overflow in the management interface of Circutor SGE-PLC1000 and SGE-PLC50 concentrators running firmw

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy