CVE-2026-15952 Sep 28, 13:10 HIGH CISA This Week

Incorrect permission assignment in ABB Protection and Control IED Manager (PCM600) through version 2.14 leaves a critical application resource on the Windows engineering workstation protected by weak access controls, letting a local user read and alter protected PCM600 data with high impact to confidentiality, integrity, and availability. Exploitation requires the attacker to already have local access to the host running PCM600 - the vendor vector describes a local attack (AV:L) with high privileges required (PR:H) and high attack complexity (AC:H), while our independent assessment scores it as a low-complexity local issue requiring only low privileges (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H), so a lower-privileged local account may be sufficient in practice. No public exploit code has been identified at time of analysis and there is no CISA KEV confirmation of active exploitation; ABB published the vendor advisory (document 2NGA003170), and this is a genuine but low-urgency issue.

Abb Ics Protection And Control Ied Manager Pcm600
NVD
CVSS 4.0
7.1
EPSS
0.1%
CVE-2026-78311 Sep 24, 08:42 HIGH PATCH This Week

SQL injection in Delta Electronics DIAEnergie before version 1.11.00.022 allows an attacker holding a valid low-privileged account to read from and write to the platform's backend database, putting the confidentiality, integrity, and availability of its operational data at risk. The flaw is network reachable (AV:N), requires only a low-privileged session (PR:L), and needs no user interaction; it is not confirmed as actively exploited (no CISA KEV listing) and no public exploit code has been identified at time of analysis. Delta released the fix in advisory PCSA-2026-00014 alongside a batch of related DIAEnergie flaws, including an authentication bypass (CVE-2026-78308) that could supply the very credentials this SQL injection depends on.

SQLi Diaenergie Deltaww Ics
NVD VulDB
CVSS 3.1
8.8
EPSS
0.2%
CVE-2026-105275 Oct 08, 21:18 MEDIUM CISA This Month

An authenticated user with Viewer privileges can exploit a relative path traversal flaw in the data import functionality of Satel Netco Design versions prior to v2.1.7 to probe file paths outside the intended import directory and use application responses as an existence oracle for files on the host system. The vulnerability is network-reachable (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N) but requires valid low-privilege credentials, and its impact is confined to low confidentiality loss via file-existence inference; it does not disclose file contents, allow writes, or enable code execution. No public exploit identified at time of analysis.

Path Traversal Ics Satel Netco Design
NVD GitHub
CVSS 4.0
5.3
EPSS
0.3%
CVE-2026-78310 Sep 24, 08:50 MEDIUM PATCH This Month

An authorization bypass through a user-controlled key (CWE-639) exists in Delta Electronics DIAEnergie versions before 1.11.00.022, allowing a low-privilege authenticated user to reference objects or records belonging to other users and read data they are not authorized to access. The flaw is network-reachable (AV:N) and requires no victim interaction (UI:N), but exploitation is gated behind a valid low-privilege session (PR:L), so realistic abuse is limited to malicious insiders, legitimate users exceeding their privileges, or attackers who have already obtained credentials; impact is bounded to confidentiality (C:L) with no integrity or availability effect, giving a CVSS 3.1 base score of 4.3. No public exploit code has been identified at time of analysis and the issue is not confirmed actively exploited (CISA KEV), making this a genuine but low-priority weakness rather than a high-severity emergency.

Authentication Bypass Diaenergie Deltaww Ics
NVD VulDB
CVSS 3.1
4.3
EPSS
0.2%
CVE-2025-11788 Dec 02, 13:15 HIGH This Week

Heap-based buffer overflow in the management interface of Circutor SGE-PLC1000 and SGE-PLC50 concentrators running firmware 9.0.2 lets an attacker who can reach the device over the network and authenticate with low privileges corrupt heap memory by supplying an oversized 'meter' parameter, yielding high confidentiality and availability impact without any user interaction. The flaw sits in ShowSupervisorParameters(), which passes the unbounded 'meter' value obtained through GetParameter(meter) into a fixed-size buffer via sprintf(). No public exploit code has been identified at time of analysis, and the EPSS score is low at 0.06% (20th percentile), so risk is driven primarily by exposure of the concentrator's management interface rather than by observed exploitation activity.

Buffer Overflow Heap Overflow Sge Plc1000 Firmware Sge Plc50 Firmware Ics
NVD VulDB
CVSS 4.0
8.5
EPSS
0.1%
CVE-2025-11787 Dec 02, 13:15 HIGH This Week

Authenticated command injection in Circutor SGE-PLC1000 and SGE-PLC50 gateways running firmware 9.0.2 lets a low-privilege user of the management interface run arbitrary operating-system commands through the GetDNS(), CheckPing() and TraceRoute() diagnostic functions, which pass unsanitized input to the underlying shell. The vendor scores this 8.5 under CVSS 4.0 with PR:L and UI:A, and our independent CVSS 3.1 assessment agrees on high confidentiality, integrity and availability impact while emphasizing that exploitation is gated behind a valid authenticated session and the ICS deployment context. EPSS is low at 0.29% (52nd percentile), the CVE is not in CISA KEV, and no public exploit code was identified at time of analysis, so this is a genuine but access-gated flaw rather than an internet-exposed, unauthenticated remote compromise.

Command Injection Sge Plc1000 Firmware Sge Plc50 Firmware Ics
NVD VulDB
CVSS 4.0
8.5
EPSS
0.3%
CVE-2025-11786 Dec 02, 13:15 HIGH This Week

Authenticated adjacent-network attackers can execute arbitrary shell commands on Circutor SGE-PLC1000 and SGE-PLC50 devices running firmware 9.0.2 by supplying shell metacharacters in the newPassword parameter of SetUserPassword(). The flaw combines an unsanitized sprintf() path into system() with CWE-121 stack-based buffer overflow conditions, requiring valid low-privilege access on the same network segment and no user interaction; it enables high confidentiality and availability impact and potential scope change onto subsequent systems. No public exploit code or CISA KEV listing was identified at time of analysis, and EPSS is 0.07% (22nd percentile).

Buffer Overflow Command Injection Stack Overflow Sge Plc1000 Firmware Sge Plc50 Firmware +1
NVD VulDB
CVSS 4.0
8.5
EPSS
0.1%
CVE-2025-11784 Dec 02, 13:15 HIGH This Week

Stack-based buffer overflow in Circutor SGE-PLC1000 and SGE-PLC50 smart-grid PLC concentrators running firmware v9.0.2 allows an attacker to corrupt memory and potentially achieve code execution or a denial-of-service condition by supplying an excessively long 'meter' parameter that is copied into a fixed-size stack buffer via sprintf() inside the ShowMeterDatabase() function. Exploitation requires the attacker to already reside on the adjacent network (same LAN/OT segment) and to hold valid low-privilege credentials, since the parameter is reached through an authenticated management function; the CVE carries a base CVSS of 8.5, though our independent assessment (CVSS 3.1 AV:A/PR:L/S:C/C:H/I:L/A:H) confirms that reachability and authentication prerequisites meaningfully narrow practical exposure. EPSS is very low at 0.07% (22nd percentile), no public exploit code has been identified at time of analysis, and the vulnerability is not listed in CISA KEV, so there is no indication of active exploitation.

Buffer Overflow Stack Overflow Sge Plc1000 Firmware Sge Plc50 Firmware Ics
NVD VulDB
CVSS 4.0
8.5
EPSS
0.1%
CVE-2025-11783 Dec 02, 13:15 HIGH This Week

A stack-based buffer overflow in the AddEvent() function of Circutor SGE-PLC1000 and SGE-PLC50 power-line communication devices running firmware v9.0.2 lets an attacker with adjacent-network access and valid low-privilege credentials overwrite a fixed 48-byte stack buffer using an over-long username, causing memory corruption and potentially remote code execution. Per the CVSS 4.0 vector (8.5) the attacker requires both adjacency to the same L2/management or substation segment (AV:A) and authentication (PR:L), with no user interaction, though exploit reliability for full code execution is described only as 'possible' and may be uncertain. No public exploit code was identified at time of analysis and EPSS is low at 0.24% (47th percentile), so real-world priority is better captured as MEDIUM despite the high base score.

RCE Buffer Overflow Stack Overflow Sge Plc1000 Firmware Sge Plc50 Firmware +1
NVD VulDB
CVSS 4.0
8.5
EPSS
0.2%
CVE-2025-11782 Dec 02, 13:15 HIGH This Week

Stack-based buffer overflow in Circutor SGE-PLC1000 and SGE-PLC50 firmware v9.0.2 allows authenticated attackers on an adjacent network to overflow a 64-byte stack buffer via a crafted 'meter' parameter to the ShowDownload() function, potentially achieving code execution or denial of service. The vulnerability requires low-privileged credentials and local network access, and no public exploit has been identified at time of analysis (EPSS 0.07%).

Buffer Overflow Stack Overflow Sge Plc1000 Firmware Sge Plc50 Firmware Ics
NVD VulDB
CVSS 4.0
8.5
EPSS
0.1%
CVE-2025-11781 Dec 02, 13:15 HIGH This Week

Hardcoded cryptographic key exposure in Circutor SGE-PLC1000 and SGE-PLC50 firmware v9.0.2 lets an attacker who has local access to the device recover the embedded static authentication key from the firmware image or a memory dump and then forge firmware update packages that the device accepts as genuine, effectively bypassing access controls and obtaining full administrative privileges. The weakness is access-gated rather than remotely reachable: the CVSS vector is AV:L (local) with PR:N (no authentication required once local access is achieved), and the assessed CVSS:3.1 score is 8.6-equivalent (AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). No public exploit code has been identified at time of analysis and the EPSS score is only 0.02% (percentile 6%), so this is a genuine but low-volume, physically/local-scoped risk concentrated in these two Circutor product lines at firmware version 9.0.2.

Authentication Bypass Sge Plc1000 Firmware Sge Plc50 Firmware Ics
NVD VulDB
CVSS 4.0
8.6
EPSS
0.0%
CVE-2025-11779 Dec 02, 13:15 CRITICAL Act Now

Stack-based buffer overflow in the Circutor SGE-PLC1000 and SGE-PLC50 power line communication devices running firmware v9.0.2 allows an authenticated attacker on the adjacent management/OT network to corrupt memory and potentially achieve command execution on the device. The flaw lives in the SetLan routine, which is invoked from the index.cgi web application whenever an operator submits a new LAN/network configuration; the submitted parameters are not sanitised before being copied into a fixed-size stack buffer. Exploitation requires network reachability to the device's management web interface plus a valid low-privilege session (CVSS 4.0 AV:A/PR:L; assessed CVSS 3.1 AV:A/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H), and no public exploit code or confirmed active exploitation was identified at time of analysis, although EPSS places the flaw at roughly the 83rd percentile (1.97%) of predicted exploitation activity.

Buffer Overflow Command Injection Stack Overflow Sge Plc1000 Firmware Sge Plc50 Firmware +1
NVD VulDB
CVSS 4.0
9.4
EPSS
2.0%
CVE-2025-55222 Dec 01, 16:15 HIGH This Week

Unauthenticated denial of service in Socomec DIRIS Digiware M-70 firmware 1.6.9 allows remote attackers to crash or disable the device by sending a crafted packet to the Modbus RTU-over-TCP service on TCP port 503. The flaw stems from missing authentication for a critical function (CWE-306) and can be triggered without credentials or user interaction; no public exploit code has been identified, and EPSS is low at 0.06% (20th percentile). Exploitation requires Layer-3 access to the OT network segment hosting the device, which typically sits on isolated networks, making this a genuine but bounded risk.

Authentication Bypass Denial Of Service Diris M 70 Firmware Ics
NVD VulDB
CVSS 3.1
7.5
EPSS
0.1%
CVE-2025-26858 Dec 01, 16:15 HIGH This Week

Unauthenticated denial of service in Socomec DIRIS Digiware M-70 power-monitoring devices running firmware 1.6.9, where a crafted sequence of Modbus TCP packets triggers a buffer overflow that crashes the affected service or device. Exploitation requires only network reachability to the device's Modbus TCP interface (CVSS 3.1: AV:N/AC:L/PR:N/UI:N, availability-only impact, 7.5), with no credentials or user interaction needed - authentication requirements are confirmed unauthenticated via the PR:N vector. No public exploit code or confirmed active exploitation has been identified at time of analysis, and EPSS is very low (0.09%, 26th percentile), reflecting that these devices are typically deployed on segmented OT/ICS or building-management networks rather than the public internet.

Buffer Overflow Denial Of Service Diris M 70 Firmware Ics
NVD VulDB
CVSS 3.1
7.5
EPSS
0.1%
CVE-2025-23417 Dec 01, 16:15 HIGH This Week

A single unauthenticated network packet sent to the Modbus RTU-over-TCP service of a Socomec DIRIS Digiware M-70 power-metering gateway running firmware 1.6.9 can crash the device, producing a denial-of-service condition (CVSS 3.1 base 7.5, AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H). The root cause is a missing authentication check for a critical Modbus function (CWE-306), so no credentials and no user interaction are required; exploitability is bounded only by network reachability to the Modbus port, which on these OT/building-management devices is normally confined to segmented industrial networks rather than the public internet. No public exploit code has been identified, EPSS is very low (0.06%, 19th percentile), and there is no confirmed active exploitation (no CISA KEV listing) at the time of analysis. Impact is limited to availability - no data disclosure, integrity loss, or code execution has been demonstrated.

Authentication Bypass Denial Of Service Modbus Diris M 70 Firmware Ics
NVD VulDB
CVSS 3.1
7.5
EPSS
0.1%
CVE-2025-20085 Dec 01, 16:15 MEDIUM This Month

A single specially crafted, unauthenticated packet sent to the Modbus RTU over TCP service of a Socomec DIRIS Digiware M-70 running firmware 1.6.9 can cause a denial of service and, as a secondary effect, weaken the device's credentials so that its documented default credentials are re-applied, enabling follow-on authenticated access. The flaw carries a CVSS 3.1 base score of 6.5 (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N), and the assessed vector confirms it is network-reachable, low-complexity, and requires no authentication or user interaction; the practical limiting factor is reachability, since these devices normally sit on segmented OT/building-management networks rather than the open internet. EPSS is very low (0.04%, 12th percentile), there is no CISA KEV listing, and no public exploit has been identified at time of analysis.

Authentication Bypass Denial Of Service Diris M 70 Firmware Ics
NVD VulDB
CVSS 3.1
6.5
EPSS
0.0%
EPSS 0% CVSS 7.1
HIGH This Week

Incorrect permission assignment in ABB Protection and Control IED Manager (PCM600) through version 2.14 leaves a critical application resource on the Windows engineering workstation protected by weak access controls, letting a local user read and alter protected PCM600 data with high impact to confidentiality, integrity, and availability. Exploitation requires the attacker to already have local access to the host running PCM600 - the vendor vector describes a local attack (AV:L) with high privileges required (PR:H) and high attack complexity (AC:H), while our independent assessment scores it as a low-complexity local issue requiring only low privileges (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H), so a lower-privileged local account may be sufficient in practice. No public exploit code has been identified at time of analysis and there is no CISA KEV confirmation of active exploitation; ABB published the vendor advisory (document 2NGA003170), and this is a genuine but low-urgency issue.

Abb Ics Protection And Control Ied Manager Pcm600
NVD
EPSS 0% CVSS 8.8
HIGH PATCH This Week

SQL injection in Delta Electronics DIAEnergie before version 1.11.00.022 allows an attacker holding a valid low-privileged account to read from and write to the platform's backend database, putting the confidentiality, integrity, and availability of its operational data at risk. The flaw is network reachable (AV:N), requires only a low-privileged session (PR:L), and needs no user interaction; it is not confirmed as actively exploited (no CISA KEV listing) and no public exploit code has been identified at time of analysis. Delta released the fix in advisory PCSA-2026-00014 alongside a batch of related DIAEnergie flaws, including an authentication bypass (CVE-2026-78308) that could supply the very credentials this SQL injection depends on.

SQLi Diaenergie Deltaww +1
NVD VulDB
EPSS 0% CVSS 5.3
MEDIUM This Month

An authenticated user with Viewer privileges can exploit a relative path traversal flaw in the data import functionality of Satel Netco Design versions prior to v2.1.7 to probe file paths outside the intended import directory and use application responses as an existence oracle for files on the host system. The vulnerability is network-reachable (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N) but requires valid low-privilege credentials, and its impact is confined to low confidentiality loss via file-existence inference; it does not disclose file contents, allow writes, or enable code execution. No public exploit identified at time of analysis.

Path Traversal Ics Satel Netco Design
NVD GitHub
EPSS 0% CVSS 4.3
MEDIUM PATCH This Month

An authorization bypass through a user-controlled key (CWE-639) exists in Delta Electronics DIAEnergie versions before 1.11.00.022, allowing a low-privilege authenticated user to reference objects or records belonging to other users and read data they are not authorized to access. The flaw is network-reachable (AV:N) and requires no victim interaction (UI:N), but exploitation is gated behind a valid low-privilege session (PR:L), so realistic abuse is limited to malicious insiders, legitimate users exceeding their privileges, or attackers who have already obtained credentials; impact is bounded to confidentiality (C:L) with no integrity or availability effect, giving a CVSS 3.1 base score of 4.3. No public exploit code has been identified at time of analysis and the issue is not confirmed actively exploited (CISA KEV), making this a genuine but low-priority weakness rather than a high-severity emergency.

Authentication Bypass Diaenergie Deltaww +1
NVD VulDB
EPSS 0% CVSS 8.5
HIGH This Week

Heap-based buffer overflow in the management interface of Circutor SGE-PLC1000 and SGE-PLC50 concentrators running firmware 9.0.2 lets an attacker who can reach the device over the network and authenticate with low privileges corrupt heap memory by supplying an oversized 'meter' parameter, yielding high confidentiality and availability impact without any user interaction. The flaw sits in ShowSupervisorParameters(), which passes the unbounded 'meter' value obtained through GetParameter(meter) into a fixed-size buffer via sprintf(). No public exploit code has been identified at time of analysis, and the EPSS score is low at 0.06% (20th percentile), so risk is driven primarily by exposure of the concentrator's management interface rather than by observed exploitation activity.

Buffer Overflow Heap Overflow Sge Plc1000 Firmware +2
NVD VulDB
EPSS 0% CVSS 8.5
HIGH This Week

Authenticated command injection in Circutor SGE-PLC1000 and SGE-PLC50 gateways running firmware 9.0.2 lets a low-privilege user of the management interface run arbitrary operating-system commands through the GetDNS(), CheckPing() and TraceRoute() diagnostic functions, which pass unsanitized input to the underlying shell. The vendor scores this 8.5 under CVSS 4.0 with PR:L and UI:A, and our independent CVSS 3.1 assessment agrees on high confidentiality, integrity and availability impact while emphasizing that exploitation is gated behind a valid authenticated session and the ICS deployment context. EPSS is low at 0.29% (52nd percentile), the CVE is not in CISA KEV, and no public exploit code was identified at time of analysis, so this is a genuine but access-gated flaw rather than an internet-exposed, unauthenticated remote compromise.

Command Injection Sge Plc1000 Firmware Sge Plc50 Firmware +1
NVD VulDB
EPSS 0% CVSS 8.5
HIGH This Week

Authenticated adjacent-network attackers can execute arbitrary shell commands on Circutor SGE-PLC1000 and SGE-PLC50 devices running firmware 9.0.2 by supplying shell metacharacters in the newPassword parameter of SetUserPassword(). The flaw combines an unsanitized sprintf() path into system() with CWE-121 stack-based buffer overflow conditions, requiring valid low-privilege access on the same network segment and no user interaction; it enables high confidentiality and availability impact and potential scope change onto subsequent systems. No public exploit code or CISA KEV listing was identified at time of analysis, and EPSS is 0.07% (22nd percentile).

Buffer Overflow Command Injection Stack Overflow +3
NVD VulDB
EPSS 0% CVSS 8.5
HIGH This Week

Stack-based buffer overflow in Circutor SGE-PLC1000 and SGE-PLC50 smart-grid PLC concentrators running firmware v9.0.2 allows an attacker to corrupt memory and potentially achieve code execution or a denial-of-service condition by supplying an excessively long 'meter' parameter that is copied into a fixed-size stack buffer via sprintf() inside the ShowMeterDatabase() function. Exploitation requires the attacker to already reside on the adjacent network (same LAN/OT segment) and to hold valid low-privilege credentials, since the parameter is reached through an authenticated management function; the CVE carries a base CVSS of 8.5, though our independent assessment (CVSS 3.1 AV:A/PR:L/S:C/C:H/I:L/A:H) confirms that reachability and authentication prerequisites meaningfully narrow practical exposure. EPSS is very low at 0.07% (22nd percentile), no public exploit code has been identified at time of analysis, and the vulnerability is not listed in CISA KEV, so there is no indication of active exploitation.

Buffer Overflow Stack Overflow Sge Plc1000 Firmware +2
NVD VulDB
EPSS 0% CVSS 8.5
HIGH This Week

A stack-based buffer overflow in the AddEvent() function of Circutor SGE-PLC1000 and SGE-PLC50 power-line communication devices running firmware v9.0.2 lets an attacker with adjacent-network access and valid low-privilege credentials overwrite a fixed 48-byte stack buffer using an over-long username, causing memory corruption and potentially remote code execution. Per the CVSS 4.0 vector (8.5) the attacker requires both adjacency to the same L2/management or substation segment (AV:A) and authentication (PR:L), with no user interaction, though exploit reliability for full code execution is described only as 'possible' and may be uncertain. No public exploit code was identified at time of analysis and EPSS is low at 0.24% (47th percentile), so real-world priority is better captured as MEDIUM despite the high base score.

RCE Buffer Overflow Stack Overflow +3
NVD VulDB
EPSS 0% CVSS 8.5
HIGH This Week

Stack-based buffer overflow in Circutor SGE-PLC1000 and SGE-PLC50 firmware v9.0.2 allows authenticated attackers on an adjacent network to overflow a 64-byte stack buffer via a crafted 'meter' parameter to the ShowDownload() function, potentially achieving code execution or denial of service. The vulnerability requires low-privileged credentials and local network access, and no public exploit has been identified at time of analysis (EPSS 0.07%).

Buffer Overflow Stack Overflow Sge Plc1000 Firmware +2
NVD VulDB
EPSS 0% CVSS 8.6
HIGH This Week

Hardcoded cryptographic key exposure in Circutor SGE-PLC1000 and SGE-PLC50 firmware v9.0.2 lets an attacker who has local access to the device recover the embedded static authentication key from the firmware image or a memory dump and then forge firmware update packages that the device accepts as genuine, effectively bypassing access controls and obtaining full administrative privileges. The weakness is access-gated rather than remotely reachable: the CVSS vector is AV:L (local) with PR:N (no authentication required once local access is achieved), and the assessed CVSS:3.1 score is 8.6-equivalent (AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). No public exploit code has been identified at time of analysis and the EPSS score is only 0.02% (percentile 6%), so this is a genuine but low-volume, physically/local-scoped risk concentrated in these two Circutor product lines at firmware version 9.0.2.

Authentication Bypass Sge Plc1000 Firmware Sge Plc50 Firmware +1
NVD VulDB
EPSS 2% CVSS 9.4
CRITICAL Act Now

Stack-based buffer overflow in the Circutor SGE-PLC1000 and SGE-PLC50 power line communication devices running firmware v9.0.2 allows an authenticated attacker on the adjacent management/OT network to corrupt memory and potentially achieve command execution on the device. The flaw lives in the SetLan routine, which is invoked from the index.cgi web application whenever an operator submits a new LAN/network configuration; the submitted parameters are not sanitised before being copied into a fixed-size stack buffer. Exploitation requires network reachability to the device's management web interface plus a valid low-privilege session (CVSS 4.0 AV:A/PR:L; assessed CVSS 3.1 AV:A/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H), and no public exploit code or confirmed active exploitation was identified at time of analysis, although EPSS places the flaw at roughly the 83rd percentile (1.97%) of predicted exploitation activity.

Buffer Overflow Command Injection Stack Overflow +3
NVD VulDB
EPSS 0% CVSS 7.5
HIGH This Week

Unauthenticated denial of service in Socomec DIRIS Digiware M-70 firmware 1.6.9 allows remote attackers to crash or disable the device by sending a crafted packet to the Modbus RTU-over-TCP service on TCP port 503. The flaw stems from missing authentication for a critical function (CWE-306) and can be triggered without credentials or user interaction; no public exploit code has been identified, and EPSS is low at 0.06% (20th percentile). Exploitation requires Layer-3 access to the OT network segment hosting the device, which typically sits on isolated networks, making this a genuine but bounded risk.

Authentication Bypass Denial Of Service Diris M 70 Firmware +1
NVD VulDB
EPSS 0% CVSS 7.5
HIGH This Week

Unauthenticated denial of service in Socomec DIRIS Digiware M-70 power-monitoring devices running firmware 1.6.9, where a crafted sequence of Modbus TCP packets triggers a buffer overflow that crashes the affected service or device. Exploitation requires only network reachability to the device's Modbus TCP interface (CVSS 3.1: AV:N/AC:L/PR:N/UI:N, availability-only impact, 7.5), with no credentials or user interaction needed - authentication requirements are confirmed unauthenticated via the PR:N vector. No public exploit code or confirmed active exploitation has been identified at time of analysis, and EPSS is very low (0.09%, 26th percentile), reflecting that these devices are typically deployed on segmented OT/ICS or building-management networks rather than the public internet.

Buffer Overflow Denial Of Service Diris M 70 Firmware +1
NVD VulDB
EPSS 0% CVSS 7.5
HIGH This Week

A single unauthenticated network packet sent to the Modbus RTU-over-TCP service of a Socomec DIRIS Digiware M-70 power-metering gateway running firmware 1.6.9 can crash the device, producing a denial-of-service condition (CVSS 3.1 base 7.5, AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H). The root cause is a missing authentication check for a critical Modbus function (CWE-306), so no credentials and no user interaction are required; exploitability is bounded only by network reachability to the Modbus port, which on these OT/building-management devices is normally confined to segmented industrial networks rather than the public internet. No public exploit code has been identified, EPSS is very low (0.06%, 19th percentile), and there is no confirmed active exploitation (no CISA KEV listing) at the time of analysis. Impact is limited to availability - no data disclosure, integrity loss, or code execution has been demonstrated.

Authentication Bypass Denial Of Service Modbus +2
NVD VulDB
EPSS 0% CVSS 6.5
MEDIUM This Month

A single specially crafted, unauthenticated packet sent to the Modbus RTU over TCP service of a Socomec DIRIS Digiware M-70 running firmware 1.6.9 can cause a denial of service and, as a secondary effect, weaken the device's credentials so that its documented default credentials are re-applied, enabling follow-on authenticated access. The flaw carries a CVSS 3.1 base score of 6.5 (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N), and the assessed vector confirms it is network-reachable, low-complexity, and requires no authentication or user interaction; the practical limiting factor is reachability, since these devices normally sit on segmented OT/building-management networks rather than the open internet. EPSS is very low (0.04%, 12th percentile), there is no CISA KEV listing, and no public exploit has been identified at time of analysis.

Authentication Bypass Denial Of Service Diris M 70 Firmware +1