Factorytalk Linx
CVE-2020-12005
HIGH
Severity by source
AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Primary rating from NVD · only source for this CVE.
CVSS VectorNVD
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Lifecycle Timeline
1DescriptionNVD
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. A vulnerability exists in the communication function that enables users to upload EDS files by FactoryTalk Linx. This may allow an attacker to upload a file with bad compression, consuming all the available CPU resources, leading to a denial-of-service condition.
AnalysisAI
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version. Rated high severity (CVSS 7.5), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
Technical ContextAI
This vulnerability is classified as Unrestricted File Upload (CWE-434), which allows attackers to upload malicious files that can be executed on the server. FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. A vulnerability exists in the communication function that enables users to upload EDS files by FactoryTalk Linx. This may allow an attacker to upload a file with bad compression, consuming all the available CPU resources, leading to a denial-of-service condition. Affected products include: Rockwellautomation Factorytalk Linx, Rockwellautomation Rslinx Classic. Version information: Version 12.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Validate file types server-side, store uploads outside webroot, use random filenames, scan for malware.
More in Factorytalk Linx
View allA heap overflow vulnerability exists within FactoryTalk Linx Version 6.11 and prior. Rated critical severity (CVSS 9.8),
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Versio
FactoryTalk Linx, in the Rockwell Automation PanelView Plus, allows an unauthenticated threat actor to read data from me
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Versio
An attacker-controlled memory allocation size can be passed to the C++ new operator in RnaDaSvr.dll by sending a special
An attacker can craft and send an OpenNamespace message to port 4241 with valid session-id that triggers an unhandled ex
A heap overflow vulnerability exists within FactoryTalk Linx Version 6.11 and prior. Rated high severity (CVSS 7.5), thi
A flaw exists in the Ingress/Egress checks routine of FactoryTalk Linx Version 6.11 and prior. Rated high severity (CVSS
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Versio
An attacker-controlled memory allocation size can be passed to the C++ new operator in the CServerManager::HandleBrowseL
A security issue exists within the FactoryTalk Linx Network Browser. Rated high severity (CVSS 8.4), this vulnerability