Skip to main content

Relion 670 Firmware CVE-2021-27196

HIGH
Improper Input Validation (CWE-20)
2021-06-14 cve@mitre.org
7.5
CVSS 3.1 · NVD
Share

Severity by source

NVD PRIMARY
7.5 HIGH
AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Primary rating from NVD · only source for this CVE.

CVSS VectorNVD

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Attack Vector
Network
Attack Complexity
Low
Privileges Required
None
User Interaction
None
Scope
Unchanged
Confidentiality
None
Integrity
None
Availability
High

Lifecycle Timeline

1
CVE Published
Jun 14, 2021 - 22:15 nvd
HIGH 7.5

DescriptionNVD

Improper Input Validation vulnerability in Hitachi ABB Power Grids Relion 670 Series, Relion 670/650 Series, Relion 670/650/SAM600-IO, Relion 650, REB500, RTU500 Series, FOX615 (TEGO1), MSM, GMS600, PWC600 allows an attacker with access to the IEC 61850 network with knowledge of how to reproduce the attack, as well as the IP addresses of the different IEC 61850 access points (of IEDs/products), to force the device to reboot, which renders the device inoperable for approximately 60 seconds. This vulnerability affects only products with IEC 61850 interfaces. This issue affects: Hitachi ABB Power Grids Relion 670 Series 1.1; 1.2.3 versions prior to 1.2.3.20; 2.0 versions prior to 2.0.0.13; 2.1; 2.2.2 versions prior to 2.2.2.3; 2.2.3 versions prior to 2.2.3.2. Hitachi ABB Power Grids Relion 670/650 Series 2.2.0 versions prior to 2.2.0.13. Hitachi ABB Power Grids Relion 670/650/SAM600-IO 2.2.1 versions prior to 2.2.1.6. Hitachi ABB Power Grids Relion 650 1.1; 1.2; 1.3 versions prior to 1.3.0.7. Hitachi ABB Power Grids REB500 7.3; 7.4; 7.5; 7.6; 8.2; 8.3. Hitachi ABB Power Grids RTU500 Series 7.x version 7.x and prior versions; 8.x version 8.x and prior versions; 9.x version 9.x and prior versions; 10.x version 10.x and prior versions; 11.x version 11.x and prior versions; 12.x version 12.x and prior versions. Hitachi ABB Power Grids FOX615 (TEGO1) R1D02 version R1D02 and prior versions. Hitachi ABB Power Grids MSM 2.1.0 versions prior to 2.1.0. Hitachi ABB Power Grids GMS600 1.3.0 version 1.3.0 and prior versions. Hitachi ABB Power Grids PWC600 1.0 versions prior to 1.0.1.4; 1.1 versions prior to 1.1.0.1.

AnalysisAI

Improper Input Validation vulnerability in Hitachi ABB Power Grids Relion 670 Series, Relion 670/650 Series, Relion 670/650/SAM600-IO, Relion 650, REB500, RTU500 Series, FOX615 (TEGO1), MSM, GMS600,. Rated high severity (CVSS 7.5), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.

Technical ContextAI

This vulnerability is classified under CWE-20. Improper Input Validation vulnerability in Hitachi ABB Power Grids Relion 670 Series, Relion 670/650 Series, Relion 670/650/SAM600-IO, Relion 650, REB500, RTU500 Series, FOX615 (TEGO1), MSM, GMS600, PWC600 allows an attacker with access to the IEC 61850 network with knowledge of how to reproduce the attack, as well as the IP addresses of the different IEC 61850 access points (of IEDs/products), to force the device to reboot, which renders the device inoperable for approximately 60 seconds. This vulnerability affects only products with IEC 61850 interfaces. This issue affects: Hitachi ABB Power Grids Relion 670 Series 1.1; 1.2.3 versions prior to 1.2.3.20; 2.0 versions prior to 2.0.0.13; 2.1; 2.2.2 versions prior to 2.2.2.3; 2.2.3 versions prior to 2.2.3.2. Hitachi ABB Power Grids Relion 670/650 Series 2.2.0 versions prior to 2.2.0.13. Hitachi ABB Power Grids Relion 670/650/SAM600-IO 2.2.1 versions prior to 2.2.1.6. Hitachi ABB Power Grids Relion 650 1.1; 1.2; 1.3 versions prior to 1.3.0.7. Hitachi ABB Power Grids REB500 7.3; 7.4; 7.5; 7.6; 8.2; 8.3. Hitachi ABB Power Grids RTU500 Series 7.x version 7.x and prior versions; 8.x version 8.x and prior versions; 9.x version 9.x and prior versions; 10.x version 10.x and prior versions; 11.x version 11.x and prior versions; 12.x version 12.x and prior versions. Hitachi ABB Power Grids FOX615 (TEGO1) R1D02 version R1D02 and prior versions. Hitachi ABB Power Grids MSM 2.1.0 versions prior to 2.1.0. Hitachi ABB Power Grids GMS600 1.3.0 version 1.3.0 and prior versions. Hitachi ABB Power Grids PWC600 1.0 versions prior to 1.0.1.4; 1.1 versions prior to 1.1.0.1. Affected products include: Hitachienergy Relion 670 Firmware, Hitachienergy Relion 650 Firmware, Hitachienergy Relion Sam600-Io Firmware, Hitachienergy Rtu500 Firmware, Hitachienergy Reb500 Firmware. Version information: prior to 1.2.3.20.

RemediationAI

No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Apply vendor patches when available. Implement network segmentation and monitoring as interim mitigations.

Share

CVE-2021-27196 vulnerability details – vuln.today

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy