Attack ChainAIDerived
Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain
-
AccessReach device Modbus TCP port 502
-
DeliveryCraft malicious Modbus packet
-
ExploitSend unauthenticated to parser
-
ExecutionTrigger fault/crash
-
ImpactDevice denial of service
Vulnerability Assessment
| Weakness |
CWE
OWASP Top 10:2025
A07:2025 - Authentication Failures
ASVS 5.0
V6 - Authentication Authentication required for critical functions
MITRE ATT&CK
1 technique across 1 tactic: Initial Access The technique list with ATT&CK links and the kill-chain view is part of the Basic plan and up. |
| Exploitation Conditions | Exploitation requires network reachability to the DIRIS Digiware M-70 (firmware 1.6.9) Modbus TCP service on port 502; the flaw is specific to malicious messages sent via Modbus TCP over that port. No authentication, credentials, or user interaction are needed (PR:N/UI:N), and Modbus TCP is unauthenticated by protocol design. The principal limiting factor is exposure: port 502 is normally confined to OT/ICS network segments, so realistic risk depends on whether the device is reachable from an attacker-controlled network. Impact is limited to availability (device DoS); no data disclosure or manipulation results. |
| Impact | All signals converge on a genuine but bounded risk. The CVSS 3.1 vector (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, base 7.5) describes a remotely reachable, low-complexity, unauthenticated flaw whose entire impact is availability - no confidentiality or integrity loss. This is consistent with the description: an unauthenticated crafted Modbus TCP packet to port 502 crashes the device. EPSS is very low at 0.06% (20th percentile), the CVE is NOT in CISA KEV, and no public proof-of-concept is referenced (only the Talos advisory), so this is 'no public exploit identified at time of analysis.' There is no signal conflict on the technical facts, but note the SSVC/impact picture: technical impact is limited to DoS of a single power-monitoring device, and exploitation is not automatable at internet scale because Modbus/502 is typically confined to OT/ICS segments. The one labeling tension worth verifying is the 'Authentication Bypass' tag and CWE-306 (missing authentication) framing versus the actual outcome, which is a denial of service, not a gained-access bypass. Net: a legitimately high base score, but real-world urgency is moderated by low EPSS, no KEV, no POC, availability-only impact, and the niche/segmented deployment of the affected product. |
| Exploit ScenarioDerived | An attacker with network reachability to the DIRIS Digiware M-70's Modbus TCP service (port 502) sends a single specially crafted, unauthenticated packet that the Modbus parser mishandles, crashing the device and cutting off its power-monitoring/measurement function until it is recovered. Because Modbus TCP has no authentication, no credentials or user interaction are required. No public exploit code is currently identified beyond the Talos vulnerability report. |
Get an e-mail when this CVE is exploited, patched or re-scored. Free account.
Alert meAnalysisAIv2 – Sep 26, 2026
Unauthenticated denial of service in Socomec DIRIS Digiware M-70 firmware 1.6.9 lets any host that can reach the device's Modbus TCP service crash or stall it by sending a single specially crafted packet to port 502; the same weakness affects the Modbus RTU over TCP USB function. The root cause is a missing-authentication condition (CWE-306) in a protocol that is unauthenticated by design, and the CVSS 3.1 vector (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, 7.5) confirms that no credentials or user interaction are needed and that only availability is impacted, with no disclosure or manipulation of data. No public exploit code and no confirmed active exploitation were identified at time of analysis, and the EPSS score is low at 0.06% (20th percentile), so realistic risk is bounded by exposure: the device is only at meaningful risk if port 502 is reachable from an attacker-controlled network rather than confined to a trusted OT/ICS segment.
Earlier versions of this analysis (1)
RemediationAI
No vendor-released patch identified at time of analysis; the provided references (Talos TALOS-2025-2251 and the NVD entry for CVE-2025-55221) should be checked for a Socomec firmware update, and any patched build must be obtained from Socomec rather than assumed from the version number. Until a fixed firmware is available, the effective mitigation is exposure reduction, since the flaw is unauthenticated by protocol design: block or tightly ACL inbound TCP port 502 so that only trusted engineering workstations and OT controllers can reach the device, ideally enforced at an OT firewall or managed switch in front of the Digiware M-70 - the trade-off is that legitimate Modbus masters outside the permitted list will lose connectivity. Where the Modbus RTU over TCP USB path is not operationally required, disabling or disconnecting that function removes the serial-over-USB attack surface at the cost of losing remote serial instrument access. Additional compensating controls include placing the device on an isolated ICS/VLAN segment with no route to IT or internet networks, and monitoring for malformed or unexpected Modbus traffic on 502 (IDS or protocol-aware inspection) to detect triggering attempts, recognizing that such monitoring may add latency and can be evaded by well-formed-appearing packets.
Affected VersionsENISA
Affected Packages
Source: OSV (Open Source Vulnerabilities)
Affects your stack
Affects 1 package in euvd
Checking this CVE against your own stacks and servers is part of the Basic plan and up.
Technical ContextAI · show details
The affected component is the Modbus TCP server and the Modbus RTU over TCP USB function implemented in Socomec DIRIS Digiware M-70 firmware 1.6.9, identified by CPE cpe:2.3:o:socomec:diris_m-70_firmware:1.6.9. Modbus TCP is an industrial protocol that runs by default on TCP port 502 and provides no native authentication or authorization, so any packet that reaches the listener is processed without a credential check; this is captured by CWE-306 (Missing Authentication for Critical Function), which is the weakness class assigned here. The specific failure is triggered by a maliciously formed Modbus message received over port 502, and the description indicates the equivalent code path reached through Modbus RTU over TCP over USB is also affected. The vulnerability is reported by Cisco Talos as TALOS-2025-2251 along with the associated NVD/EUVD advisory records (EUVD-2025-200036), and the impact class is purely availability loss: the device becomes unresponsive or its Modbus service stops responding, with no integrity or confidentiality effect per the CVSS vector.
Know when Modbus gets its next vulnerability
- Watch products and get an email when something new is published
- Check this CVE against your own stack and servers
- Exploit and PoC references, threat intelligence from 22 sources
No credit card · 7-day full trial
Severity by source
AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Unauthenticated crafted packet over network port 502 with no user interaction (AV:N/AC:L/PR:N/UI:N); impact is availability-only device crash, so C:N/I:N/A:H, scope unchanged.
Primary rating from NVD.
CVSS VectorNVD
Lifecycle Timeline
3DescriptionNVD
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP USB Function functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted network packet can lead to a denial of service. An attacker can send an unauthenticated packet to trigger this vulnerability.This vulnerability is specific to the malicious message sent via Modbus TCP over port 502.
Executive ViewAI
Socomec DIRIS Digiware M-70 devices (version 1.6.9) are vulnerable to unauthenticated denial of service attacks via Modbus TCP, potentially disrupting critical infrastructure monitoring and control systems. Organizations using this device should immediately assess exposure and implement network-level protections, as no vendor patch is currently available.
Implement network segmentation to isolate Modbus TCP port 502 traffic; deploy firewall rules to restrict port 502 access to trusted hosts only; configure rate limiting and connection throttling on port 502; monitor for suspicious Modbus traffic patterns; disable remote Modbus TCP access if not operationally required; consider deploying a WAF or Modbus proxy with malicious packet filtering if available from vendors.
Threat Intelligence Overview
How this decision was reached
The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.
What every action level means
SSVC AssessmentENISA
Priority Score
Attack Technique
Authentication bypass attacks exploit flaws in the verification mechanisms that control access to systems and applications.
Denial of Service attacks render applications or systems unavailable by overwhelming resources or triggering failure conditions.
CVE-2025-48466 is a security vulnerability (CVSS 8.1). Risk factors: public PoC available.
Unauthenticated remote attackers with network reachability to a UPS's Modbus command interface can switch off the unit's
A single unauthenticated network packet sent to the Modbus RTU-over-TCP service of a Socomec DIRIS Digiware M-70 power-m
Unauthenticated remote attackers can cause a denial of service of the Modbus service on affected devices by sending a sp
EUVD-2025-200036
NVD
CVE.org
EPSS
VulDB
GitHub PoC
Exploit-DB