Attack ChainAIDerived
Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain
-
AccessPosition rogue runtime or MITM the channel
-
DeliveryUser trusts runtime and opens visualization
-
ExploitDeliver crafted visualization data
-
ExecutionInvoke local COM/ActiveX on workstation
-
ImpactExecute arbitrary code as the operator
Vulnerability Assessment
| Weakness |
CWE
ASVS 5.0
V15 - Secure Coding and Architecture Incorrect resource transfer between spheres
|
| Exploitation Conditions | Exploitation requires a specific operational state: a user must be simultaneously logged in to a CODESYS Control runtime AND actively operating a visualization on the engineering workstation (per UI:A, passive user interaction is required). Beyond that, the attacker must satisfy one of two concrete prerequisites - either (a) control a malicious CODESYS Control runtime and successfully trick the user into trusting/connecting to it (a social-engineering step), or (b) hold a man-in-the-middle position on the communication between the legitimate runtime and the engineering workstation (requiring a privileged network vantage point). The affected engineering workstation must be a Windows system exposing COM/ActiveX functionality, since that is the resource the visualization data abuses. These factors - mandatory active-operator interaction, the trust decision, and the required MITM/rogue-runtime position - materially limit realistic exploitation despite the network attack vector and lack of authentication. |
| Impact | This is a credible but conditional threat rather than a mass-exploitation emergency. The CVSS 4.0 vector (AV:N/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H, 8.6) reflects network reach, no attacker privileges, and high confidentiality/integrity/availability impact to the engineering workstation, but UI:A confirms the victim must be actively operating a visualization while logged in to a runtime - the flaw cannot fire on its own. Crucially, exploitation depends on the attacker either controlling a malicious CODESYS Control runtime that the user is socially engineered into trusting, or holding a man-in-the-middle position on the runtime-to-workstation channel; both are meaningful real-world barriers that the AC:L/AT:N rating arguably understates (a privileged network position or a trust-decision is closer to an attack requirement than a trivial one). The vuln.today decision label is 'this_week' (a priority, not 'act_now'/'emergency'). No EPSS score, no CISA KEV listing, and no public exploit were provided, so there is no evidence of active or at-scale exploitation - this reads as a targeted/opportunistic risk against operators of CODESYS visualizations, not a wormable internet-facing bug. Priority is justified for OT/ICS asset owners running CODESYS, but it is not a drop-everything scenario on the available signals. |
| Exploit ScenarioDerived | An operator logged in to a CODESYS Control runtime opens a visualization served by an attacker-controlled or manipulated runtime; the malicious visualization data drives local COM/ActiveX functionality on the Windows engineering workstation, yielding arbitrary code execution in the operator's context. The attacker achieves this either by luring the user into trusting a rogue runtime or by man-in-the-middling the runtime-to-workstation communication. No public exploit identified at time of analysis, so this is an inferred scenario grounded in the advisory description. |
Get an e-mail when this CVE is exploited, patched or re-scored. Free account.
Alert meAnalysisAIv1 – Nov 24, 2026
CODESYS Visualization does not sufficiently constrain runtime-supplied visualization content, allowing crafted visualization data to reach local COM/ActiveX functionality on a Windows engineering workstation and execute arbitrary code. The issue is network-reachable and unauthenticated, but exploitation is conditional: the user must be logged in to a CODESYS Control runtime and actively operating a visualization, and the attacker must either run a malicious runtime that the user is tricked into trusting or hold a man-in-the-middle position on runtime-to-workstation traffic. No public exploit was identified at time of analysis, and the vuln.today decision is this_week, consistent with a credible but conditional threat rather than a mass-exploitation emergency.
RemediationAI
No vendor-released patch version is identified in the supplied data; confirm fixed versions and any vendor-specific upgrade guidance through CERTVDE advisory VDE-2026-154 (https://www.certvde.com/en/advisories/VDE-2026-154/). Until a fixed release is confirmed, reduce exposure by restricting engineering workstations to known, explicitly trusted CODESYS Control runtimes and requiring operator verification before accepting a new runtime; this lowers rogue-runtime risk but depends on user behavior. Encrypt and authenticate runtime-to-workstation traffic with an existing protected channel such as IPSec or a VPN to defeat man-in-the-middle positioning, accepting added configuration complexity and possible latency. Where operationally feasible, limit or disable unnecessary COM/ActiveX activation on engineering workstations, with the trade-off that visualization features depending on local ActiveX controls may stop working.
Affected VersionsENISA
Affected Packages
Source: OSV (Open Source Vulnerabilities)
Affects your stack
Affects 1 package in euvd
Checking this CVE against your own stacks and servers is part of the Basic plan and up.
Technical ContextAI · show details
The affected component is CODESYS Visualization, identified by the CPE cpe:2.3:a:codesys:visualization:*:*:*:*:*:*:*:*. The product consumes visualization data supplied by a CODESYS Control runtime and transfers that data into the engineering workstation's local execution environment without adequate restriction; CWE-669 (Incorrect Resource Transfer Between Spheres) describes this cross-sphere transfer of a resource from the runtime into the workstation. The local resource abused is Windows COM/ActiveX functionality, so the engineering workstation must expose that capability. The supplied sources do not describe the exact parsing path or the specific visualization element that invokes COM/ActiveX; the trigger details beyond runtime-supplied visualization data are not fully described. The independent assessment rates the issue AC:H and UI:R because the user must be actively operating a visualization and the attacker must either control a malicious runtime that the user trusts or obtain a privileged man-in-the-middle position between the runtime and the engineering workstation.
Know when Visualization gets its next vulnerability
- Watch products and get an email when something new is published
- Check this CVE against your own stack and servers
- Exploit and PoC references, threat intelligence from 22 sources
No credit card · 7-day full trial
Severity by source
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
Network, no auth, but victim must actively operate a visualization (UI:R) and attacker must win a trust decision or MITM position (AC:H); full code execution gives C/I/A:H, scope unchanged.
Primary rating from Vendor (CERTVDE).
CVSS VectorVendor: CERTVDE
Lifecycle Timeline
2DescriptionCVE.org
The affected products insufficiently restrict runtime-supplied visualization data, allowing to invoke local COM/ActiveX functionality on the engineering workstation, if a user is both logged in to a CODESYS Control runtime and operates a visualization. An unauthenticated remote attacker controlling a malicious runtime and tricking a user to trust it, or performing a man-in-the-middle attack on the communication between the CODESYS Control runtime and the engineering workstation, may cause arbitrary code execution on the engineering workstation.
Executive ViewAI
A high-severity vulnerability (CVE-2026-121017) in CODESYS Visualization could allow an attacker to execute arbitrary code on Windows engineering workstations used to operate CODESYS Control runtimes, but only under specific conditions: the user must be actively logged in and operating a visualization, and the attacker must either deceive the user into trusting a malicious runtime or intercept runtime-to-workstation traffic. This puts engineering teams and the integrity of industrial control system configurations at risk, though no public exploit has been identified, so the immediate likelihood of widespread exploitation is low.
No vendor-released patch identified at time of analysis. Interim mitigations: restrict engineering workstation network access to trusted runtime devices only, use encrypted channels (TLS/VPN) for runtime-to-workstation traffic, enforce user awareness training to avoid trusting malicious runtimes, and implement application control to block unauthorized code execution.
Threat Intelligence Overview
How this decision was reached
The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.
What every action level means
SSVC AssessmentENISA
Priority Score
Attack Technique
Remote Code Execution represents the critical moment when an attacker successfully runs arbitrary code on a target system without physical access.
More in Visualization
View allInsufficient restriction of runtime-supplied visualization commands in CODESYS Visualization allows a malicious or imper
Arbitrary code execution on a CODESYS engineering workstation can be triggered through visualization data supplied at ru
CODESYS Visualization (versions 1.0.0.0 through below 4.10.0.0) exposes authentication credentials of one low-privileged
All CODESYS Visualization versions before V4.2.0.0 generate a login dialog vulnerable to information exposure allowing a
CODESYS Visualization derives the output directory for an offline boot application from attacker-controlled project data
EUVD-2026-133710
NVD
CVE.org
GitHub PoC
Exploit-DB