Attack ChainAIDerived
Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain
-
AccessReach device Modbus port 503
-
ExploitSend crafted Modbus RTU-over-TCP packet
-
ImpactDevice denial of service
Vulnerability Assessment
| Weakness |
CWE
OWASP Top 10:2025
A07:2025 - Authentication Failures
ASVS 5.0
V6 - Authentication Authentication required for critical functions
MITRE ATT&CK
1 technique across 1 tactic: Initial Access The technique list with ATT&CK links and the kill-chain view is part of the Basic plan and up. |
| Exploitation Conditions | Exploitation requires network reachability to the DIRIS Digiware M-70's Modbus RTU-over-TCP service specifically on TCP port 503; the standard Modbus TCP path is not the stated vector - the malicious message must be delivered via Modbus RTU over TCP on port 503. No authentication, credentials, or user interaction are needed (PR:N/UI:N). Limiting factors: the attacker must have Layer-3 access to the OT network segment hosting the device, and these industrial metering devices are typically deployed on isolated/segmented networks rather than exposed to the internet, which meaningfully constrains real-world reach despite the AV:N rating. |
| Impact | This is a genuine but bounded risk. The CVSS 3.1 vector (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, base 7.5) accurately reflects a remote, unauthenticated, low-complexity availability-only attack - there is no confidentiality or integrity impact, so the 'HIGH' rating is driven entirely by A:H denial of service. Signals are internally consistent and point AWAY from urgent widespread exploitation: EPSS is 0.06% (20th percentile), the CVE is NOT in CISA KEV, and no public exploit code is referenced by the Talos advisory. The apparent tension between CWE-306 (Missing Authentication for Critical Function) and the actual outcome is worth noting - the flaw is really an unauthenticated DoS, not a privilege/authentication bypass that yields access; the impact metrics correctly show only A:H. Net: this is a real, patch-worthy defect for operators of this specific device, but not a mass-exploitation priority - the primary concern is availability of an industrial power-monitoring/metering device in an OT/ICS context where uptime matters, and where such devices are typically expected to sit on segmented, non-internet-facing networks. |
| Exploit ScenarioDerived | An attacker with network reachability to the DIRIS Digiware M-70's Modbus RTU-over-TCP service on port 503 sends a single specially crafted, unauthenticated packet that crashes or hangs the device's Modbus handling, denying service. No authentication, user interaction, or special privileges are required. No public proof-of-concept is identified in the provided data, though Talos (the reporting CNA) has published a detailed vulnerability report. |
Get an e-mail when this CVE is exploited, patched or re-scored. Free account.
Alert meAnalysisAIv2 – Sep 26, 2026
Unauthenticated denial of service in Socomec DIRIS Digiware M-70 firmware 1.6.9 allows remote attackers to crash or disable the device by sending a crafted packet to the Modbus RTU-over-TCP service on TCP port 503. The flaw stems from missing authentication for a critical function (CWE-306) and can be triggered without credentials or user interaction; no public exploit code has been identified, and EPSS is low at 0.06% (20th percentile). Exploitation requires Layer-3 access to the OT network segment hosting the device, which typically sits on isolated networks, making this a genuine but bounded risk.
Earlier versions of this analysis (1)
RemediationAI
No vendor-released patch identified at time of analysis; consult the vendor advisory (https://talosintelligence.com/vulnerability_reports/TALOS-2025-2251) for any firmware updates. As a compensating control, restrict network access to TCP port 503 on the device to only trusted management hosts via firewall rules or ACLs; this blocks the attack vector but requires careful maintenance to avoid disrupting legitimate Modbus RTU-over-TCP communications. If the Modbus RTU-over-TCP USB Function is not needed, disable it entirely, though this may impact monitoring or integration workflows. Segment the OT network so that the device is not reachable from untrusted networks, and monitor for malformed Modbus packets. Restarting the device may temporarily recover from a denial-of-service condition but does not remediate the underlying flaw.
Affected VersionsENISA
Affected Packages
Source: OSV (Open Source Vulnerabilities)
Affects your stack
Affects 1 package in euvd
Checking this CVE against your own stacks and servers is part of the Basic plan and up.
Technical ContextAI · show details
The Socomec DIRIS Digiware M-70 is an industrial metering device. The vulnerability resides in its Modbus TCP and Modbus RTU over TCP USB Function functionality. While standard Modbus TCP uses port 502, this flaw is specifically triggered via Modbus RTU over TCP on port 503. The root cause is CWE-306: Missing Authentication for Critical Function, meaning the device processes a specially crafted network packet without requiring authentication, leading to a denial of service. The affected firmware is identified by CPE cpe:2.3:o:socomec:diris_m-70_firmware:1.6.9:*:*:*:*:*:*:*.
Know when Diris M 70 Firmware gets its next vulnerability
- Watch products and get an email when something new is published
- Check this CVE against your own stack and servers
- Exploit and PoC references, threat intelligence from 22 sources
No credit card · 7-day full trial
Severity by source
AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Unauthenticated crafted packet over Modbus RTU-over-TCP port 503 (AV:N/AC:L/PR:N/UI:N) causing only denial of service (C:N/I:N/A:H), no scope change.
Primary rating from NVD.
CVSS VectorNVD
Lifecycle Timeline
3DescriptionNVD
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP USB Function functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted network packet can lead to a denial of service. An attacker can send an unauthenticated packet to trigger this vulnerability.This vulnerability is specific to the malicious message sent via Modbus RTU over TCP on port 503.
Executive ViewAI
Socomec DIRIS Digiware M-70 devices running version 1.6.9 are vulnerable to unauthenticated denial of service attacks via malicious Modbus TCP packets, potentially disrupting critical power distribution monitoring and control. Organizations using these devices face service disruption risk until patches become available, with no known workaround currently provided by the vendor.
Implement network segmentation to isolate affected devices from untrusted networks; restrict access to port 503 using firewall rules or WAF policies to authorized Modbus clients only; deploy network-based IDS/IPS signatures to detect and block malformed Modbus RTU packets; disable Modbus RTU over TCP functionality if not operationally required; increase monitoring and alerting for service availability of affected DIRIS devices.
Threat Intelligence Overview
How this decision was reached
The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.
What every action level means
SSVC AssessmentENISA
Priority Score
Attack Technique
Authentication bypass attacks exploit flaws in the verification mechanisms that control access to systems and applications.
Denial of Service attacks render applications or systems unavailable by overwhelming resources or triggering failure conditions.
More in Diris M 70 Firmware
View allA cross-site request forgery (csrf) vulnerability exists in the WEBVIEW-M functionality of Socomec DIRIS Digiware M-70 1
Unauthenticated denial of service in Socomec DIRIS Digiware M-70 power-monitoring devices running firmware 1.6.9, where
Unauthenticated denial of service in Socomec DIRIS Digiware M-70 firmware 1.6.9 lets any host that can reach the device'
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiwa
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiwa
A single unauthenticated network packet sent to the Modbus RTU-over-TCP service of a Socomec DIRIS Digiware M-70 power-m
A denial of service vulnerability exists in the Modbus TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A special
A cleartext transmission vulnerability exists in the WEBVIEW-M functionality of Socomec DIRIS Digiware M-70 1.6.9. A spe
A single specially crafted, unauthenticated packet sent to the Modbus RTU over TCP service of a Socomec DIRIS Digiware M
A denial of service vulnerability exists in the Modbus TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A special
EUVD-2025-200035
NVD
CVE.org
EPSS
VulDB
GitHub PoC
Exploit-DB