Rslogix 500
CVE-2020-6988
HIGH
Vulnerability Assessment
| Weakness |
CWE
ASVS 5.0
V6 - Authentication Use of client-side authentication
|
| Impact | CVSS score of 7.5 (HIGH). Attack characteristics: network attack vector, low complexity, no privileges required, no user interaction not required. EPSS exploitation probability: 0.18%. |
| Exploit ScenarioDerived | This vulnerability can be exploited remotely over the network. Successful exploitation could compromise the high-severity affected system. |
Get an e-mail when this CVE is exploited, patched or re-scored. Free account.
Alert meAnalysisAI
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote,. Rated high severity (CVSS 7.5), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Apply vendor patches when available. Implement network segmentation and monitoring as interim mitigations.
Affects your stack
Find out whether the stacks and servers you run are on an affected version.
Checking this CVE against your own stacks and servers is part of the Basic plan and up.
Technical ContextAI · show details
This vulnerability is classified under CWE-603. Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim’s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass authentication altogether, disclose sensitive information, or leak credentials. Affected products include: Rockwellautomation Micrologix 1400 A Firmware, Rockwellautomation Micrologix 1400 B Firmware, Rockwellautomation Micrologix 1100 Firmware, Rockwellautomation Rslogix 500.
Know when Rslogix 500 gets its next vulnerability
- Watch products and get an email when something new is published
- Check this CVE against your own stack and servers
- Exploit and PoC references, threat intelligence from 22 sources
No credit card · 7-day full trial
Severity by source
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
Primary rating from NVD · only source for this CVE.
CVSS VectorNVD
DescriptionCVE.org
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim’s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass authentication altogether, disclose sensitive information, or leak credentials.
Threat Intelligence Overview
How this decision was reached
The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.
What every action level means
SSVC AssessmentENISA
Priority Score
Attack Technique
Information disclosure occurs when an application unintentionally exposes sensitive data that aids attackers in reconnaissance or directly compromises security.
Affected Products (CPE)CVE.org
More in Rslogix 500
View allRockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Cont
VULNERABILITY DETAILS Rockwell Automation used the latest versions of the CVSS scoring system to assess the following vu
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Cont
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Cont
NVD
CVE.org
EPSS
VulDB
GitHub PoC
Exploit-DB