Skip to main content

DIRIS Digiware M-70 EUVDEUVD-2025-200028

| CVE-2025-20085 MEDIUM
Missing Authentication for Critical Function (CWE-306)
2025-12-01 talos-cna@cisco.com
6.5
CVSS 3.1 · NVD
View

Attack ChainAIDerived

Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain

  1. Access
    Reach device Modbus TCP port
  2. Delivery
    Send crafted unauthenticated packet
  3. Exploit
    Trigger DoS and credential reset
  4. Execution
    Log in with documented default credentials
  5. Impact
    Control energy-metering device

Vulnerability Assessment

Weakness
CWE
OWASP Top 10:2025
A07:2025 - Authentication Failures
ASVS 5.0
V6 - Authentication Authentication required for critical functions
MITRE ATT&CK

1 technique across 1 tactic: Initial Access

The technique list with ATT&CK links and the kill-chain view is part of the Basic plan and up.

Exploitation Conditions

Exploitation requires network access to the device's Modbus RTU over TCP service on a Socomec DIRIS Digiware M-70 running firmware 1.6.9; a single specially crafted, unauthenticated packet triggers the flaw (AV:N/AC:L/PR:N/UI:N - no authentication, no user interaction, default configuration). The practical limiting factor is reachability: these devices are typically deployed on segmented OT/building-management networks rather than the open internet, so the attacker must already be on a network path to the Modbus TCP interface. The secondary credential-reset impact depends on the vendor's default credentials being documented (which the description states they are), enabling follow-on authenticated access.

Impact

The CVSS 3.1 vector (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N, base 6.5) describes an unauthenticated, low-complexity, network-reachable flaw requiring no user interaction - signals that normally warrant priority. However, real-world exploitation pressure is low: EPSS is 0.04% (12th percentile), there is no CISA KEV listing, and no public exploit was identified in the provided data (Cisco Talos published a vulnerability report, TALOS-2025-2138, which typically documents technical detail but the input does not confirm released PoC code). The most consequential signal is qualitative rather than numeric: the description states the crafted packet not only causes denial of service but 'weakens credentials resulting in default documented credentials being applied to the device' - meaning a remote unauthenticated attacker can reset the device to publicly-documented default credentials and then authenticate, a far more serious secondary impact than the modest C:L/I:L base metrics suggest. There is an internal conflict worth flagging: the vulnerability is titled/tagged 'Denial Of Service' and the description says it 'can lead to denial of service,' yet the CVSS vector sets A:N (no availability impact) - this understates the availability dimension and should be verified against the Talos and Socomec advisories. Net: this is a genuine concern for the specific niche of deployed Socomec DIRIS Digiware M-70 energy-metering devices (especially any internet- or OT-network-exposed unit), but the very low deployment footprint and absence of exploitation evidence keep aggregate real-world risk moderate rather than urgent.

Exploit ScenarioDerived

An attacker with network reachability to a Socomec DIRIS Digiware M-70 (firmware 1.6.9) sends a single crafted Modbus RTU-over-TCP packet without authentication. The device is knocked into denial of service and its credentials are reset to the vendor's documented defaults, after which the attacker logs in with those well-known default credentials to control or monitor the metering device. Cisco Talos documented the flaw (TALOS-2025-2138); no public weaponized exploit is confirmed in the provided data.

This Month Plan within 30 days. Why: MEDIUM severity (CVSS 4.0-6.9).
No patch listed yet 0.0% exploitation probability (EPSS)

Get an e-mail when this CVE is exploited, patched or re-scored. Free account.

Alert me

AnalysisAIv2 – Sep 26, 2026

A single specially crafted, unauthenticated packet sent to the Modbus RTU over TCP service of a Socomec DIRIS Digiware M-70 running firmware 1.6.9 can cause a denial of service and, as a secondary effect, weaken the device's credentials so that its documented default credentials are re-applied, enabling follow-on authenticated access. The flaw carries a CVSS 3.1 base score of 6.5 (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N), and the assessed vector confirms it is network-reachable, low-complexity, and requires no authentication or user interaction; the practical limiting factor is reachability, since these devices normally sit on segmented OT/building-management networks rather than the open internet. EPSS is very low (0.04%, 12th percentile), there is no CISA KEV listing, and no public exploit has been identified at time of analysis.

Earlier versions of this analysis (1)
v1 Mar 15, 2026 - 13:34 CVSS 7.2

RemediationAI

Consult the Socomec advisory (https://www.socomec.fr/sites/default/files/2025-04/CVE-2025-20085---Diris-Digiware-Webview-_VULNERABILITIES_2025-04-11-17-14-39_English_0.pdf) and the Talos report TALOS-2025-2138 (https://talosintelligence.com/vulnerability_reports/TALOS-2025-2138) for the vendor's fixed firmware release, and upgrade DIRIS Digiware M-70 units from firmware 1.6.9 to the latest vendor-supplied version; the provided data does not include an independently confirmed patch version, so the exact fixed build should be verified against the vendor advisory. Because the flaw is triggered by an unauthenticated packet to the Modbus RTU over TCP service, immediate compensating controls include blocking TCP port 502 (or whatever port the Modbus TCP listener uses) at network boundaries and placing the device behind a firewall or OT gateway that permits Modbus traffic only from known engineering/SCADA hosts - this reduces exposure but will break legitimate polling if the allow-list is too narrow. Segment the device onto an isolated OT/building-management VLAN so it is not reachable from corporate or internet-facing networks, and change the documented default credentials to strong unique values on every unit, since the credential-weakening side effect can reapply those defaults; be aware that a Modbus DoS can still take the device offline even after credential hardening. Monitor for repeated malformed Modbus frames and unexpected device reboots or authentication changes as detection signals.

Affected VersionsENISA

DIRIS Digiware M-70 1.6.9

Affected Packages

euvd diris_digiware_m_70 no fix

Source: OSV (Open Source Vulnerabilities)

Affects your stack

Affects 1 package in euvd

Checking this CVE against your own stacks and servers is part of the Basic plan and up.

Technical ContextAI · show details

The vulnerability resides in the Modbus RTU over TCP functionality of the Socomec DIRIS Digiware M-70, an industrial power-monitoring and metering device. Modbus is a legacy, unauthenticated industrial protocol, and tunneling Modbus RTU frames over TCP exposes that command surface to any host with a network path to the service. The root cause is classified as CWE-306 (Missing Authentication for Critical Function): the code path that processes incoming Modbus packets does not authenticate or validate the caller before acting on the request, so a malformed packet drives the device into a denial-of-service state and additionally triggers a credential-handling condition that resets or reverts authentication to the vendor's documented default credentials. The affected product is identified by CPE cpe:2.3:o:socomec:diris_m-70_firmware:1.6.9, and the EUVD entry (EUVD-2025-200028) lists DIRIS Digiware M-70 1.6.9 as the sole affected version. The report was coordinated by Cisco Talos (TALOS-2025-2138) with a vendor advisory from Socomec.

Know when Diris M 70 Firmware gets its next vulnerability

  • Watch products and get an email when something new is published
  • Check this CVE against your own stack and servers
  • Exploit and PoC references, threat intelligence from 22 sources

No credit card · 7-day full trial

Severity by source

NVD PRIMARY 6.5 MEDIUM
AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N
vuln.today AI 7.3 HIGH

Unauthenticated network packet (AV:N/AC:L/PR:N/UI:N); credential reset to defaults gives limited confidentiality/integrity (C:L/I:L) and the stated DoS warrants A:L rather than the input's A:N.

3.1 AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L
4.0 AV:N/AC:L/AT:N/PR:N/UI:N/VC:L/VI:L/VA:L/SC:N/SI:N/SA:N

Primary rating from NVD.

CVSS VectorNVD

Attack Vector
Network
Attack Complexity
Low
Privileges Required
None
User Interaction
None
Scope
Unchanged
Confidentiality
Low
Integrity
Low
Availability
None

Lifecycle Timeline

3
Severity Changed
Sep 26, 2026 - 00:22 NVD
HIGH MEDIUM
CVSS changed
Sep 26, 2026 - 00:22 NVD
7.2 (HIGH) 6.5 (MEDIUM)
CVE Published
Dec 01, 2025 - 16:15 nvd
HIGH 7.2

DescriptionNVD

A denial of service vulnerability exists in the Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted network packet can lead to denial of service and weaken credentials resulting in default documented credentials being applied to the device. An attacker can send an unauthenticated packet to trigger this vulnerability.

Executive ViewAI

Why It Matters

Socomec DIRIS Digiware M-70 devices (version 1.6.9) are vulnerable to remote denial of service attacks that can also reset devices to default credentials, enabling unauthorized access. Any organization operating these industrial control devices faces immediate risk of operational disruption and potential security compromise without vendor patches currently available.

Business Impact: High
Compensating Controls

Implement network segmentation isolating Modbus RTU devices from untrusted networks; deploy network intrusion detection/prevention systems (IDS/IPS) configured to detect malformed Modbus packets; restrict TCP port access to only authorized management systems using firewall rules; disable Modbus RTU over TCP functionality if not operationally required; enforce strong authentication credentials and disable default accounts; monitor device availability and connection logs for anomalies indicating denial of service attempts.

Threat Intelligence Overview

EPSS Score
0.0%
Top 88% exploitable
Prevalence
Low
niche industrial energy-metering device, limited OT/ICS deployment footprint
Data Quality
4 sources
Confidence: Medium

How this decision was reached

The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.

SignalValue
Severity MEDIUM
CISA KEV No
Public POC No
EPSS 0.0%
Patch available No
Active threat No
Deciding rule
MEDIUM severity (CVSS 4.0-6.9)
What every action level means
Emergency Immediate action required. Criteria: CRITICAL + in CISA KEV (actively exploited) without patch, OR CRITICAL + EPSS > 30% without patch, OR CRITICAL + active threat signals without patch.
Act Now Prioritize within 24-48h. Criteria: in KEV with patch available, OR CRITICAL + public POC, OR HIGH + EPSS > 10%, OR CRITICAL + active threat, OR any CRITICAL severity.
This Week Schedule remediation this week. Criteria: HIGH severity (CVSS 7.0-8.9). Patch within normal change window.
This Month Plan within 30 days. Criteria: MEDIUM severity (CVSS 4.0-6.9), lower exploitation probability. Include in regular patch cycle.
Monitor Track and reassess. Criteria: LOW severity (CVSS 0.1-3.9), minimal exploitation risk. No immediate action needed.

SSVC AssessmentENISA

SSVC Decision· derived
Scheduled
Exploitation· derived
None
System Exposure· derived
Open
Automatable· derived
Yes
Human Impact
High

Priority Score

32
Low Medium High Critical
KEV: 0
EPSS: 0
CVSS: +32
PoC: 0
Weaponized: 0
Threat intel: 0
Gov advisory: 0

Attack Technique

Authentication bypass attacks exploit flaws in the verification mechanisms that control access to systems and applications.

Denial of Service attacks render applications or systems unavailable by overwhelming resources or triggering failure conditions.

CVE-2024-53684 HIGH
8.8 Dec 01

A cross-site request forgery (csrf) vulnerability exists in the WEBVIEW-M functionality of Socomec DIRIS Digiware M-70 1

CVE-2025-26858 HIGH
7.5 Dec 01

Unauthenticated denial of service in Socomec DIRIS Digiware M-70 power-monitoring devices running firmware 1.6.9, where

CVE-2025-55222 HIGH
7.5 Dec 01

Unauthenticated denial of service in Socomec DIRIS Digiware M-70 firmware 1.6.9 allows remote attackers to crash or disa

CVE-2025-55221 HIGH
7.5 Dec 01

Unauthenticated denial of service in Socomec DIRIS Digiware M-70 firmware 1.6.9 lets any host that can reach the device'

CVE-2025-54851 HIGH
7.5 Dec 01

A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiwa

CVE-2025-54850 HIGH
7.5 Dec 01

A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiwa

CVE-2025-23417 HIGH
7.5 Dec 01

A single unauthenticated network packet sent to the Modbus RTU-over-TCP service of a Socomec DIRIS Digiware M-70 power-m

CVE-2024-48882 HIGH
7.5 Dec 01

A denial of service vulnerability exists in the Modbus TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A special

CVE-2024-48894 HIGH
7.5 Dec 01

A cleartext transmission vulnerability exists in the WEBVIEW-M functionality of Socomec DIRIS Digiware M-70 1.6.9. A spe

CVE-2024-49572 MEDIUM
6.5 Dec 01

A denial of service vulnerability exists in the Modbus TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A special

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy