Attack ChainAIDerived
Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain
-
AccessIdentify RSLinx Classic host with CIP port exposed
-
DeliveryCraft CIP packet with manipulated data length field
-
ExploitDeliver packet to TCP 44818
-
ExecutionTrigger integer underflow in length validation
-
PersistRSLinx Classic service crashes
-
ImpactOperator loses PLC communication until manual service restart
Vulnerability Assessment
| Weakness |
CWE
ASVS 5.0
V15 - Secure Coding and Architecture Integer underflow checks
|
| Exploitation Conditions | The RSLinx Classic service must be running and its CIP communication port (typically TCP 44818 or UDP 2222) must be reachable by the attacker over the network. The CVSS 4.0 vector confirms PR:N and UI:N - no authentication or user interaction is required, and the attack is effective against the default service configuration. Exploitation is limited to denial-of-service only; no confidentiality or integrity impact is achievable through this vector. Environments that enforce strict network segmentation restricting CIP port access to authorized engineering workstations only materially reduce exposure by preventing unauthenticated external packets from reaching the service. |
| Impact | The CVSS 4.0 vector (AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H) confirms a high-severity, unauthenticated, zero-complexity denial-of-service with no privileges or user interaction required. In ICS environments, RSLinx Classic serves as the communication backbone between HMIs, SCADA systems, and PLCs - crashing it disrupts operator visibility and remote configuration across the production floor. EPSS data is absent from available intelligence, and the vulnerability is not in the CISA KEV catalog at time of analysis, so active exploitation in the wild is not confirmed. No POC is publicly available. Despite the absence of active exploitation evidence, the combination of zero authentication requirements, broad network accessibility on standard CIP ports, and the operational criticality of RSLinx Classic in industrial environments means this should be treated as urgent - availability loss in OT contexts can directly translate to production outages or delayed safety responses. |
| Exploit ScenarioDerived | An attacker with network access to the CIP port of a host running RSLinx Classic sends a single malformed CIP packet containing a manipulated data length field. The integer underflow in the RSLinx Classic service parser causes an immediate service crash, severing the communication link between engineering workstations and connected PLCs. Production operators lose real-time data visibility and remote reconfiguration capability until IT or OT staff manually restart the service, potentially causing production halts or delayed incident response. |
Get an e-mail when this CVE is exploited, patched or re-scored. Free account.
Alert meAnalysisAIv1 – Sep 01, 2026
Denial-of-service in Rockwell Automation RSLinx Classic allows unauthenticated remote attackers to crash the communication service by sending a specially crafted CIP packet with a manipulated data length field. The root cause is an integer underflow (CWE-191) in the packet length validation routine, causing the service to terminate and requiring a manual restart to recover. No public exploit has been identified at time of analysis and the vulnerability is not listed in CISA KEV, but the zero-barrier network attack vector against a critical ICS communication layer makes this a high-priority remediation target.
RemediationAI
Consult Rockwell Automation security advisory SD1794 (https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1794.html) to obtain the patched release - a specific fixed version number is not confirmed in the available intelligence and should not be assumed. As compensating controls pending patch deployment, restrict inbound access to RSLinx Classic's CIP ports (TCP 44818, UDP 2222) to only known, authorized engineering workstation IP addresses using host-based or network-layer firewall allowlist rules; this blocks unauthenticated external packet delivery without disrupting legitimate PLC communications from approved hosts. ICS-aware network monitoring capable of detecting malformed or anomalous CIP packet lengths provides an additional detection layer. Note that overly broad CIP port restrictions will disrupt HMI and SCADA connectivity, so allowlist-based rules are strongly preferred over blanket blocks.
Affected VersionsENISA
Affects your stack
Find out whether the stacks and servers you run are on an affected version.
Checking this CVE against your own stacks and servers is part of the Basic plan and up.
Technical ContextAI · show details
RSLinx Classic is Rockwell Automation's OPC server and communication driver software, providing connectivity between engineering workstations and Allen-Bradley PLCs via the Common Industrial Protocol (CIP) over EtherNet/IP. CWE-191 (Integer Underflow/Wrap or Wraparound) describes the root cause: a crafted CIP packet with a manipulated length field causes the parser's integer counter to underflow, resulting in an attempt to process insufficient or invalid data and a subsequent service crash. The CPE string cpe:2.3:a:rockwell_automation:rslinx_classic®:*:*:*:*:*:*:*:* covers all versions with no lower or upper bound specified. CIP is typically exposed on TCP port 44818 and UDP 2222; in many OT environments these ports receive minimal network-layer filtering.
Know when Rslinx Classic gets its next vulnerability
- Watch products and get an email when something new is published
- Check this CVE against your own stack and servers
- Exploit and PoC references, threat intelligence from 22 sources
No credit card · 7-day full trial
Severity by source
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N
Unauthenticated network DoS with no confidentiality or integrity impact; scope unchanged as the crash is confined to the RSLinx Classic service process.
Primary rating from Vendor (Rockwell).
CVSS VectorVendor: Rockwell
DescriptionCVE.org
A denial-of-service security issue exists within RSLinx® Classic. A crafted CIP packet can cause the RSLinx® Classic service to crash due to insufficient data length validation, requiring a restart of the service to recover.
Executive ViewAI
Rockwell Automation RSLinx Classic contains a network-accessible denial-of-service vulnerability (CVSS 8.7) affecting critical ICS communication infrastructure; unauthenticated remote attackers can crash the communication service by sending a crafted CIP packet, requiring manual restart and causing production downtime. No public exploit has been identified at time of analysis, but the zero-barrier remote attack vector and absence of a vendor patch create urgent risk for manufacturing and control system environments. Organizations must immediately implement network containment and monitoring to reduce exposure until a patch becomes available.
Until vendor-released patch becomes available: (1) Restrict CIP communication port access using firewall rules, limiting source IP addresses to known trusted systems only; (2) Implement network segmentation isolating RSLinx Classic systems from untrusted network segments and external access; (3) Deploy continuous monitoring and alerting for RSLinx Classic service availability and abnormal CIP packet patterns; (4) Establish rapid restart procedures and maintain redundant communication paths to minimize downtime if exploitation occurs; (5) Maintain regular contact with Rockwell Automation for patch availability updates.
Threat Intelligence Overview
How this decision was reached
The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.
What every action level means
SSVC AssessmentENISA
Priority Score
Attack Technique
Denial of Service attacks render applications or systems unavailable by overwhelming resources or triggering failure conditions.
More in Rslinx Classic
View allAn unquoted search path or element in RSLinx Classic Versions 3.90.01 and prior and FactoryTalk Linx Gateway Versions 3.
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Versio
Remote denial-of-service in Rockwell Automation RSLinx Classic allows an unauthenticated network attacker to crash the R
Unauthenticated denial-of-service in Rockwell Automation RSLinx Classic allows a remote attacker to crash the communicat
Denial-of-service in Rockwell Automation RSLinx Classic allows unauthenticated remote attackers to crash the RSLinx Clas
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Versio
In Rockwell Automation RSLinx Classic versions 4.11.00 and prior, an authenticated local attacker could modify a registr
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Versio
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Versio
EUVD-2026-69140
GHSA-gcxp-mxpm-5m5v
NVD
CVE.org
EPSS
Vulnrichment
Exploit-DB