Vulnerability Assessment
| Weakness |
CWE
OWASP Top 10:2025
A07:2025 - Authentication Failures
ASVS 5.0
V6 - Authentication Password recovery security
|
| Exploitation Conditions | The specific prerequisite is possession of the system 'unlock' challenge response, which the vendor states is common to all users and fixed across installations - so the attacker must first obtain this single static value 'by some means' (this is the CVSS AT:P attack requirement). Once that value is known it is universally reusable, since it is not per-user or per-installation. Exploitation requires network reachability to the affected ICONICS/GENESIS, GENESIS64, Hyper Historian, AnalytiX, MobileHMI, IoTWorX, MC Works64, GENESIS32, or BizViz component (AV:N) and NO authentication (PR:N) and NO user interaction (UI:N). The primary limiting factor is therefore the one-time effort to acquire the fixed challenge response; there is no required login, no victim interaction, and no documented non-default configuration needed beyond the system being deployed and network-accessible. |
| Impact | This is a genuine high-priority issue, not merely a high-CVSS paper risk. The CVSS 4.0 vector (AV:N/AC:L/AT:P/PR:N/UI:N) describes a network-reachable, low-complexity, unauthenticated flaw with high confidentiality, integrity, and availability impact (VC:H/VI:H/VA:H), scoring 9.2 (Critical). The root cause (CWE-640) is severe by design: per the description, the unlock challenge response is COMMON to all users and FIXED, meaning a single secret - once recovered - works everywhere across every affected installation, which is exactly the kind of systemic weakness that tends to spread quickly once disclosed. The one tempering signal is AT:P (Attack Requirements: Present), reflected in the phrase 'by obtaining the challenge response by some means' - the attacker must first acquire that fixed response, so exploitation is not purely spray-and-pray. Conflicting/missing data must be stated: there is NO EPSS score, NO CISA KEV listing, NO SSVC decision data, and NO public POC in the provided intelligence, so there is no public exploit identified at time of analysis and no evidence of active exploitation despite the critical score. The high CVSS therefore reflects design severity and worst-case impact, while the real-world exploitation likelihood currently depends on how easily the common/fixed challenge response can be obtained or reverse-engineered - a factor the vendor advisory (2026-006) should clarify. |
| Exploit ScenarioDerived | A remote attacker targeting an exposed ICONICS/GENESIS SCADA/HMI server obtains the fixed, universal challenge-response value (e.g., by extracting it from the software, a leaked sample, or another compromised deployment) and replays it to unlock the system without any valid user account. Once unlocked, the attacker reads or tampers with industrial process data and configuration, or forces the HMI/historian into a denial-of-service state. No public exploit identified at time of analysis, but the shared/fixed nature of the secret makes a reusable tool straightforward once the value is known. |
Get an e-mail when this CVE is exploited, patched or re-scored. Free account.
Alert meAnalysisAIv1 – Oct 15, 2026
Remote, unauthenticated attackers can unlock Mitsubishi Electric's ICONICS GENESIS, GENESIS64, ICONICS Suite and related SCADA/HMI products by obtaining the system's challenge-response unlock value, which the vendor confirms is fixed and identical for every user and every installation, after which the attacker can disclose, tamper with, destroy or delete internal information or force the system into a denial-of-service condition. Affected builds are GENESIS 11.03 and prior, GENESIS64/ICONICS Suite/Hyper Historian/AnalytiX/MobileHMI/IoTWorX 10.97.3 and prior, and MC Works64, GENESIS32 and BizViz at all versions. The vendor assigns CVSS 4.0 a 9.2 score, while our independent CVSS 3.1 assessment lands at 8.1 (AV:N/AC:H/PR:N/UI:N) because exploitation hinges on the one-time prerequisite of acquiring the static challenge response (the CVSS 4.0 AT:P attack requirement); no public exploit code and no confirmed active exploitation were identified at time of analysis, so the risk driver is the universal reusability of a single leaked value rather than any observed campaign.
RemediationAI
No vendor-released patch version is identified in the supplied data for any affected product; the authoritative remediation guidance is the Mitsubishi Electric PSIRT advisory 2026-006 (https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf) and JVN#93251594 (https://jvn.jp/vu/JVNVU#93251594/), which should be treated as the source of truth for fixed builds and for any vendor-supplied countermeasure. Because the unlock challenge response is fixed and common to all users, it cannot be rotated or per-site customized by the operator, so treat any exposure of that value as a permanent compromise of every GENESIS/GENESIS64/ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI, IoTWorX, MC Works64, GENESIS32 or BizViz instance reachable on the same network. The highest-value compensating control is to make the vulnerable unlock path unreachable: remove the affected systems from any internet-facing network and block inbound access to their management/unlock services at the firewall or industrial DMZ, accepting that this breaks legitimate remote support and recovery workflows. Where the product permits the unlock function to be restricted to a local console, disable or gate remote unlock and require on-site recovery, trading availability of remote recovery for removal of the unauthenticated attack path; segregate the remaining SCADA/HMI hosts into IEC 62443-style zones with deny-by-default rules and monitor logs for unlock or challenge-response exchanges. For MC Works64, GENESIS32 and BizViz, which are affected at all versions, network isolation and segmentation are the only controls the data supports. Operators should also assume process data, configuration and visualization logic on these hosts have been exposed and re-validate their integrity once access controls are in place.
Affected VersionsENISA
Affects your stack
Find out whether the stacks and servers you run are on an affected version.
Checking this CVE against your own stacks and servers is part of the Basic plan and up.
Technical ContextAI · show details
The root cause is CWE-640, Weak Password Recovery Mechanism for Forgotten Password. The affected platforms are ICONICS-built SCADA/HMI and industrial analytics software (GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI, IoTWorX, MC Works64, GENESIS32, BizViz) sold under both the Mitsubishi Electric Corporation and Mitsubishi Electric Iconics Digital Solutions CPE namespaces, which in the provided CPE data refer to the same product line. The flawed mechanism is the system 'unlock' challenge-response used to restore access when credentials are lost: because the expected response is hard-coded and shared across users and installations, it carries no per-user or per-installation entropy, and a single observed or reverse-engineered value is universally reusable. This is why the vendor's CVSS 4.0 vector marks AT:P (Attack Requirements: Present) - the attacker must first acquire that static response 'by some means', which is the real barrier and is reflected in our CVSS 3.1 AC:H rating. Once obtained, no login (PR:N), no user interaction (UI:N) and no non-default configuration are required, and only network reachability to the exposed component (AV:N) is needed, yielding high confidentiality, integrity and availability impact. The ecosystem context (SCADA/HMI, historian and MES-adjacent software) means successful exploitation exposes process data, visualization logic and control-adjacent configurations rather than a single application record.
Know when Genesis gets its next vulnerability
- Watch products and get an email when something new is published
- Check this CVE against your own stack and servers
- Exploit and PoC references, threat intelligence from 22 sources
No credit card · 7-day full trial
Severity by source
CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
Network-reachable and unauthenticated (AV:N/PR:N), but attacker must first obtain the fixed challenge response, mapping the 4.0 AT:P requirement to AC:H; full C/I/A impact per the described disclosure, tampering, and DoS.
Primary rating from Vendor (Mitsubishi).
CVSS VectorVendor: Mitsubishi
DescriptionCVE.org
Weak Password Recovery Mechanism for Forgotten Password vulnerability in Mitsubishi Electric GENESIS versions 11.03 and prior, GENESIS64 versions 10.97.3 and prior, ICONICS Suite versions 10.97.3 and prior, Hyper Historian versions 10.97.3 and prior, AnalytiX versions 10.97.3 and prior, MobileHMI 10.97.3 and prior, IoTWorX 10.97.3 and prior, MC Works64 all versions, GENESIS32 all versions, BizViz all versions, Mitsubishi Electric Iconics Digital Solutions GENESIS versions 11.03 and prior, GENESIS64 versions 10.97.3 and prior, ICONICS Suite versions 10.97.3 and prior, Hyper Historian versions 10.97.3 and prior, AnalytiX versions 10.97.3 and prior, MobileHMI 10.97.3 and prior, IoTWorX 10.97.3 and prior, GENESIS32 all versions, and BizViz all versions allows a remote attacker to unlock the system by obtaining the challenge response by some means. The challenge response used to unlock the system is common to all users and fixed. As a result, the attacker may disclose, tamper with, destroy, or delete internal information, or cause the affected system to enter a denial-of-service (DoS) condition.
Executive ViewAI
Mitsubishi Electric ICONICS GENESIS, GENESIS64, ICONICS Suite and related SCADA/HMI products are exposed to a critical authentication bypass that can allow remote unauthenticated attackers to unlock and manipulate industrial control systems, potentially causing data destruction or denial-of-service. No vendor-released patch identified at time of analysis, and no public exploit identified at time of analysis, but the affected systems often support physical operations, so leadership should treat this as an operational resilience, safety, and availability risk requiring immediate containment. Organizations running GENESIS 11.03 and prior, GENESIS64/ICONICS Suite/Hyper Historian/AnalytiX/MobileHMI/IoTWorX 10.97.3 and prior, and MC Works64, GENESIS32, or BizViz at all versions should prioritize exposure reduction while awaiting a fix.
No vendor-released patch identified at time of analysis; isolate affected GENESIS, GENESIS64, ICONICS Suite, MC Works64, GENESIS32, and BizViz systems behind segmented networks, remove direct internet exposure, restrict remote access with VPN/MFA and allowlists, monitor for challenge-response or unlock abuse, and apply any vendor-provided workarounds or configuration hardening until a patch is released.
Threat Intelligence Overview
How this decision was reached
The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.
What every action level means
SSVC AssessmentENISA
Priority Score
Attack Technique
Information disclosure occurs when an application unintentionally exposes sensitive data that aids attackers in reconnaissance or directly compromises security.
SQL Server credentials are displayed in cleartext within the Hyper Historian Splitter GUI across multiple Mitsubishi Ele
Plaintext SQL Server credential storage in Mitsubishi Electric SCADA/HMI products allows local authenticated attackers w
CVE-2026-16437 lets a locally authenticated administrator defeat the forgotten-password recovery mechanism in Mitsubishi
EUVD-2026-101939
GHSA-j5vq-rv93-4ff2
NVD
CVE.org
EPSS
Vulnrichment
VulDB
Exploit-DB