Skip to main content

Microscada X Sys600 CVE-2022-29492

HIGH
Improper Input Validation (CWE-20)
2022-09-14 cybersecurity@hitachienergy.com
7.5
CVSS 3.1 · NVD
Share

Severity by source

NVD PRIMARY
7.5 HIGH
AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Primary rating from NVD · only source for this CVE.

CVSS VectorNVD

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Attack Vector
Network
Attack Complexity
Low
Privileges Required
None
User Interaction
None
Scope
Unchanged
Confidentiality
None
Integrity
None
Availability
High

Lifecycle Timeline

1
CVE Published
Sep 14, 2022 - 18:15 nvd
HIGH 7.5

DescriptionNVD

Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*

AnalysisAI

Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Rated high severity (CVSS 7.5), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.

Technical ContextAI

This vulnerability is classified under CWE-20. Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:* Affected products include: Hitachienergy Microscada X Sys600. Version information: version 9.4.

RemediationAI

No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Apply vendor patches when available. Implement network segmentation and monitoring as interim mitigations.

CVE-2024-7940 CRITICAL
9.8 Aug 27

The product exposes a service that is intended for local only to all network interfaces without any authentication. Rate

CVE-2024-4872 HIGH
8.8 Aug 27

A vulnerability exists in the query validation of the MicroSCADA Pro/X SYS600 product. Rated high severity (CVSS 8.8), t

CVE-2024-3980 HIGH
8.8 Aug 27

The MicroSCADA Pro/X SYS600 product allows an authenticated user input to control or influence paths or file names that

CVE-2022-29490 HIGH
8.8 Sep 12

Improper Authorization vulnerability exists in the Workplace X WebUI of the Hitachi Energy MicroSCADA X SYS600 allows an

CVE-2024-3982 HIGH
8.2 Aug 27

An attacker with local access to machine where MicroSCADA X SYS600 is installed, could enable the session logging suppor

CVE-2022-3388 HIGH
7.8 Nov 21

An input validation vulnerability exists in the Monitor Pro interface of MicroSCADA Pro and MicroSCADA X SYS600. Rated h

CVE-2022-2277 HIGH
7.5 Sep 14

Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP co

CVE-2022-29922 HIGH
7.5 Sep 14

Improper Input Validation vulnerability in the handling of a specially crafted IEC 61850 packet with a valid data item b

CVE-2025-39202 HIGH
7.3 Jun 24

CVE-2025-39202 is a local privilege escalation vulnerability in MicroSCADA X SYS600's Monitor Pro interface that allows

CVE-2025-39204 MEDIUM
6.5 Jun 24

A vulnerability exists in the Web interface of the MicroSCADA X SYS600 product. The filtering query in the Web interface

CVE-2025-39203 MEDIUM
6.5 Jun 24

A vulnerability exists in the IEC 61850 of the MicroSCADA X SYS600 product. An IEC 61850-8 crafted message content from

CVE-2025-39205 MEDIUM
6.5 Jun 24

A vulnerability exists in the IEC 61850 in MicroSCADA X SYS600 product. The certificate validation of the TLS protocol a

Share

CVE-2022-29492 vulnerability details – vuln.today

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy