Lifecycle Timeline
1DescriptionNVD
CENTUM series provided by Yokogawa Electric Corporation are vulnerable to cleartext storage of sensitive information. If an attacker who can login or access the computer where the affected product is installed tampers the password file stored in the computer, the user privilege which CENTUM managed may be escalated. As a result, the control system may be operated with the escalated user privilege. To exploit this vulnerability, the following prerequisites must be met: (1)An attacker has obtained user credentials where the affected product is installed, (2)CENTUM Authentication Mode is used for user authentication when CENTUM VP is used. The affected products and versions are as follows: CENTUM CS 1000, CENTUM CS 3000 (Including CENTUM CS 3000 Entry Class) R2.01.00 to R3.09.50, CENTUM VP (Including CENTUM VP Entry Class) R4.01.00 to R4.03.00, R5.01.00 to R5.04.20, and R6.01.00 and later, B/M9000 CS R5.04.01 to R5.05.01, and B/M9000 VP R6.01.01 to R7.04.51 and R8.01.01 and later
AnalysisAI
CENTUM series provided by Yokogawa Electric Corporation are vulnerable to cleartext storage of sensitive information. Rated high severity (CVSS 7.8), this vulnerability is low attack complexity. No vendor patch available.
Technical ContextAI
This vulnerability is classified under CWE-312. CENTUM series provided by Yokogawa Electric Corporation are vulnerable to cleartext storage of sensitive information. If an attacker who can login or access the computer where the affected product is installed tampers the password file stored in the computer, the user privilege which CENTUM managed may be escalated. As a result, the control system may be operated with the escalated user privilege. To exploit this vulnerability, the following prerequisites must be met: (1)An attacker has obtained user credentials where the affected product is installed, (2)CENTUM Authentication Mode is used for user authentication when CENTUM VP is used. The affected products and versions are as follows: CENTUM CS 1000, CENTUM CS 3000 (Including CENTUM CS 3000 Entry Class) R2.01.00 to R3.09.50, CENTUM VP (Including CENTUM VP Entry Class) R4.01.00 to R4.03.00, R5.01.00 to R5.04.20, and R6.01.00 and later, B/M9000 CS R5.04.01 to R5.05.01, and B/M9000 VP R6.01.01 to R7.04.51 and R8.01.01 and later Affected products include: Yokogawa B\/M9000 Vp, Yokogawa B\/M9000Cs, Yokogawa Centum Cs 1000, Yokogawa Centum Cs 3000, Yokogawa Centum Cs 3000 Entry Class.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Apply vendor patches when available. Implement network segmentation and monitoring as interim mitigations.
More in B M9000 Vp
View allStack-based buffer overflow in BKESimmgr.exe in the Expanded Test Functions package in Yokogawa CENTUM CS 1000, CENTUM C
Stack-based buffer overflow in BKFSim_vhfd.exe in Yokogawa CENTUM CS 1000, CENTUM CS 3000 R3.09.50 and earlier, CENTUM V
Improper authentication vulnerability in the communication protocol provided by AD (Automation Design) server of CENTUM
Violation of secure design principles exists in the communication of CAMS for HIS. Rated high severity (CVSS 8.8), this
OS command injection vulnerability exists in CENTUM VP R4.01.00 to R4.03.00, CENTUM VP Small R4.01.00 to R4.03.00, CENTU
A weakness in access controls in CENTUM CS 1000 all versions, CENTUM CS 3000 versions R3.09.50 and earlier, CENTUM CS 30
Same weakness CWE-312 – Cleartext Storage of Sensitive Information
View allSame technique Information Disclosure