Skip to main content

Severity by source

NVD PRIMARY
7.5 HIGH
AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N

Primary rating from NVD · only source for this CVE.

CVSS VectorNVD

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N
Attack Vector
Network
Attack Complexity
Low
Privileges Required
None
User Interaction
None
Scope
Unchanged
Confidentiality
None
Integrity
High
Availability
None

Lifecycle Timeline

1
CVE Published
Aug 13, 2019 - 19:15 nvd
HIGH 7.5

DescriptionNVD

A vulnerability has been identified in SIMATIC Drive Controller family (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V20.8), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V20.8), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.4.0), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.4.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.8.1), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.8.1), SIMATIC S7-1500 Software Controller (All versions < V20.8), SIMATIC S7-1500 Software Controller (All versions >= V20.8), SIMATIC S7-PLCSIM Advanced (All versions < V3.0), SIMATIC S7-PLCSIM Advanced (All versions >= V3.0). An attacker with network access to port 102/tcp could potentially modify the user program on the PLC in a way that the running code is different from the source code which is stored on the device. An attacker must have network access to affected devices and must be able to perform changes to the user program. The vulnerability could impact the perceived integrity of the user program stored on the CPU. An engineer that tries to obtain the code of the user program running on the device, can receive different source code that is not actually running on the device.

AnalysisAI

A vulnerability has been identified in SIMATIC Drive Controller family (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. Rated high severity (CVSS 7.5), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.

Technical ContextAI

This vulnerability is classified under CWE-353. A vulnerability has been identified in SIMATIC Drive Controller family (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V20.8), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V20.8), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.4.0), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.4.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.8.1), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.8.1), SIMATIC S7-1500 Software Controller (All versions < V20.8), SIMATIC S7-1500 Software Controller (All versions >= V20.8), SIMATIC S7-PLCSIM Advanced (All versions < V3.0), SIMATIC S7-PLCSIM Advanced (All versions >= V3.0). An attacker with network access to port 102/tcp could potentially modify the user program on the PLC in a way that the running code is different from the source code which is stored on the device. An attacker must have network access to affected devices and must be able to perform changes to the user program. The vulnerability could impact the perceived integrity of the user program stored on the CPU. An engineer that tries to obtain the code of the user program running on the device, can receive different source code that is not actually running on the device. Affected products include: Siemens Simatic Et 200Sp Open Controller Cpu 1515Sp Pc Firmware, Siemens Simatic Et 200Sp Open Controller Cpu 1515Sp Pc2 Firmware, Siemens Simatic S7-1200 Cpu 1211C Firmware, Siemens Simatic S7-1200 Cpu 1212C Firmware, Siemens Simatic S7-1200 Cpu 1214C Firmware.

RemediationAI

No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Apply vendor patches when available. Implement network segmentation and monitoring as interim mitigations.

Share

CVE-2019-10943 vulnerability details – vuln.today

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy