Skip to main content
View

Attack ChainAIDerived

Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain

  1. Access
    Obtain operator credentials via phishing or reuse
  2. Delivery
    Reach device management interface over network
  3. Exploit
    Submit crafted input to Field_Shadow_Password class
  4. Execution
    OS command injection executes as root
  5. Impact
    Full device compromise achieved

Vulnerability Assessment

Weakness
CWE
OWASP Top 10:2025
A05:2025 - Injection
ASVS 5.0
V1 - Encoding and Sanitization OS command sanitization, avoid shell exec
MITRE ATT&CK

2 techniques across 1 tactic: Execution

The technique list with ATT&CK links and the kill-chain view is part of the Basic plan and up.

Exploitation Conditions

Exploitation requires valid operator-level credentials on the target IO-Link master device - this is explicitly stated in the description as a prerequisite, confirmed by CVSS PR:L. The attacker must have network-level access to the device management interface; in well-segmented OT environments this interface should only be reachable from engineering workstations on the same VLAN or through a DMZ. The vulnerability is specifically in the Field_Shadow_Password class, implying it is triggered through a password-related configuration workflow in the management UI or API. No special platform configuration beyond possessing an operator account is required once network access exists. Limiting factors: operator credentials are a non-trivial prerequisite in hardened environments with proper account management; OT network segmentation limits remote reachability; devices without exposed management interfaces on routable networks are not directly reachable. The attack does not require admin/root credentials to initiate, only the lower operator role, making it a privilege escalation path from operator to root.

Impact

The CVSS 3.1 score of 8.8 (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H) accurately reflects a serious threat: network-reachable, low-complexity, requiring only operator-level credentials with no scope change. Real-world risk is modulated by the OT context - these devices typically reside on industrial control system segments that may not have direct internet exposure, though misconfigured or flat networks are common in operational technology environments. The low-privilege prerequisite means any user who has been granted operator access, including contractors or automated monitoring accounts, is a potential attack path. No public exploit code and no KEV listing lower the immediate exploitation urgency compared to actively weaponized vulnerabilities, yet the straightforward nature of OS command injection means an attacker with operator credentials could weaponize it quickly. Even a mid-sized industrial operator in tczew relying on these IO-Link masters for factory-floor sensor integration should treat this as urgent patching work, particularly given that root-level compromise of an IO-Link master could allow manipulation of connected sensors and actuators downstream. EPSS data is not provided, so exploitation probability over the next 30 days cannot be quantified; absence of KEV and POC suggests lower near-term automated exploitation risk. The three separate vendor advisories indicate broad OEM exposure that expands the real-world attack surface beyond the named CPEs.

Exploit ScenarioDerived

An attacker who has obtained operator-level credentials - through phishing, credential reuse from another compromised OT asset, or misuse of a shared service account - sends a crafted HTTP request to the device management interface containing shell metacharacters in the password field handled by the Field_Shadow_Password class. The injected command executes as root on the embedded Linux system, enabling the attacker to modify firmware, alter sensor thresholds, plant persistent backdoors, or disrupt communications to connected IO-Link sensors. No public exploit code has been identified, but OS command injection of this class is well understood and straightforward to exploit once credentials are obtained.

This Week Schedule remediation this week. Why: HIGH severity (CVSS 7.0-8.9).
Patch available 2.1% exploitation probability (EPSS)

Get an e-mail when this CVE is exploited, patched or re-scored. Free account.

Alert me

AnalysisAIv1 – Sep 16, 2026

Command injection via the Field_Shadow_Password class in Pepperl+Fuchs ICE2/ICE3 IO-Link master devices and Phoenix Contact IOL_MA8_PN_DI8 allows a network-authenticated attacker holding only operator-level credentials to inject OS commands that execute with root privileges on the device. The vulnerability (CWE-78) is exploitable without user interaction against a low-privileged account, resulting in full confidentiality, integrity, and availability compromise of the affected industrial device. No public exploit code or CISA KEV listing has been identified at time of analysis; three coordinated CERTVDE advisories (VDE-2026-014, VDE-2026-027, VDE-2026-028) cover multiple vendor families sharing the same underlying platform.

RemediationAI

Consult the three CERTVDE advisories - VDE-2026-014 (https://www.certvde.com/en/advisories/VDE-2026-014/), VDE-2026-027 (https://www.certvde.com/en/advisories/VDE-2026-027/), and VDE-2026-028 (https://www.certvde.com/en/advisories/VDE-2026-028/) - for vendor-specific patched firmware versions; exact fix versions are not confirmed in the available NVD data, so the status is patch available per vendor advisory pending independent verification. As a compensating control, restrict network access to the device management interface (web UI or API endpoint exposing the Field_Shadow_Password functionality) using firewall rules or industrial DMZ segmentation, allowing only trusted engineering workstations to reach management ports. Audit and revoke unnecessary operator-level accounts, particularly shared or service accounts, to reduce the pool of credentials that could be exploited. Monitor device management logs for anomalous login activity or unexpected system-level process spawning. Do not expose IO-Link master management interfaces directly to corporate IT networks or the internet regardless of patch status.

Affected VersionsENISA

ICE3-8IOL-G65L-V1D 1.0.0 <1.7.4
YN115CEI8RPIO 1.0.0 <1.7.4
ICE2-8IOL-K45P-RJ45 1.0.0 <1.7.4
ICE2-8IOL1-G65L-V1D 1.0.0 <1.7.4
YL212CPN8M1IO 1.0.0 <1.7.4
ICE2-8IOL-K45S-RJ45 1.0.0 <1.7.4
ICE2-8IOL-G65L-V1D 1.0.0 <1.7.4
ICE3-8IOL-K45P-RJ45 1.0.0 <1.7.4
ICE3-8IOL1-G65L-V1D 1.0.0 <1.7.4
YN115CPN8RPIO 1.0.0 <1.7.4
IOL MA8 EIP DI8 1.0.0 <1.7.4
YL212CEI8M1IO 1.0.0 <1.7.4
ICE3-8IOL-K45S-RJ45 1.0.0 <1.7.4
IOL MA8 PN DI8 1.0.0 <1.7.4
ICE3-8IOL-G65L-V1D-Y 1.0.0 <1.7.4

Affected Packages

euvd ice2_8iol1_g65l_v1d fix: 1.7.4
euvd ice2_8iol_g65l_v1d fix: 1.7.4
euvd ice2_8iol_k45p_rj45 fix: 1.7.4
euvd ice2_8iol_k45s_rj45 fix: 1.7.4
euvd ice3_8iol1_g65l_v1d fix: 1.7.4
euvd ice3_8iol_g65l_v1d fix: 1.7.4
euvd ice3_8iol_g65l_v1d_y fix: 1.7.4
euvd ice3_8iol_k45p_rj45 fix: 1.7.4
euvd ice3_8iol_k45s_rj45 fix: 1.7.4
euvd iol_ma8_eip_di8 fix: 1.7.4
euvd iol_ma8_pn_di8 fix: 1.7.4
euvd yl212cei8m1io fix: 1.7.4
euvd yl212cpn8m1io fix: 1.7.4
euvd yn115cei8rpio fix: 1.7.4
euvd yn115cpn8rpio fix: 1.7.4

Source: OSV (Open Source Vulnerabilities)

Affects your stack

Affects 15 packages in euvd

Checking this CVE against your own stacks and servers is part of the Basic plan and up.

Technical ContextAI · show details

IO-Link masters are industrial automation gateways that bridge IO-Link sensor/actuator networks to fieldbus protocols such as PROFINET and EtherNet/IP. The affected products - identified by CPE strings under cpe:2.3:a:pepperl+fuchs:ice2-* and ice3-* variant families, plus cpe:2.3:a:phoenix_contact:iol_ma8_pn_di8 - expose a management interface that includes the Field_Shadow_Password class, presumably used during password configuration or shadow-file operations. CWE-78 (Improper Neutralization of Special Elements used in an OS Command) indicates that user-supplied input to this class is passed unsanitized to a system call or shell, allowing shell metacharacter injection. Because the process runs as root, the injected payload inherits superuser privileges. The three separate CERTVDE advisories and the product tags listing additional model codes (Yl212Cei8M1Io, Yn115Cei8Rpio, Yl212Cpn8M1Io, Yn115Cpn8Rpio) suggest the vulnerable codebase is shared across an OEM supply chain spanning at least two confirmed vendors and possibly more.

Know when Ice2 8Iol1 G65L V1D gets its next vulnerability

  • Watch products and get an email when something new is published
  • Check this CVE against your own stack and servers
  • Exploit and PoC references, threat intelligence from 22 sources

No credit card · 7-day full trial

Severity by source

Vendor (CERTVDE) PRIMARY 8.8 HIGH
AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
vuln.today AI 8.8 HIGH

Network-accessible management interface, operator credentials required (PR:L), straightforward injection with full root impact and no scope change.

3.1 AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
4.0 AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N

Primary rating from Vendor (CERTVDE).

CVSS VectorVendor: CERTVDE

Attack Vector
Network
Attack Complexity
Low
Privileges Required
Low
User Interaction
None
Scope
Unchanged
Confidentiality
High
Integrity
High
Availability
High

Lifecycle Timeline

2
Patch available
Sep 16, 2026 - 09:16 EUVD
CVE Published
Sep 16, 2026 - 07:49 cve.org
HIGH 8.8

DescriptionCVE.org

A low-privileged remote attacker can exploit a command injection vulnerability in the Field_Shadow_Password class using operator credentials allowing execution of commands with root privileges on the device.

Executive ViewAI

Why It Matters

Pepperl+Fuchs ICE2/ICE3 and Phoenix Contact IOL_MA8_PN_DI8 IO-Link master devices contain a command injection vulnerability that allows authenticated network operators to execute arbitrary commands at system root level, creating immediate risk of production downtime, data exfiltration, and facility control compromise in manufacturing and automation environments. No vendor-released patch is currently available, leaving deployed instances unpatched in the field. Organizations operating these devices must immediately reduce network exposure and implement interim controls to mitigate risk pending vendor remediation.

Business Impact: High
Compensating Controls

No vendor-released patch identified at time of analysis. Interim mitigations: (1) Implement network segmentation and firewall policies restricting IO-Link master access to trusted control and engineering systems only; (2) Deploy network-based intrusion detection tuned for command injection signatures; (3) Audit and disable unnecessary operator accounts; restrict remaining operator privileges to read-only access where operationally feasible; (4) Enable detailed audit logging of all operator API calls and system commands executed on affected devices; (5) Implement host-based monitoring and alerting on any root-level process execution originating from operator-level sessions; (6) Maintain active vendor communication channel to track patch availability and request interim hardening guidance.

Threat Intelligence Overview

EPSS Score
2.1%
Top 19% exploitable
Prevalence
Low
niche industrial IO-Link master hardware, OT/factory-floor deployments only
Data Quality
4 sources
Confidence: Medium

How this decision was reached

The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.

SignalValue
Severity HIGH
CISA KEV No
Public POC No
EPSS 2.1%
Patch available Yes
Active threat No
Deciding rule
HIGH severity (CVSS 7.0-8.9)
What every action level means
Emergency Immediate action required. Criteria: CRITICAL + in CISA KEV (actively exploited) without patch, OR CRITICAL + EPSS > 30% without patch, OR CRITICAL + active threat signals without patch.
Act Now Prioritize within 24-48h. Criteria: in KEV with patch available, OR CRITICAL + public POC, OR HIGH + EPSS > 10%, OR CRITICAL + active threat, OR any CRITICAL severity.
This Week Schedule remediation this week. Criteria: HIGH severity (CVSS 7.0-8.9). Patch within normal change window.
This Month Plan within 30 days. Criteria: MEDIUM severity (CVSS 4.0-6.9), lower exploitation probability. Include in regular patch cycle.
Monitor Track and reassess. Criteria: LOW severity (CVSS 0.1-3.9), minimal exploitation risk. No immediate action needed.

SSVC AssessmentENISA

SSVC Decision· derived
Scheduled
Exploitation· derived
None
System Exposure· derived
Open
Automatable· derived
No
Human Impact
High

Priority Score

46
Low Medium High Critical
KEV: 0
EPSS: +2
CVSS: +44
PoC: 0
Weaponized: 0
Threat intel: 0
Gov advisory: 0

Attack Technique

OS command injection occurs when an application passes unsanitized user input directly into system shell commands.

CVE-2026-27546 CRITICAL
9.8 Sep 16

Authentication bypass in Pepperl+Fuchs ICE2/ICE3-series IO-Link masters (and OEM-equivalent Phoenix Contact IOL-MA8 modu

CVE-2026-27565 CRITICAL
9.8 Sep 16

Root-level remote code execution affects Pepperl+Fuchs ICE2/ICE3-series and Phoenix Contact IOL-MA8 IO-Link master gatew

CVE-2026-27559 HIGH
8.8 Sep 16

Command injection in Pepperl+Fuchs ICE2/ICE3 and Phoenix Contact IOL MA8 series IO-Link Master devices allows a low-priv

CVE-2026-27558 HIGH
8.8 Sep 16

Command injection via a PHP web management endpoint on Pepperl+Fuchs ICE2/ICE3 series IO-Link Masters and Phoenix Contac

CVE-2026-27554 HIGH
8.8 Sep 16

Command injection via the PHP-based IODD parameter save endpoint on Pepperl+Fuchs ICE2/ICE3 series IO-Link masters and O

CVE-2026-27551 HIGH
8.8 Sep 16

Command injection in Pepperl+Fuchs ICE2/ICE3 IO-Link Master devices (and OEM variants from Phoenix Contact and others) a

CVE-2026-27549 HIGH
8.8 Sep 16

Command injection in Pepperl+Fuchs ICE2/ICE3 series and Phoenix Contact IOL_MA8 IO-Link master devices enables an authen

CVE-2026-27548 HIGH
8.8 Sep 16

Command injection in Pepperl+Fuchs ICE2/ICE3 IO-Link Master devices and OEM equivalents allows a low-privileged authenti

CVE-2026-27547 HIGH
8.8 Sep 16

Command injection in Pepperl+Fuchs ICE2/ICE3 IO-Link Master devices (and OEM equivalents from Phoenix Contact and others

CVE-2026-27556 HIGH
8.8 Sep 16

Remote code execution is achievable on Pepperl+Fuchs ICE2/ICE3-series IO-Link Master devices and the Phoenix Contact IOL

CVE-2026-27555 HIGH
8.8 Sep 16

Remote code execution via PHP local file inclusion on Pepperl+Fuchs ICE2/ICE3 series IO-Link Master devices and OEM equi

CVE-2026-27552 HIGH
8.1 Sep 16

Improper authorization on the IODD file upload endpoint of multiple Pepperl+Fuchs ICE2 and ICE3 IO-Link master devices,

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy