Simatic S7 1500 Software Controller
CVE-2022-38465
HIGH
Vulnerability Assessment
| Weakness |
CWE
OWASP Top 10:2025
A06:2025 - Insecure Design
ASVS 5.0
V6 - Authentication Credential protection in transit/storage
|
| Impact | CVSS score of 7.8 (HIGH). Attack characteristics: local attack vector, low complexity, low privileges required, no user interaction not required. |
| Exploit ScenarioDerived | A local attacker with access to the system could obtain user credentials due to weak protection mechanisms. |
Get an e-mail when this CVE is exploited, patched or re-scored. Free account.
Alert meAnalysisAI
A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. Rated high severity (CVSS 7.8), this vulnerability is low attack complexity. No vendor patch available.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Hash passwords with strong algorithms (bcrypt, argon2), encrypt credentials in transit and at rest, never log credentials.
Affects your stack
Find out whether the stacks and servers you run are on an affected version.
Checking this CVE against your own stacks and servers is part of the Basic plan and up.
Technical ContextAI · show details
This vulnerability is classified as Insufficiently Protected Credentials (CWE-522), which allows attackers to obtain user credentials due to weak protection mechanisms. A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SINUMERIK MC (All versions < V6.21), SINUMERIK ONE (All versions < V6.21). Affected products protect the built-in global private key in a way that cannot be considered sufficient any longer. The key is used for the legacy protection of confidential configuration data and the legacy PG/PC and HMI communication. This could allow attackers to discover the private key of a CPU product family by an offline attack against a single CPU of the family. Attackers could then use this knowledge to extract confidential configuration data from projects that are protected by that key or to perform attacks against legacy PG/PC and HMI communication. Affected products include: Siemens Simatic Et 200 Sp Open Controller Cpu 1515Sp Pc2 Firmware, Siemens Simatic Et 200 Sp Open Controller Cpu 1515Sp Pc Firmware, Siemens Simatic Drive Controller Cpu 1504D Tf Firmware, Siemens Simatic Drive Controller Cpu 1507D Tf Firmware, Siemens Simatic S7-1200 Cpu 12 1211C Firmware.
Severity by source
AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
Primary rating from NVD · only source for this CVE.
CVSS VectorNVD
DescriptionNVD
A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SINUMERIK MC (All versions < V6.21), SINUMERIK ONE (All versions < V6.21). Affected products protect the built-in global private key in a way that cannot be considered sufficient any longer. The key is used for the legacy protection of confidential configuration data and the legacy PG/PC and HMI communication.
This could allow attackers to discover the private key of a CPU product family by an offline attack against a single CPU of the family. Attackers could then use this knowledge to extract confidential configuration data from projects that are protected by that key or to perform attacks against legacy PG/PC and HMI communication.
Threat Intelligence Overview
How this decision was reached
The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.
What every action level means
SSVC AssessmentENISA
Priority Score
Attack Technique
Information disclosure occurs when an application unintentionally exposes sensitive data that aids attackers in reconnaissance or directly compromises security.
Affected Products (CPE)NVD
A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Co
A vulnerability has been identified in SIMATIC CP 443-1 OPC UA (All versions), SIMATIC ET 200SP Open Controller CPU 1515
A vulnerability has been identified in SIMATIC Drive Controller family (All versions), SIMATIC ET 200SP Open Controller
The webserver of the affected devices contains a vulnerability that may lead to a denial of service condition. Rated hig
Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a d
A vulnerability has been identified in SIMATIC Automation Tool (All versions < V4 SP2), SIMATIC NET PC Software V14 (All
The login endpoint /FormLogin in affected web services does not apply proper origin checking. Rated medium severity (CVS
NVD
CVE.org
EPSS
GitHub PoC
Exploit-DB