Attack ChainAIDerived
Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain
-
AccessObtain admin web credentials
-
DeliveryCraft modified firmware image
-
ExploitUpload via web upgrade function
-
ExecutionDevice installs without signature check
-
ImpactPersistent firmware-level compromise
Vulnerability Assessment
| Weakness |
CWE
OWASP Top 10:2025
A08:2025 - Software or Data Integrity Failures
ASVS 5.0
V15 - Secure Coding and Architecture Data authenticity verification
|
| Exploitation Conditions | Exploitation requires an authenticated administrator-level session on the EKI-1242EIMS/EKI-1242IEIMS web management interface (PR:H) and network reachability to that interface (AV:N). The specific enabling condition is that the firmware upgrade mechanism in firmware V1.06.01 performs NO cryptographic signature or certificate verification on uploaded firmware images, so any admin-supplied image is accepted. Limiting factors: attacker must already hold admin credentials (no privilege escalation or pre-auth path within this CVE itself), and exploitation is bounded to environments where the management interface is reachable by the attacker; no user interaction is needed once admin access exists. |
| Impact | This is a genuine but access-gated risk. The CVSS 4.0 vector (AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H, 8.6) accurately reflects a firmware-authenticity flaw: an attacker who already holds administrator credentials on the web management interface can flash unsigned, attacker-modified firmware, yielding full persistent platform compromise (all three impact metrics High). The PR:H requirement is the dominant limiter - this is a post-authentication persistence/root-of-trust weakness, not a pre-auth breach. No EPSS score, no CISA KEV listing, and no public POC are provided, so there is no evidence of active or opportunistic exploitation; realistically this is a targeted post-compromise capability (an attacker who has phished/brute-forced admin, or an insider, converting admin access into durable firmware-level implants). Contrast with same-advisory sibling CVE-2026-73172, a pre-auth (PR:N) root RCE at 9.3 - that is a far higher acquisition priority than this authenticated flaw. Prioritize CVE-2026-73177 as a defense-in-depth/root-of-trust fix rather than an emergency, but note that once admin is obtained via any of the sibling web-UI RCEs, this flaw makes eviction extremely difficult. No signals conflict; the vector and description are consistent. |
| Exploit ScenarioDerived | An attacker who has obtained administrator credentials to the EKI-1242EIMS web management interface (via reused/default credentials, phishing, or one of the sibling pre-auth RCEs) uploads a maliciously modified firmware image through the standard upgrade function. Because the device performs no signature or certificate verification, it accepts and installs the tampered image, giving the attacker a persistent, firmware-level implant that survives reboots and factory resets. No public exploit code is identified at time of analysis. |
Get an e-mail when this CVE is exploited, patched or re-scored. Free account.
Alert meAnalysisAIv1 – Sep 16, 2026
Authenticated administrators with network reachability to the web management interface of Advantech EKI-1242EIMS and EKI-1242IEIMS devices running firmware V1.06.01 can upload firmware images that the device accepts without any cryptographic signature or certificate verification, resulting in full, persistent compromise of the platform (CWE-345; CVSS 4.0 base 8.6). The risk is genuine but access-gated: the attacker must already hold administrator-level credentials for the management interface (PR:H), so this CVE does not by itself provide a pre-authentication or privilege-escalation path, but the resulting ability to replace device firmware gives durable control over an industrial edge device that may sit on an OT/IT boundary. No public exploit code or confirmed active exploitation was identified at time of analysis.
RemediationAI
No fixed firmware version is confirmed in the available data; patch status is therefore "patch available per vendor advisory" only in the sense that Advantech has published a vendor security advisory, and the exact remediated firmware build must be taken from that advisory (https://advcloudfiles.advantech.com/cms/5dafee28-ad53-4d07-a328-7896fcc24b6e/Security%20Advisory%20PDF%20File/SECURITY-ADVISORY----EKI-1242IEIMS-updated-20260904.pdf) or from Nozomi Networks (https://www.nozominetworks.com/labs/vulnerability-advisories-cve-2026-73177) before upgrading EKI-1242EIMS/EKI-1242IEIMS units. Because the upgrade path itself performs no authenticity verification, the strongest compensating controls are network-level: block management-interface access from untrusted networks (WAN/Internet and general user VLANs) and permit only a dedicated, firewall-restricted management VLAN or jump host, accepting the trade-off that remote administration must then go through that bastion or VPN and that break-glass access must be planned; where remote management is not required, disable the web management service or external-facing management access entirely, acknowledging that this removes remote monitoring and configuration capability. Rotate and strictly limit administrator credentials and enable logging/alerting on management logins and firmware-upgrade events, and monitor for unexpected reboots, firmware-version drift, and configuration changes via syslog or SNMP, understanding that such monitoring is detective only and will not prevent an admin who already holds valid credentials from pushing a modified image.
Affected VersionsENISA
Affected Packages
Source: OSV (Open Source Vulnerabilities)
Affects your stack
Affects 2 packages in euvd
Checking this CVE against your own stacks and servers is part of the Basic plan and up.
Technical ContextAI · show details
The root-cause class is CWE-345, Insufficient Verification of Data Authenticity, applied to the firmware upgrade workflow. In firmware V1.06.01 on the EKI-1242EIMS and EKI-1242IEIMS, the authenticated web management interface accepts an uploaded firmware image and flashes it without validating a vendor digital signature, certificate chain, or any trusted-root check, so image integrity depends only on the confidentiality of the administrator session (e.g., HTTPS transport) rather than on cryptographic proof of origin. The CPE records cpe:2.3:a:advantech:eki-1242eims and cpe:2.3:a:advantech:eki-1242ieims use a wildcard version field, meaning both models are tracked as potentially affected across firmware versions, while the Nozomi Networks research and the Advantech advisory scope the demonstrated flaw to firmware V1.06.01. The practical exploit chain is straightforward: an admin uploads a modified image, the device writes it to the firmware partition and reboots into it, granting persistent control over the device's networking and management functions; because there is no post-flash authenticity check, the compromise survives until a clean image is manually reinstalled.
Know when Eki 1242Ieims gets its next vulnerability
- Watch products and get an email when something new is published
- Check this CVE against your own stack and servers
- Exploit and PoC references, threat intelligence from 22 sources
No credit card · 7-day full trial
Severity by source
CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
Network-reachable web interface with low complexity, but requires administrator privileges (PR:H); unsigned firmware install yields full persistent compromise, so C/I/A all High, scope unchanged.
Primary rating from Vendor (Nozomi).
CVSS VectorVendor: Nozomi
DescriptionCVE.org
Nozomi Networks Labs identified a CWE-345: Insufficient Verification of Data Authenticity vulnerability in the firmware upgrade mechanism of the Advantech EKI-1242EIMS in firmware version V1.06.01. The device accepts firmware images through the authenticated web management interface without performing any cryptographic signature or certificate verification. An authenticated administrator-level attacker can install arbitrary modified firmware on the device, enabling full persistent compromise of the platform.
Executive ViewAI
Advantech EKI-1242EIMS and EKI-1242IEIMS industrial edge devices running firmware V1.06.01 accept firmware uploads without cryptographic signature verification, so a user who already holds administrator credentials and can reach the web management interface can install unauthorized firmware and obtain lasting, persistent control of the platform. These devices commonly sit at the OT/IT boundary in manufacturing and critical-infrastructure environments, meaning a compromised unit could serve as a durable foothold for observing or disrupting operational networks. No vendor patch is currently available, and exploitation requires pre-existing administrator access, so leadership should treat this as a significant but access-gated risk that warrants immediate exposure reduction and a hardening plan for the fleet.
No vendor-released patch identified at time of analysis. Interim mitigations: isolate the web management interface on a dedicated OT management VLAN reachable only from allowlisted administrative jump hosts; enforce least privilege, unique accounts, and MFA for all administrator credentials; monitor and alert on firmware-write and configuration-change events via syslog/SNMP; periodically verify running firmware against known-good baseline hashes and reflash from offline, integrity-checked images if a mismatch is found; disable unused management services and protocols; and retain offline firmware backups for rapid recovery.
Threat Intelligence Overview
How this decision was reached
The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.
What every action level means
SSVC AssessmentENISA
Priority Score
Attack Technique
Information disclosure occurs when an application unintentionally exposes sensitive data that aids attackers in reconnaissance or directly compromises security.
More in Eki 1242Ieims
View allUnauthenticated OS command injection in the edgserver management service of Advantech EKI-1242EIMS and EKI-1242IEIMS gat
Advantech EKI-1242EIMS and EKI-1242IEIMS industrial gateways running firmware V1.06.01 expose their edgserver management
Authenticated OS command injection in the web management interface of Advantech EKI-1242IEIMS and EKI-1242EIMS industria
OS command injection in the web management interface of the Advantech EKI-1242IEIMS and EKI-1242EIMS industrial gateways
OS command injection in the web management interface of Advantech EKI-1242IEIMS and EKI-1242EIMS industrial devices runn
Authenticated high-privileged users of Advantech EKI-1242IEIMS and EKI-1242EIMS industrial gateways running firmware V1.
OS command injection in the web management interface of Advantech EKI-1242IEIMS industrial gateways (firmware V1.06.01)
Code injection in the web management interface of Advantech EKI-1242IEIMS (and the closely related EKI-1242EIMS) industr
Passive interception of the cleartext edgserver management protocol on Advantech EKI-1242EIMS and EKI-1242IEIMS devices
Arbitrary Lua code execution is possible on Advantech EKI-1242EIMS and EKI-1242IEIMS industrial Modbus gateways running
An authenticated file-overwrite vulnerability in the backup-restore workflow of Advantech EKI-1242EIMS (and EKI-1242IEIM
Cross-site request forgery in the LuCI administrative web interface of Advantech EKI-1242IEIMS running firmware V1.06.01
EUVD-2026-80700
GHSA-pxh8-mw2j-c73g
NVD
CVE.org
EPSS
Exploit-DB