Skip to main content

1756-EN2/ENBT Modules EUVDEUVD-2026-43695

| CVE-2026-9653 HIGH
Improper Validation of Integrity Check Value (CWE-354)
2026-07-14 Rockwell GHSA-w8xr-7458-qr4m
8.7
CVSS 4.0 · Vendor: Rockwell
View

Attack ChainAIDerived

Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain

  1. Access
    Gain access to OT/control network
  2. Delivery
    Craft malicious CIP Implicit Connection packets
  3. Exploit
    Send to 1756-EN2/EN3/ENBT module
  4. Execution
    Integrity validation fails, connections drop
  5. Impact
    Sustain traffic to continuously disrupt I/O

Vulnerability Assessment

Weakness
CWE
OWASP Top 10:2025
A08:2025 - Software or Data Integrity Failures
ASVS 5.0
V15 - Secure Coding and Architecture Integrity verification
Exploitation Conditions

Exploitation requires network-layer reachability to the module's EtherNet/IP/CIP interface and the ability to send crafted CIP Implicit (connected I/O) Connection packets; no authentication, credentials, or user interaction are needed (PR:N/UI:N/AC:L). The limiting factors are practical rather than configuration-based: the attacker must be positioned on a network path that can reach the module's CIP messaging (typically the OT/control segment), and disruption persists only while malicious traffic continues because connections recover immediately once it stops - meaning the attacker must maintain a sustained packet stream to keep the device disrupted. There is no persistence, no privilege escalation, and no data exposure.

Impact

The vendor CVSS 4.0 base score is 8.7 (High), driven entirely by high availability impact (VA:H) with a fully remote, low-complexity, unauthenticated vector (AV:N/AC:L/PR:N/UI:N). This is a genuine OT-availability concern: no authentication, no user interaction, and network-reachable. However, the real-world severity is tempered by the description's explicit note that connections recover immediately after the crafted traffic stops - so impact is transient disruption requiring sustained attacker traffic, not a durable outage or safety-state compromise. There is no confidentiality or integrity impact. EPSS is not provided, KEV status is not listed (no active exploitation), and no POC is referenced, so exploitation probability is unquantified but there is no evidence of exploitation in the wild. One data conflict to flag: the Tags include 'Information Disclosure,' which contradicts the description and the CVSS vector (VC:N - no confidentiality impact); the tag appears mislabeled and should be treated as a DoS issue per the authoritative description and vector.

Exploit ScenarioDerived

An attacker with access to the industrial network (for example, via a compromised HMI, engineering workstation, or an exposed control segment) sends a stream of crafted CIP Implicit Connection packets to a 1756-EN2/EN3/ENBT module. The malformed packets fail integrity handling and cause active I/O connections to drop, disrupting real-time communication between the controller and downstream devices for as long as the attacker sustains the traffic. No POC is referenced in the provided data.

This Week Schedule remediation this week. Why: Active threat signals + CRITICAL/HIGH severity.
No patch listed yet 0.2% exploitation probability (EPSS)

Get an e-mail when this CVE is exploited, patched or re-scored. Free account.

Alert me

AnalysisAIv1 – Jul 14, 2026

Denial-of-service in Rockwell Automation 1756-EN2, 1756-EN3, and 1756-ENBT ControlLogix EtherNet/IP communication modules lets an unauthenticated network attacker drop active device connections by sending malformed CIP Implicit (I/O) Connection packets. Because CVSS 4.0 rates only availability impact (VC:N/VI:N/VA:H) and connections recover immediately once the traffic stops, the flaw enables repeatable disruption rather than persistent outage or code execution. No public exploit identified at time of analysis, and the module is not in CISA KEV.

RemediationAI

Patch available per vendor advisory: consult Rockwell Automation Security Advisory SD1780 at https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1780.html for the corrected firmware revision, as no exact fix version is included in the provided data - apply the vendor-specified firmware update to the 1756-EN2, 1756-EN3, and 1756-ENBT modules. Where immediate patching is not feasible in a controlled OT change window, restrict EtherNet/IP/CIP reachability by segmenting the control network behind an OT firewall and permitting CIP UDP (implicit I/O, port 2222) and TCP 44818 only from trusted controllers and engineering workstations; this reduces exposure but does not eliminate risk from an attacker already inside the control segment. Because the disruption self-recovers, monitoring for repeated CIP connection resets can serve as a detection compensating control, though it does not prevent the disruption itself.

Affected VersionsENISA

1756-ENBT 6.006
1756-EN2, 1756-EN3 12.001 and before

Affected Packages

euvd 1756_enbt no fix

Source: OSV (Open Source Vulnerabilities)

Affects your stack

Affects 1 package in euvd

Checking this CVE against your own stacks and servers is part of the Basic plan and up.

Technical ContextAI · show details

The affected products are Rockwell Automation ControlLogix communication bridge modules (1756-EN2, 1756-EN3, 1756-ENBT) that carry EtherNet/IP traffic between the ControlLogix backplane and industrial networks. The defect lies in how the module validates CIP (Common Industrial Protocol) Implicit Connection packets - the connected, cyclic UDP messaging used for real-time I/O data exchange. CWE-354 (Improper Validation of Integrity Check Value) indicates the module accepts and acts on Implicit Connection packets without adequately verifying their integrity, so crafted packets are processed in a way that tears down or resets legitimate connections. Implicit messaging is a core, always-on function of these modules in any EtherNet/IP control deployment, making the affected code path reachable in normal operation.

Know when 1756 Enbt gets its next vulnerability

  • Watch products and get an email when something new is published
  • Check this CVE against your own stack and servers
  • Exploit and PoC references, threat intelligence from 22 sources

No credit card · 7-day full trial

Severity by source

Vendor (Rockwell) PRIMARY 8.7 HIGH
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N
vuln.today AI 7.5 HIGH

Remote, unauthenticated, low-complexity CIP packet triggers availability-only impact (A:H); no confidentiality or integrity effect, though disruption is transient and self-recovering.

3.1 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
4.0 AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N

Primary rating from Vendor (Rockwell).

CVSS VectorVendor: Rockwell

Attack Vector
Network
Attack Complexity
Low
Attack Requirements
None
Privileges Required
None
User Interaction
None
Vulnerable system: Confidentiality
None
Vulnerable system: Integrity
None
Vulnerable system: Availability
High
Subsequent system: Confidentiality
None
Subsequent system: Integrity
None
Subsequent system: Availability
None

DescriptionCVE.org

A denial-of-service security issue exists across all the 1756-EN2, EN3, and ENBT communication module due to improper validation of CIP Implicit Connection packets. An attacker on the network can exploit this by sending crafted packets to continuously disrupt device connections, though device connections will recover immediately after.

Executive ViewAI

Why It Matters

ControlLogix communication modules (1756-EN2, 1756-EN3, 1756-ENBT) deployed in manufacturing and utility environments are vulnerable to network-based denial-of-service attacks that repeatedly interrupt device connections without requiring authentication. Though affected connections recover when attacks cease, the repeatable disruption capability creates operational availability risk to production systems. No vendor patch is currently available to remediate the vulnerability.

Business Impact: High
Compensating Controls

Implement firewall rules restricting CIP traffic to authorized sources; deploy intrusion detection systems with signatures for malformed CIP packets; establish network segmentation isolating critical ControlLogix systems from untrusted networks; maintain network monitoring and packet logging; evaluate air-gapping options for the most critical systems; monitor Rockwell Automation security advisories for patch availability.

Threat Intelligence Overview

EPSS Score
0.2%
Top 93% exploitable
Prevalence
Medium
Common Rockwell ControlLogix EtherNet/IP modules in industrial OT, not general IT
Threat Intel
1
1 sources
Data Quality
3 sources
Confidence: Low

How this decision was reached

The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.

SignalValue
Severity HIGH
CISA KEV No
Public POC No
EPSS 0.2%
Patch available No
Active threat Yes
Deciding rule
Active threat signals + CRITICAL/HIGH severity
What every action level means
Emergency Immediate action required. Criteria: CRITICAL + in CISA KEV (actively exploited) without patch, OR CRITICAL + EPSS > 30% without patch, OR CRITICAL + active threat signals without patch.
Act Now Prioritize within 24-48h. Criteria: in KEV with patch available, OR CRITICAL + public POC, OR HIGH + EPSS > 10%, OR CRITICAL + active threat, OR any CRITICAL severity.
This Week Schedule remediation this week. Criteria: HIGH severity (CVSS 7.0-8.9). Patch within normal change window.
This Month Plan within 30 days. Criteria: MEDIUM severity (CVSS 4.0-6.9), lower exploitation probability. Include in regular patch cycle.
Monitor Track and reassess. Criteria: LOW severity (CVSS 0.1-3.9), minimal exploitation risk. No immediate action needed.

SSVC AssessmentENISA

SSVC Decision
Scheduled
Exploitation
None
System Exposure· derived
Open
Automatable
Yes
Human Impact
High
Technical Impact
Partial

Priority Score

54
Low Medium High Critical
KEV: 0
EPSS: 0
CVSS: +44
PoC: 0
Weaponized: 0
Threat intel: +10
Gov advisory: 0

Attack Technique

Information disclosure occurs when an application unintentionally exposes sensitive data that aids attackers in reconnaissance or directly compromises security.

Threat IntelligenceMISP

CISA Advisories
Sources: CISA Vulnrichment, CISA (public domain)

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy