Attack ChainAIDerived
Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain
-
AccessGain adjacent-network foothold with elevated access
-
DeliverySatisfy required attack precondition
-
ExploitAbuse insecure default initialization to bypass auth
-
ExecutionAlter controller config/logic
-
ImpactCompromise integrity and availability of building systems
Vulnerability Assessment
| Weakness |
CWE
ASVS 5.0
V13 - Configuration Secure default settings
|
| Exploitation Conditions | Exploitation requires an insecurely-initialized default resource on the EasyIO FS32 controller to be present (the condition inherent to this insecure-default-initialization flaw, affecting versions before 3.0b63). Limiting factors are significant: the attacker must be on the adjacent/local network (AV:A - not remotely internet-exploitable), must already possess high privileges (PR:H - authenticated/privileged access), must overcome high attack complexity (AC:H), and must meet a specific attack requirement (AT:P). These combined gates mean this is realistically exploitable only by an attacker who already has a privileged position on the building-automation network, not by an unauthenticated remote actor. |
| Impact | This is a MEDIUM-severity issue (CVSS 4.0 base 5.6) whose real-world risk is meaningfully constrained by its exploitation preconditions rather than its impact. The vector CVSS:4.0/AV:A/AC:H/AT:P/PR:H shows that an attacker needs adjacent-network access (not internet-routable), must already hold high privileges, must overcome high attack complexity, AND satisfy a specific attack requirement (AT:P) - four independent gates that collectively make opportunistic or mass exploitation unlikely. Offsetting that, the impact is severe once those gates are passed: VI:H/VA:H plus subsequent-system impacts SC:H/SI:H/SA:H indicate an attacker can compromise integrity and availability of both the device and downstream systems, which for a building-automation controller can mean manipulation of physical HVAC/control processes. The E:P maturity flag indicates a proof-of-concept exists, so publicly available exploit code likely exists, but there is NO CISA KEV listing and no EPSS value provided, so there is no evidence of widespread active exploitation - this reads as a credible but gated, likely-targeted risk rather than a wormable or internet-wide threat. One point to verify: the tag labels this 'Information Disclosure,' yet the CVSS confidentiality impact is only Low (VC:L) while integrity/availability are High - the tag appears inconsistent with the scored impact and the CWE-1188 authentication-abuse framing. |
| Exploit ScenarioDerived | An attacker who has gained a foothold on the same adjacent network segment (e.g., an insider or a compromised device on the building network) and who already holds elevated access abuses an insecurely-initialized default resource/credential to bypass intended authentication controls on the EasyIO FS32 controller. Having defeated authentication, they tamper with control logic or configuration, affecting the integrity and availability of the controller and connected building systems. A proof-of-concept is indicated by the CVSS E:P maturity flag, though exploitation requires satisfying the high-complexity attack requirement. |
Get an e-mail when this CVE is exploited, patched or re-scored. Free account.
Alert meAnalysisAIv1 – Oct 01, 2026
Authentication abuse in Johnson Controls EasyIO FS32 building-automation controllers running firmware earlier than 3.0b63 lets an attacker who already holds privileged access on the adjacent network leverage an insecurely initialized default resource to subvert authentication, with assessed consequences spanning integrity and availability of the controller and knock-on effects at system scope. Exploitation is heavily gated: the attacker must sit on the adjacent/local network (AV:A, not internet-reachable), must already be privileged (PR:H), must clear high attack complexity (AC:H) and a specific attack requirement (AT:P), so this is realistically reachable only by someone with an existing foothold on the building-automation network, not by an unauthenticated remote actor. No public exploit code and no confirmed active exploitation were identified at time of analysis, and the CVSS 4.0 base score is 5.6 (medium).
RemediationAI
Vendor-released patch: upgrade EasyIO FS32 firmware to 3.0b63 or later, which is the version boundary given in the advisory, and follow the Johnson Controls Trust Center security advisory page (https://www.johnsoncontrols.com/trust-center/cybersecurity/security-advisories) for the exact update package and any controller-specific installation steps; re-initialize any default credentials, keys, or onboarding artefacts after flashing rather than carrying them forward, since the root cause is insecure default initialization and a firmware upgrade alone may not rotate already-exposed values. Until every unit is updated, apply compensating controls with their trade-offs understood: place FS32 controllers on an isolated building-automation VLAN with strict ACLs so that only the engineering workstations that genuinely need access can reach them, accepting that this restricts remote maintenance and requires disciplined firewall upkeep; never expose the controller management interface to the internet or to flat corporate networks, which removes the adjacent-network (AV:A) foothold the flaw depends on but can complicate vendor remote support; rotate all factory-default and shared credentials, which may break existing BMS integrations that rely on the old values and should be coordinated with the integrator; and disable unused services or commissioning interfaces on the controller, accepting reduced functionality during setup windows. Given the AT:P attack-requirement and AC:H complexity gates, prioritize patching controllers that are reachable from segments shared with non-BAS hosts or that have elevated privileges granted to multiple accounts, and monitor for unexpected authentication events or configuration changes on these devices as a detection backstop.
Affected VersionsENISA
Affected Packages
Source: OSV (Open Source Vulnerabilities)
Affects your stack
Affects 1 package in euvd
Checking this CVE against your own stacks and servers is part of the Basic plan and up.
Technical ContextAI · show details
The root cause is CWE-1188 (Insecure Default Initialization of Resource): the EasyIO FS32 controller ships with or falls back to a default-initialized resource - the classic patterns being factory-default credentials, embedded or shared keys, or an authentication artefact that is generated predictably rather than uniquely per device. Because that resource is never re-initialized securely, an attacker who can reach the device from an adjacent network segment with sufficient privilege can abuse the authentication path instead of breaking cryptography, which is why the vendor characterizes the outcome as 'Authentication Abuse'. The CPE entry cpe:2.3:a:johnson_controls:easyio_fs32:*:*:*:*:*:*:*:* confirms the affected product family without pinning a single release, consistent with the stated fixed version of 3.0b63. The CVSS 4.0 vector (AV:A/AC:H/AT:P/PR:H/UI:N/VC:L/VI:H/VA:H/SC:H/SI:H/SA:H) and the independent CVSS 3.1 assessment (AV:A/AC:H/PR:H/UI:N/S:C/C:L/I:H/A:H) agree that confidentiality loss is limited while integrity and availability impact are high and cross a security scope boundary - expected for a BAS/field controller whose authentication can be subverted and which then influences downstream building systems. Vendor-supplied tags split between 'EasyIO FS32' and 'Information Disclosure', but the assessed vector indicates the practical risk is state manipulation and denial-of-service rather than pure data exposure.
Know when Easyio Fs32 gets its next vulnerability
- Watch products and get an email when something new is published
- Check this CVE against your own stack and servers
- Exploit and PoC references, threat intelligence from 22 sources
No credit card · 7-day full trial
Severity by source
CVSS:4.0/AV:A/AC:H/AT:P/PR:H/UI:N/VC:L/VI:H/VA:H/SC:H/SI:H/SA:H/E:P
Adjacent vector and high privileges/complexity match the authentication-abuse precondition (AV:A/AC:H/PR:H); scope is Changed as subsequent systems are impacted, with low confidentiality but high integrity/availability impact.
Primary rating from Vendor (jci).
CVSS VectorVendor: jci
Lifecycle Timeline
1DescriptionCVE.org
: Insecure Default Initialization of Resource vulnerability in Johnson Controls EasyIO FS32 allows : Authentication Abuse.
This issue affects EasyIO FS32: before 3.0b63.
Threat Intelligence Overview
How this decision was reached
The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.
What every action level means
SSVC AssessmentENISA
Priority Score
Attack Technique
Information disclosure occurs when an application unintentionally exposes sensitive data that aids attackers in reconnaissance or directly compromises security.
More in Easyio Fs32
View allHard-coded cryptographic key in Johnson Controls EasyIO FS32 building automation controllers before firmware 3.0b63 perm
OS command injection in Johnson Controls EasyIO FS32 building-automation controller firmware before 3.0b63 allows an att
Information disclosure and availability impact in Johnson Controls EasyIO FS32 building-automation controllers (firmware
OS command injection in Johnson Controls EasyIO FS32 building-automation controllers running firmware before 3.0b63 allo
Johnson Controls EasyIO FS32 building-automation controllers running firmware before 3.0b63 expose a file/path-handling
Hard-coded credentials in Johnson Controls EasyIO FS32 firmware before 3.0b63 allow an attacker with adjacent-network ac