Skip to main content

1756-EN2/ENBT Modules EUVDEUVD-2026-43695

| CVE-2026-9653 HIGH
Improper Validation of Integrity Check Value (CWE-354)
2026-07-14 Rockwell GHSA-w8xr-7458-qr4m
8.7
CVSS 4.0 · Vendor: Rockwell
Share

Severity by source

Vendor (Rockwell) PRIMARY
8.7 HIGH
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
vuln.today AI
7.5 HIGH

Remote, unauthenticated, low-complexity CIP packet triggers availability-only impact (A:H); no confidentiality or integrity effect, though disruption is transient and self-recovering.

3.1 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
4.0 AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N

Primary rating from Vendor (Rockwell).

CVSS VectorVendor: Rockwell

Attack Vector
Network
Attack Complexity
Low
Privileges Required
None
User Interaction
None
Scope
X

Lifecycle Timeline

2
Analysis Generated
Jul 14, 2026 - 15:35 vuln.today
CVE Published
Jul 14, 2026 - 15:00 cve.org
HIGH 8.7

DescriptionCVE.org

A denial-of-service security issue exists across all the 1756-EN2, EN3, and ENBT communication module due to improper validation of CIP Implicit Connection packets. An attacker on the network can exploit this by sending crafted packets to continuously disrupt device connections, though device connections will recover immediately after.

AnalysisAI

Denial-of-service in Rockwell Automation 1756-EN2, 1756-EN3, and 1756-ENBT ControlLogix EtherNet/IP communication modules lets an unauthenticated network attacker drop active device connections by sending malformed CIP Implicit (I/O) Connection packets. Because CVSS 4.0 rates only availability impact (VC:N/VI:N/VA:H) and connections recover immediately once the traffic stops, the flaw enables repeatable disruption rather than persistent outage or code execution. No public exploit identified at time of analysis, and the module is not in CISA KEV.

Technical ContextAI

The affected products are Rockwell Automation ControlLogix communication bridge modules (1756-EN2, 1756-EN3, 1756-ENBT) that carry EtherNet/IP traffic between the ControlLogix backplane and industrial networks. The defect lies in how the module validates CIP (Common Industrial Protocol) Implicit Connection packets - the connected, cyclic UDP messaging used for real-time I/O data exchange. CWE-354 (Improper Validation of Integrity Check Value) indicates the module accepts and acts on Implicit Connection packets without adequately verifying their integrity, so crafted packets are processed in a way that tears down or resets legitimate connections. Implicit messaging is a core, always-on function of these modules in any EtherNet/IP control deployment, making the affected code path reachable in normal operation.

RemediationAI

Patch available per vendor advisory: consult Rockwell Automation Security Advisory SD1780 at https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1780.html for the corrected firmware revision, as no exact fix version is included in the provided data - apply the vendor-specified firmware update to the 1756-EN2, 1756-EN3, and 1756-ENBT modules. Where immediate patching is not feasible in a controlled OT change window, restrict EtherNet/IP/CIP reachability by segmenting the control network behind an OT firewall and permitting CIP UDP (implicit I/O, port 2222) and TCP 44818 only from trusted controllers and engineering workstations; this reduces exposure but does not eliminate risk from an attacker already inside the control segment. Because the disruption self-recovers, monitoring for repeated CIP connection resets can serve as a detection compensating control, though it does not prevent the disruption itself.