Socomec
Monthly
Socomec DIRIS A-40 power monitoring devices contain an authentication bypass vulnerability in their HTTP API that allows network-adjacent attackers to gain unauthorized access without credentials. The vulnerability affects all versions of the DIRIS A-40 product due to lack of authentication enforcement on the web API listening on TCP port 80, enabling attackers to read sensitive data, modify configurations, and potentially disrupt power monitoring operations. This is a moderate-severity flaw (CVSS 6.3) with low attack complexity that poses real risk in industrial/operational technology environments where these devices are deployed.
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP USB Function functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted network packet can lead to a denial of service. An attacker can send an unauthenticated packet to trigger this vulnerability.This vulnerability is specific to the malicious message sent via Modbus RTU over TCP on port 503.
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP USB Function functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted network packet can lead to a denial of service. An attacker can send an unauthenticated packet to trigger this vulnerability.This vulnerability is specific to the malicious message sent via Modbus TCP over port 502.
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a single Modbus TCP message to port 503 using the Write Single Register function code (6) to write the value 1 to register 4352. This action changes the Modbus address to 15. After this message is sent, the device will be in a denial-of-service state.
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a sequence of Modbus RTU over TCP messages to port 503 using the Write Single Register function code (6). The attack sequence begins with a message to register 58112 with a value of 1000, indicating that a configuration change will follow. Next, a message is sent to register 29440 with a value corresponding to the new Modbus address to be configured. Finally, a message to register 57856 with a value of 161 commits the configuration change. After this configuration change, the device will be in a denial-of-service state.
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a single Modbus TCP message to port 502 using the Write Single Register function code (6) to write the value 1 to register 4352. This action changes the Modbus address to 15. After this message is sent, the device will be in a denial-of-service state.
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a sequence of Modbus TCP messages to port 502 using the Write Single Register function code (6). The attack sequence begins with a message to register 58112 with a value of 1000, indicating that a configuration change will follow. Next, a message is sent to register 29440 with a value corresponding to the new Modbus address to be configured. Finally, a message to register 57856 with a value of 161 commits the configuration change. After this configuration change, the device will be in a denial-of-service state.
A buffer overflow vulnerability exists in the Modbus TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted set of network packets can lead to denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.
A denial of service vulnerability exists in the Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted network packet can lead to denial of service. An attacker can send an unauthenticated packet to trigger this vulnerability.
A denial of service vulnerability exists in the Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted network packet can lead to denial of service and weaken credentials resulting in default documented credentials being applied to the device. An attacker can send an unauthenticated packet to trigger this vulnerability.
A cross-site request forgery (csrf) vulnerability exists in the WEBVIEW-M functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted HTTP request can lead to unauthorized access. An attacker can stage a malicious webpage to trigger this vulnerability.
A denial of service vulnerability exists in the Modbus TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted network packet can lead to denial of service and weaken credentials resulting in default documented credentials being applied to the device. An attacker can send an unauthenticated packet to trigger this vulnerability.
A cleartext transmission vulnerability exists in the WEBVIEW-M functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted HTTP request can lead to a disclosure of sensitive information. An attacker can sniff network traffic to trigger this vulnerability.
A denial of service vulnerability exists in the Modbus TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted network packet can lead to denial of service. An attacker can send an unauthenticated packet to trigger this vulnerability.
The web application that owns the device clearly stores the credentials within the user management section. Rated high severity (CVSS 7.5), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
Thanks to the weaknesses that the web application has at the user management level, an attacker could obtain the information from the headers that is necessary to create specially designed URLs and. Rated high severity (CVSS 8.8), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
Persistent cross-site scripting (XSS) in the web application of MOD3GP-SY-120K allows an authenticated remote attacker to introduce arbitrary JavaScript by injecting an XSS payload into the field. Rated medium severity (CVSS 5.4), this vulnerability is remotely exploitable, low attack complexity. No vendor patch available.
A potential attacker with or without (cookie theft) access to the device would be able to include malicious code (XSS) when uploading new device configuration that could affect the intended function. Rated medium severity (CVSS 6.1), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
Sending some requests in the web application of the vulnerable device allows information to be obtained due to the lack of security in the authentication process. Rated high severity (CVSS 7.5), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
Session management within the web application is incorrect and allows attackers to steal session cookies to perform a multitude of actions that the web app allows on the device. Rated critical severity (CVSS 9.8), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
The absence of filters when loading some sections in the web application of the vulnerable device allows potential attackers to inject malicious code that will be interpreted when a legitimate user. Rated high severity (CVSS 8.8), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
SOCOMEC MODULYS GP Netvision versions 7.20 and prior lack strong encryption for credentials on HTTP connections, which could result in threat actors obtaining sensitive information. Rated high severity (CVSS 7.5), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
An issue was discovered in Socomec REMOTE VIEW PRO 2.0.41.4. Rated medium severity (CVSS 5.4), this vulnerability is remotely exploitable, low attack complexity. No vendor patch available.
An issue was discovered in the firmware update form in Socomec REMOTE VIEW PRO 2.0.41.4. Rated high severity (CVSS 8.8), this vulnerability is remotely exploitable, low attack complexity. No vendor patch available.
Password disclosure in the web interface on socomec DIRIS A-40 devices before 48250501 allows a remote attacker to get full access to a device via the /password.jsn URI. Rated critical severity (CVSS 9.8), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
Socomec DIRIS A-40 power monitoring devices contain an authentication bypass vulnerability in their HTTP API that allows network-adjacent attackers to gain unauthorized access without credentials. The vulnerability affects all versions of the DIRIS A-40 product due to lack of authentication enforcement on the web API listening on TCP port 80, enabling attackers to read sensitive data, modify configurations, and potentially disrupt power monitoring operations. This is a moderate-severity flaw (CVSS 6.3) with low attack complexity that poses real risk in industrial/operational technology environments where these devices are deployed.
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP USB Function functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted network packet can lead to a denial of service. An attacker can send an unauthenticated packet to trigger this vulnerability.This vulnerability is specific to the malicious message sent via Modbus RTU over TCP on port 503.
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP USB Function functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted network packet can lead to a denial of service. An attacker can send an unauthenticated packet to trigger this vulnerability.This vulnerability is specific to the malicious message sent via Modbus TCP over port 502.
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a single Modbus TCP message to port 503 using the Write Single Register function code (6) to write the value 1 to register 4352. This action changes the Modbus address to 15. After this message is sent, the device will be in a denial-of-service state.
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a sequence of Modbus RTU over TCP messages to port 503 using the Write Single Register function code (6). The attack sequence begins with a message to register 58112 with a value of 1000, indicating that a configuration change will follow. Next, a message is sent to register 29440 with a value corresponding to the new Modbus address to be configured. Finally, a message to register 57856 with a value of 161 commits the configuration change. After this configuration change, the device will be in a denial-of-service state.
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a single Modbus TCP message to port 502 using the Write Single Register function code (6) to write the value 1 to register 4352. This action changes the Modbus address to 15. After this message is sent, the device will be in a denial-of-service state.
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a sequence of Modbus TCP messages to port 502 using the Write Single Register function code (6). The attack sequence begins with a message to register 58112 with a value of 1000, indicating that a configuration change will follow. Next, a message is sent to register 29440 with a value corresponding to the new Modbus address to be configured. Finally, a message to register 57856 with a value of 161 commits the configuration change. After this configuration change, the device will be in a denial-of-service state.
A buffer overflow vulnerability exists in the Modbus TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted set of network packets can lead to denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.
A denial of service vulnerability exists in the Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted network packet can lead to denial of service. An attacker can send an unauthenticated packet to trigger this vulnerability.
A denial of service vulnerability exists in the Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted network packet can lead to denial of service and weaken credentials resulting in default documented credentials being applied to the device. An attacker can send an unauthenticated packet to trigger this vulnerability.
A cross-site request forgery (csrf) vulnerability exists in the WEBVIEW-M functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted HTTP request can lead to unauthorized access. An attacker can stage a malicious webpage to trigger this vulnerability.
A denial of service vulnerability exists in the Modbus TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted network packet can lead to denial of service and weaken credentials resulting in default documented credentials being applied to the device. An attacker can send an unauthenticated packet to trigger this vulnerability.
A cleartext transmission vulnerability exists in the WEBVIEW-M functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted HTTP request can lead to a disclosure of sensitive information. An attacker can sniff network traffic to trigger this vulnerability.
A denial of service vulnerability exists in the Modbus TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted network packet can lead to denial of service. An attacker can send an unauthenticated packet to trigger this vulnerability.
The web application that owns the device clearly stores the credentials within the user management section. Rated high severity (CVSS 7.5), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
Thanks to the weaknesses that the web application has at the user management level, an attacker could obtain the information from the headers that is necessary to create specially designed URLs and. Rated high severity (CVSS 8.8), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
Persistent cross-site scripting (XSS) in the web application of MOD3GP-SY-120K allows an authenticated remote attacker to introduce arbitrary JavaScript by injecting an XSS payload into the field. Rated medium severity (CVSS 5.4), this vulnerability is remotely exploitable, low attack complexity. No vendor patch available.
A potential attacker with or without (cookie theft) access to the device would be able to include malicious code (XSS) when uploading new device configuration that could affect the intended function. Rated medium severity (CVSS 6.1), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
Sending some requests in the web application of the vulnerable device allows information to be obtained due to the lack of security in the authentication process. Rated high severity (CVSS 7.5), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
Session management within the web application is incorrect and allows attackers to steal session cookies to perform a multitude of actions that the web app allows on the device. Rated critical severity (CVSS 9.8), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
The absence of filters when loading some sections in the web application of the vulnerable device allows potential attackers to inject malicious code that will be interpreted when a legitimate user. Rated high severity (CVSS 8.8), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
SOCOMEC MODULYS GP Netvision versions 7.20 and prior lack strong encryption for credentials on HTTP connections, which could result in threat actors obtaining sensitive information. Rated high severity (CVSS 7.5), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
An issue was discovered in Socomec REMOTE VIEW PRO 2.0.41.4. Rated medium severity (CVSS 5.4), this vulnerability is remotely exploitable, low attack complexity. No vendor patch available.
An issue was discovered in the firmware update form in Socomec REMOTE VIEW PRO 2.0.41.4. Rated high severity (CVSS 8.8), this vulnerability is remotely exploitable, low attack complexity. No vendor patch available.
Password disclosure in the web interface on socomec DIRIS A-40 devices before 48250501 allows a remote attacker to get full access to a device via the /password.jsn URI. Rated critical severity (CVSS 9.8), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.