Skip to main content

ADAM-3600 EdgeLink EUVDEUVD-2026-51387

| CVE-2026-43831 HIGH
Stack-based Buffer Overflow (CWE-121)
2026-07-31 CSA GHSA-x65g-869w-3ggw
7.5
CVSS 3.1 · Vendor: CSA
Share

Severity by source

Vendor (CSA) PRIMARY
7.5 CRITICAL
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
vuln.today AI
9.8 CRITICAL

Network-reachable, unauthenticated RCE grants full C/I/A impact; provided NVD vector's I:N/A:N is inconsistent with code execution and is assessed as erroneous.

3.1 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
4.0 AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N

Primary rating from Vendor (CSA).

CVSS VectorVendor: CSA

Attack Vector
Network
Attack Complexity
Low
Privileges Required
None
User Interaction
None
Scope
Unchanged
Confidentiality
High
Integrity
None
Availability
None

Lifecycle Timeline

6
Analysis Updated
Jul 31, 2026 - 20:31 vuln.today
v2 (cvss_changed)
Re-analysis Queued
Jul 31, 2026 - 20:22 vuln.today
cvss_changed
Severity Changed
Jul 31, 2026 - 20:22 NVD
CRITICAL HIGH
CVSS changed
Jul 31, 2026 - 20:22 NVD
9.2 (CRITICAL) 7.5 (HIGH)
Analysis Generated
Jul 31, 2026 - 04:30 vuln.today
CVE Published
Jul 31, 2026 - 02:57 cve.org
CRITICAL 9.2

DescriptionCVE.org

Successful exploitation of the vulnerability could allow an unauthenticated attacker to exploit a stack-based buffer overflow in the log message functionality to conduct code execution.

AnalysisAI

Remote code execution in Advantech ADAM-3600 EdgeLink industrial edge controllers is possible through a stack-based buffer overflow in the device's log message handling functionality, exploitable by unauthenticated network attackers on versions prior to 2.8.5.1. Reported by the Cyber Security Agency of Singapore (CSA), the vulnerability carries a CWE-121 classification - a well-understood root cause class with a history of weaponizable exploits, particularly in embedded and OT/ICS devices. No public exploit has been identified at time of analysis, and EPSS sits at 0.14% (4th percentile), though the network-accessible, unauthenticated nature of the flaw and the industrial deployment context elevate operational risk above what the percentile alone suggests.

Technical ContextAI

The Advantech ADAM-3600 EdgeLink is an industrial IoT edge controller (CPE: cpe:2.3:a:advantech:adam-3600_edgelink:*:*:*:*:*:*:*:*) designed for data acquisition and remote monitoring in OT/SCADA environments. The vulnerability is rooted in CWE-121 (Stack-based Buffer Overflow): the log message processing routine allocates a fixed-size stack buffer but fails to validate the length of attacker-controlled input before copying it, allowing adjacent stack memory - including the saved return address - to be overwritten. On embedded/industrial firmware where stack canaries, ASLR, or NX protections may be absent or weakened, this class of flaw is routinely exploitable to achieve arbitrary code execution. Because the log message path is network-exposed and requires no authentication, the attack surface is broad for any device reachable over the network.

RemediationAI

The primary remediation is to upgrade Advantech ADAM-3600 EdgeLink firmware to version 2.8.5.1 or later, as identified in the EUVD affected-versions data. The CSA advisory at https://www.csa.gov.sg/alerts-and-advisories/alerts/al-2026-097 should be consulted for vendor-specific upgrade procedures and any additional guidance. If immediate patching is not operationally feasible, defenders should enforce strict network segmentation to ensure the device is not reachable from untrusted networks or the internet - ADAM-3600 devices are OT edge controllers and should only be accessible from authorized engineering workstations or SCADA systems via allowlisted firewall rules. Blocking or rate-limiting access to log-related network services on the device, if configurable, is an additional compensating control, though its effectiveness depends on whether the vulnerable log path is separable from core device communication. Note that network segmentation prevents remote exploitation but does not eliminate insider or lateral-movement risk.

Share

EUVD-2026-51387 vulnerability details – vuln.today

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy