Attack ChainAIDerived
Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain
-
AccessReach Modbus TCP service on OT network
-
ExploitSend crafted unauthenticated Modbus packet sequence
-
ExecutionTrigger buffer overflow in parser
-
ImpactCrash device (denial of service)
Vulnerability Assessment
| Weakness |
CWE
OWASP Top 10:2025
A05:2025 - Injection
ASVS 5.0
V2 - Validation and Business Logic Input validation, allowlisting
|
| Exploitation Conditions | Exploitation requires network reachability to the Modbus TCP functionality of a Socomec DIRIS Digiware M-70 running firmware 1.6.9; the attacker sends a specially crafted sequence of unauthenticated Modbus packets, so no credentials or user interaction are needed. The main limiting factor is network exposure: these devices are normally deployed on segmented OT/ICS or building-management networks, so realistic risk depends on whether the Modbus TCP port (commonly 502) is reachable by the attacker. Impact is limited to denial of service (device crash/unavailability) with no data disclosure or code execution. |
| Impact | All signals point to a genuine but bounded (availability-only) risk. The CVSS 3.1 vector (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H) and the description agree: an unauthenticated remote attacker can crash the device over the network by sending crafted Modbus TCP packets, with no confidentiality or integrity impact - the 7.5 score is driven entirely by A:H. EPSS is very low at 0.09% (26th percentile), and there is no CISA KEV listing and no public exploit identified at time of analysis, so widespread opportunistic exploitation is not indicated. The finding was discovered and reported by Cisco Talos (talos-cna@cisco.com) with a dedicated vulnerability report, and Socomec has published a vendor advisory PDF (dated 2025-10-01), lending high credibility to the technical claims. This is a real, unauthenticated DoS against an industrial power-monitoring device where availability is operationally meaningful, but it is not a confidentiality/integrity/RCE issue and shows no signs of active exploitation - treat as a moderate ICS availability risk to be patched on normal cycles, prioritized higher only for exposed/critical deployments. No signal is strongly conflicting; the low EPSS is consistent with a niche ICS product and DoS-only impact rather than mass exploitation. |
| Exploit ScenarioDerived | An attacker with network reachability to the device's Modbus TCP service (typically port 502) sends a crafted sequence of unauthenticated packets that triggers a buffer overflow in the M-70's Modbus parser, crashing the device and denying power-monitoring/metering telemetry. No authentication or user interaction is required and attack complexity is low, though the attacker must first reach the (normally segmented) OT/ICS network. No public proof-of-concept exploit code was identified at time of analysis. |
Get an e-mail when this CVE is exploited, patched or re-scored. Free account.
Alert meAnalysisAIv2 – Sep 26, 2026
Unauthenticated denial of service in Socomec DIRIS Digiware M-70 power-monitoring devices running firmware 1.6.9, where a crafted sequence of Modbus TCP packets triggers a buffer overflow that crashes the affected service or device. Exploitation requires only network reachability to the device's Modbus TCP interface (CVSS 3.1: AV:N/AC:L/PR:N/UI:N, availability-only impact, 7.5), with no credentials or user interaction needed - authentication requirements are confirmed unauthenticated via the PR:N vector. No public exploit code or confirmed active exploitation has been identified at time of analysis, and EPSS is very low (0.09%, 26th percentile), reflecting that these devices are typically deployed on segmented OT/ICS or building-management networks rather than the public internet.
Earlier versions of this analysis (1)
RemediationAI
Apply the firmware update published by Socomec in its advisory for CVE-2025-26858 (see the Socomec product security document at socomec.fr and the Talos report TALOS-2025-2152); patch availability is confirmed per the vendor advisory, though a specific fixed firmware version number is not given in the data provided, so operators should consult the advisory directly for the exact target release. Where immediate upgrade is not possible, the most effective compensating control is to restrict network access to the Modbus TCP service (commonly port 502) using firewall/ACL rules or OT-aware segmentation so only trusted engineering workstations and controllers can reach the device - the trade-off is that legitimate SCADA/HMI polling must be re-permitted by explicit rule, and misconfigured rules can disrupt monitoring. If Modbus TCP is not operationally required, disable the service entirely, at the cost of losing Modbus-based integration. For deployments that cannot segment, place devices behind a Modbus-aware firewall or protocol gateway that filters malformed or oversized function-code payloads. Because the failure mode is a crash/DoS, add availability monitoring and alerting for unexpected device restarts to detect exploitation attempts, and treat repeated crashes as a sign of attack rather than hardware fault. Note that Modbus TCP itself provides no authentication, so credential-based mitigations are not applicable here.
Affected VersionsENISA
Affected Packages
Source: OSV (Open Source Vulnerabilities)
Affects your stack
Affects 1 package in euvd
Checking this CVE against your own stacks and servers is part of the Basic plan and up.
Technical ContextAI · show details
The affected component is the Modbus TCP server implemented in Socomec DIRIS Digiware M-70 firmware 1.6.9 (CPE cpe:2.3:o:socomec:diris_m-70_firmware:1.6.9). Modbus TCP is a widely used industrial protocol that carries Modbus function codes over TCP, conventionally on port 502, and provides no native authentication or encryption - which is why the crafted packets reach the vulnerable parsing routine without any credential check. The root cause is classified as CWE-20 (Improper Input Validation): the firmware fails to correctly validate the length or structure of incoming Modbus request fields before copying data into a fixed-size memory buffer, producing the described buffer overflow. Notably, the assigned CWE is the general input-validation class rather than a memory-corruption-specific CWE (e.g., CWE-120/121/122), so the exact overflow primitive and whether corruption can extend beyond denial of service is not fully established from the available data; the assessed impact is bounded to availability (device crash/reboot and loss of monitoring/control telemetry) with no confidentiality or integrity effect. This is a common weakness pattern in embedded OT/ICS device firmware, where protocol stacks are frequently re-implemented without defensive memory handling.
Know when Diris M 70 Firmware gets its next vulnerability
- Watch products and get an email when something new is published
- Check this CVE against your own stack and servers
- Exploit and PoC references, threat intelligence from 22 sources
No credit card · 7-day full trial
Severity by source
AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Unauthenticated crafted Modbus TCP packets over the network with low complexity (AV:N/AC:L/PR:N/UI:N); impact is availability-only denial of service, so C:N/I:N/A:H.
Primary rating from NVD.
CVSS VectorNVD
Lifecycle Timeline
3DescriptionNVD
A buffer overflow vulnerability exists in the Modbus TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted set of network packets can lead to denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.
Executive ViewAI
A high-severity vulnerability in Socomec DIRIS Digiware M-70 devices allows unauthenticated attackers to cause service disruptions through specially crafted network packets. Organizations operating these industrial control systems face potential operational downtime, as no patch is currently available from the vendor.
Implement network segmentation to restrict Modbus TCP (port 502) access to trusted administrative networks only; deploy firewall rules blocking untrusted inbound connections to affected devices; monitor network traffic for anomalous packet patterns targeting Modbus TCP; consider temporarily disabling Modbus TCP if not operationally critical; implement intrusion detection signatures for malformed Modbus packets; isolate affected devices on air-gapped or tightly controlled networks pending vendor patch availability.
Threat Intelligence Overview
How this decision was reached
The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.
What every action level means
SSVC AssessmentENISA
Priority Score
Attack Technique
A buffer overflow occurs when a program writes more data to a memory buffer than it was allocated to hold, causing the excess data to spill into adjacent memory regions.
Denial of Service attacks render applications or systems unavailable by overwhelming resources or triggering failure conditions.
More in Diris M 70 Firmware
View allA cross-site request forgery (csrf) vulnerability exists in the WEBVIEW-M functionality of Socomec DIRIS Digiware M-70 1
Unauthenticated denial of service in Socomec DIRIS Digiware M-70 firmware 1.6.9 allows remote attackers to crash or disa
Unauthenticated denial of service in Socomec DIRIS Digiware M-70 firmware 1.6.9 lets any host that can reach the device'
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiwa
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiwa
A single unauthenticated network packet sent to the Modbus RTU-over-TCP service of a Socomec DIRIS Digiware M-70 power-m
A denial of service vulnerability exists in the Modbus TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A special
A cleartext transmission vulnerability exists in the WEBVIEW-M functionality of Socomec DIRIS Digiware M-70 1.6.9. A spe
A single specially crafted, unauthenticated packet sent to the Modbus RTU over TCP service of a Socomec DIRIS Digiware M
A denial of service vulnerability exists in the Modbus TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A special
EUVD-2025-200030
NVD
CVE.org
EPSS
VulDB
GitHub PoC