1DescriptionNVD
The Trend Controls IC protocol through 2022-05-06 allows Cleartext Transmission of Sensitive Information. According to FSCT-2022-0050, there is a Trend Controls Inter-Controller (IC) protocol cleartext transmission of credentials issue. The affected components are characterized as: Inter-Controller (IC) protocol (57612/UDP). The potential impact is: Compromise of credentials. Several Trend Controls building automation controllers utilize the Inter-Controller (IC) protocol in for information exchange and automation purposes. This protocol offers authentication in the form of a 4-digit PIN in order to protect access to sensitive operations like strategy uploads and downloads as well as optional 0-30 character username and password protection for web page access protection. Both the PIN and usernames and passwords are transmitted in cleartext, allowing an attacker with passive interception capabilities to obtain these credentials. Credentials are transmitted in cleartext. An attacker who obtains Trend IC credentials can carry out sensitive engineering actions such as manipulating controller strategy or configuration settings. If the credentials in question are (re)used for other applications, their compromise could potentially facilitate lateral movement.
AnalysisAI
The Trend Controls IC protocol through 2022-05-06 allows Cleartext Transmission of Sensitive Information. Rated medium severity (CVSS 6.5), this vulnerability is no authentication required, low attack complexity. No vendor patch available.
Technical ContextAI
This vulnerability is classified under CWE-319. The Trend Controls IC protocol through 2022-05-06 allows Cleartext Transmission of Sensitive Information. According to FSCT-2022-0050, there is a Trend Controls Inter-Controller (IC) protocol cleartext transmission of credentials issue. The affected components are characterized as: Inter-Controller (IC) protocol (57612/UDP). The potential impact is: Compromise of credentials. Several Trend Controls building automation controllers utilize the Inter-Controller (IC) protocol in for information exchange and automation purposes. This protocol offers authentication in the form of a 4-digit PIN in order to protect access to sensitive operations like strategy uploads and downloads as well as optional 0-30 character username and password protection for web page access protection. Both the PIN and usernames and passwords are transmitted in cleartext, allowing an attacker with passive interception capabilities to obtain these credentials. Credentials are transmitted in cleartext. An attacker who obtains Trend IC credentials can carry out sensitive engineering actions such as manipulating controller strategy or configuration settings. If the credentials in question are (re)used for other applications, their compromise could potentially facilitate lateral movement. Affected products include: Honeywell Trend Iq412 Firmware, Honeywell Trend Iq411 Firmware, Honeywell Trend Iq422 Firmware, Honeywell Trend Iq4Nc Firmware, Honeywell Trend Iq4E Firmware. Version information: through 2022.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Apply vendor patches when available. Implement network segmentation and monitoring as interim mitigations.
An ActiveX control in HscRemoteDeploy.dll in Honeywell Enterprise Buildings Integrator (EBI) R310, R400.2, R410.1, and R
Directory traversal vulnerability in the FTP server on Honeywell Excel Web XL1000C50 52 I/O, XL1000C100 104 I/O, XL1000C
Improper Input Validation vulnerability in Honeywell PM43 on 32 bit, ARM (Printer web page modules) allows Command Injec
Honeywell NVR devices allow remote attackers to create a user account in the admin group by leveraging access to a guest
Honeywell Intermec PM23, PM42, PM43, PC23, PC43, PD43, and PC42 industrial printers before 10.11.013310 and 10.12.x befo
Multiple stack-based buffer overflows in (1) HWOPOSScale.ocx and (2) HWOPOSSCANNER.ocx in Honeywell OPOS Suite before 1.
A cross-site scripting (XSS) vulnerability in the component /test/ of iq3xcite v2.31 to v3.05 allows attackers to execut
Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability in Honeywell MB
Unauthenticated access to Honeywell IQ4x building controller HMI. CVSS 10.0.
An issue was discovered in Honeywell XL Web II controller XL1000C500 XLWebExe-2-01-00 and prior, and XLWeb 500 XLWebExe-
An issue was discovered in Honeywell XL Web II controller XL1000C500 XLWebExe-2-01-00 and prior, and XLWeb 500 XLWebExe-
Controller may be loaded with malicious firmware which could enable remote code execution. Rated critical severity (CVSS