Skip to main content

DIRIS Digiware M-70 EUVDEUVD-2025-200035

| CVE-2025-55222 HIGH
Missing Authentication for Critical Function (CWE-306)
2025-12-01 talos-cna@cisco.com
7.5
CVSS 3.1 · NVD
View

Attack ChainAIDerived

Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain

  1. Access
    Reach device Modbus port 503
  2. Exploit
    Send crafted Modbus RTU-over-TCP packet
  3. Impact
    Device denial of service

Vulnerability Assessment

Weakness
CWE
OWASP Top 10:2025
A07:2025 - Authentication Failures
ASVS 5.0
V6 - Authentication Authentication required for critical functions
MITRE ATT&CK

1 technique across 1 tactic: Initial Access

The technique list with ATT&CK links and the kill-chain view is part of the Basic plan and up.

Exploitation Conditions

Exploitation requires network reachability to the DIRIS Digiware M-70's Modbus RTU-over-TCP service specifically on TCP port 503; the standard Modbus TCP path is not the stated vector - the malicious message must be delivered via Modbus RTU over TCP on port 503. No authentication, credentials, or user interaction are needed (PR:N/UI:N). Limiting factors: the attacker must have Layer-3 access to the OT network segment hosting the device, and these industrial metering devices are typically deployed on isolated/segmented networks rather than exposed to the internet, which meaningfully constrains real-world reach despite the AV:N rating.

Impact

This is a genuine but bounded risk. The CVSS 3.1 vector (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, base 7.5) accurately reflects a remote, unauthenticated, low-complexity availability-only attack - there is no confidentiality or integrity impact, so the 'HIGH' rating is driven entirely by A:H denial of service. Signals are internally consistent and point AWAY from urgent widespread exploitation: EPSS is 0.06% (20th percentile), the CVE is NOT in CISA KEV, and no public exploit code is referenced by the Talos advisory. The apparent tension between CWE-306 (Missing Authentication for Critical Function) and the actual outcome is worth noting - the flaw is really an unauthenticated DoS, not a privilege/authentication bypass that yields access; the impact metrics correctly show only A:H. Net: this is a real, patch-worthy defect for operators of this specific device, but not a mass-exploitation priority - the primary concern is availability of an industrial power-monitoring/metering device in an OT/ICS context where uptime matters, and where such devices are typically expected to sit on segmented, non-internet-facing networks.

Exploit ScenarioDerived

An attacker with network reachability to the DIRIS Digiware M-70's Modbus RTU-over-TCP service on port 503 sends a single specially crafted, unauthenticated packet that crashes or hangs the device's Modbus handling, denying service. No authentication, user interaction, or special privileges are required. No public proof-of-concept is identified in the provided data, though Talos (the reporting CNA) has published a detailed vulnerability report.

This Week Schedule remediation this week. Why: HIGH severity (CVSS 7.0-8.9).
No patch listed yet 0.1% exploitation probability (EPSS)

Get an e-mail when this CVE is exploited, patched or re-scored. Free account.

Alert me

AnalysisAIv2 – Sep 26, 2026

Unauthenticated denial of service in Socomec DIRIS Digiware M-70 firmware 1.6.9 allows remote attackers to crash or disable the device by sending a crafted packet to the Modbus RTU-over-TCP service on TCP port 503. The flaw stems from missing authentication for a critical function (CWE-306) and can be triggered without credentials or user interaction; no public exploit code has been identified, and EPSS is low at 0.06% (20th percentile). Exploitation requires Layer-3 access to the OT network segment hosting the device, which typically sits on isolated networks, making this a genuine but bounded risk.

Earlier versions of this analysis (1)
v1 Mar 15, 2026 - 13:34 CVSS 8.6

RemediationAI

No vendor-released patch identified at time of analysis; consult the vendor advisory (https://talosintelligence.com/vulnerability_reports/TALOS-2025-2251) for any firmware updates. As a compensating control, restrict network access to TCP port 503 on the device to only trusted management hosts via firewall rules or ACLs; this blocks the attack vector but requires careful maintenance to avoid disrupting legitimate Modbus RTU-over-TCP communications. If the Modbus RTU-over-TCP USB Function is not needed, disable it entirely, though this may impact monitoring or integration workflows. Segment the OT network so that the device is not reachable from untrusted networks, and monitor for malformed Modbus packets. Restarting the device may temporarily recover from a denial-of-service condition but does not remediate the underlying flaw.

Affected VersionsENISA

DIRIS Digiware M-70 1.6.9

Affected Packages

euvd diris_digiware_m_70 no fix

Source: OSV (Open Source Vulnerabilities)

Affects your stack

Affects 1 package in euvd

Checking this CVE against your own stacks and servers is part of the Basic plan and up.

Technical ContextAI · show details

The Socomec DIRIS Digiware M-70 is an industrial metering device. The vulnerability resides in its Modbus TCP and Modbus RTU over TCP USB Function functionality. While standard Modbus TCP uses port 502, this flaw is specifically triggered via Modbus RTU over TCP on port 503. The root cause is CWE-306: Missing Authentication for Critical Function, meaning the device processes a specially crafted network packet without requiring authentication, leading to a denial of service. The affected firmware is identified by CPE cpe:2.3:o:socomec:diris_m-70_firmware:1.6.9:*:*:*:*:*:*:*.

Know when Diris M 70 Firmware gets its next vulnerability

  • Watch products and get an email when something new is published
  • Check this CVE against your own stack and servers
  • Exploit and PoC references, threat intelligence from 22 sources

No credit card · 7-day full trial

Severity by source

NVD PRIMARY 7.5 HIGH
AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
vuln.today AI 7.5 HIGH

Unauthenticated crafted packet over Modbus RTU-over-TCP port 503 (AV:N/AC:L/PR:N/UI:N) causing only denial of service (C:N/I:N/A:H), no scope change.

3.1 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
4.0 AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N

Primary rating from NVD.

CVSS VectorNVD

Attack Vector
Network
Attack Complexity
Low
Privileges Required
None
User Interaction
None
Scope
Unchanged
Confidentiality
None
Integrity
None
Availability
High

Lifecycle Timeline

3
CVSS changed
Sep 26, 2026 - 00:22 NVD
8.6 (HIGH) 7.5 (HIGH)
CVE Published
Dec 01, 2025 - 16:15 nvd
HIGH 8.6
CVE Published
Dec 01, 2025 - 16:15 nvd
HIGH 7.5

DescriptionNVD

A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP USB Function functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted network packet can lead to a denial of service. An attacker can send an unauthenticated packet to trigger this vulnerability.This vulnerability is specific to the malicious message sent via Modbus RTU over TCP on port 503.

Executive ViewAI

Why It Matters

Socomec DIRIS Digiware M-70 devices running version 1.6.9 are vulnerable to unauthenticated denial of service attacks via malicious Modbus TCP packets, potentially disrupting critical power distribution monitoring and control. Organizations using these devices face service disruption risk until patches become available, with no known workaround currently provided by the vendor.

Business Impact: High
Compensating Controls

Implement network segmentation to isolate affected devices from untrusted networks; restrict access to port 503 using firewall rules or WAF policies to authorized Modbus clients only; deploy network-based IDS/IPS signatures to detect and block malformed Modbus RTU packets; disable Modbus RTU over TCP functionality if not operationally required; increase monitoring and alerting for service availability of affected DIRIS devices.

Threat Intelligence Overview

EPSS Score
0.1%
Top 80% exploitable
Prevalence
Low
niche industrial power-monitoring/energy metering device, no broad enterprise footprint
Data Quality
4 sources
Confidence: Medium

How this decision was reached

The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.

SignalValue
Severity HIGH
CISA KEV No
Public POC No
EPSS 0.1%
Patch available No
Active threat No
Deciding rule
HIGH severity (CVSS 7.0-8.9)
What every action level means
Emergency Immediate action required. Criteria: CRITICAL + in CISA KEV (actively exploited) without patch, OR CRITICAL + EPSS > 30% without patch, OR CRITICAL + active threat signals without patch.
Act Now Prioritize within 24-48h. Criteria: in KEV with patch available, OR CRITICAL + public POC, OR HIGH + EPSS > 10%, OR CRITICAL + active threat, OR any CRITICAL severity.
This Week Schedule remediation this week. Criteria: HIGH severity (CVSS 7.0-8.9). Patch within normal change window.
This Month Plan within 30 days. Criteria: MEDIUM severity (CVSS 4.0-6.9), lower exploitation probability. Include in regular patch cycle.
Monitor Track and reassess. Criteria: LOW severity (CVSS 0.1-3.9), minimal exploitation risk. No immediate action needed.

SSVC AssessmentENISA

SSVC Decision· derived
Scheduled
Exploitation· derived
None
System Exposure· derived
Open
Automatable· derived
Yes
Human Impact
High

Priority Score

38
Low Medium High Critical
KEV: 0
EPSS: 0
CVSS: +38
PoC: 0
Weaponized: 0
Threat intel: 0
Gov advisory: 0

Attack Technique

Authentication bypass attacks exploit flaws in the verification mechanisms that control access to systems and applications.

Denial of Service attacks render applications or systems unavailable by overwhelming resources or triggering failure conditions.

CVE-2024-53684 HIGH
8.8 Dec 01

A cross-site request forgery (csrf) vulnerability exists in the WEBVIEW-M functionality of Socomec DIRIS Digiware M-70 1

CVE-2025-26858 HIGH
7.5 Dec 01

Unauthenticated denial of service in Socomec DIRIS Digiware M-70 power-monitoring devices running firmware 1.6.9, where

CVE-2025-55221 HIGH
7.5 Dec 01

Unauthenticated denial of service in Socomec DIRIS Digiware M-70 firmware 1.6.9 lets any host that can reach the device'

CVE-2025-54851 HIGH
7.5 Dec 01

A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiwa

CVE-2025-54850 HIGH
7.5 Dec 01

A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiwa

CVE-2025-23417 HIGH
7.5 Dec 01

A single unauthenticated network packet sent to the Modbus RTU-over-TCP service of a Socomec DIRIS Digiware M-70 power-m

CVE-2024-48882 HIGH
7.5 Dec 01

A denial of service vulnerability exists in the Modbus TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A special

CVE-2024-48894 HIGH
7.5 Dec 01

A cleartext transmission vulnerability exists in the WEBVIEW-M functionality of Socomec DIRIS Digiware M-70 1.6.9. A spe

CVE-2025-20085 MEDIUM
6.5 Dec 01

A single specially crafted, unauthenticated packet sent to the Modbus RTU over TCP service of a Socomec DIRIS Digiware M

CVE-2024-49572 MEDIUM
6.5 Dec 01

A denial of service vulnerability exists in the Modbus TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A special

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy