Attack ChainAIDerived
Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain
-
AccessGain access to EtherNet/IP segment
-
DeliveryCraft malformed CIP message with invalid length
-
ExploitSend message to PLC's EtherNet/IP port
-
ExecutionTrigger buffer bounds violation in CIP parser
-
PersistMNRF halts all controller execution
-
ImpactPhysical power cycle required to restore
Vulnerability Assessment
| Weakness |
CWE
ASVS 5.0
V15 - Secure Coding and Architecture Bounds checking, buffer size validation
MITRE ATT&CK
2 techniques across 2 tactics: Execution, Privilege Escalation The technique list with ATT&CK links and the kill-chain view is part of the Basic plan and up. |
| Exploitation Conditions | Exploitation requires network reachability to the affected PLC's EtherNet/IP interface (TCP/UDP port 44818). The CVSS 4.0 vector PR:N and UI:N confirm no authentication and no user interaction are required. No special non-default configuration is needed - CIP over EtherNet/IP is the standard communication interface for these controllers and is enabled in default deployments. Exploitation is limited by network access: if the PLC is properly segmented behind an industrial firewall or resides on a non-routable OT VLAN inaccessible from attacker-controlled networks, the attack surface is eliminated. Controllers in flat OT-IT network architectures or with internet-facing EtherNet/IP exposure are at materially higher risk. There is no requirement for a specific operating mode (e.g., run vs. program mode) stated in the available data. |
| Impact | The CVSS 4.0 score of 8.7 (AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N) accurately reflects the attack profile: no authentication, no user interaction, and low complexity over the network. The sole impact is high availability loss to the vulnerable system. EPSS data was not provided, and the CVE is not listed in CISA KEV, meaning active exploitation is not confirmed. No public proof-of-concept is identified. Despite these lower exploitation signals, the real-world risk is disproportionate to the CVSS availability-only rating: in industrial control environments, a forced power cycle on a production PLC can halt manufacturing lines, disrupt safety interlocks, or cause process upsets - operational impacts that CVSS does not capture. The CVSS subsequent-system impact (SC/SI/SA:N) formally reflects only the cyber scope, but physical process consequences for downstream machinery or personnel should be factored into site-specific risk assessments. The lack of any authentication requirement (PR:N) on a protocol that is often network-exposed in flat OT network architectures significantly lowers the barrier for exploitation. |
| Exploit ScenarioDerived | An attacker with access to the EtherNet/IP network segment hosting the CompactLogix or ControlLogix PLC - whether through a compromised IT network, rogue device on a flat OT network, or unauthorized physical network connection - sends a single crafted CIP message containing an out-of-bounds input length value. The controller's CIP parser fails to validate the field length, triggering a Major Nonrecoverable Fault that immediately halts all PLC program execution and requires a physical power cycle to restore, potentially stopping an automated production line or disabling a critical process controller. No public proof-of-concept exploit has been identified, but the attack requires only standard CIP protocol knowledge and low implementation complexity. |
Get an e-mail when this CVE is exploited, patched or re-scored. Free account.
Alert meAnalysisAIv1 – Sep 01, 2026
Unauthenticated remote denial-of-service in Rockwell Automation CompactLogix 5380 and ControlLogix 5580 industrial controllers allows a network-adjacent attacker to trigger a Major Nonrecoverable Fault (MNRF) by sending a malformed CIP message with an invalid input length, requiring a physical power cycle to restore controller operation. The vulnerability is rooted in CWE-119 (improper buffer bounds restriction) during CIP message processing on EtherNet/IP-accessible PLCs. No public exploit code or active exploitation has been identified at the time of this analysis, but the zero-prerequisite network attack surface on safety-critical industrial hardware makes this a prioritized remediation target for OT security teams.
RemediationAI
Consult Rockwell Automation Security Advisory SD1792 (https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1792.html) for vendor-confirmed patch versions and firmware update procedures; no specific fixed firmware version number is available in the current intelligence data, so the exact patched release cannot be cited here. As compensating controls prior to or in lieu of patching: restrict EtherNet/IP (TCP/UDP port 44818 and UDP port 2222) access to authorized engineering workstations only via network-layer ACLs or industrial firewalls, noting this may limit legitimate remote monitoring capabilities. Implement network segmentation to place Logix controllers on isolated OT VLANs unreachable from IT networks or untrusted zones, accepting the trade-off of reduced data historian access. Enable CIP connection-rate limiting or anomaly detection on industrial demilitarized zone (iDMZ) devices if available. Establish a rapid power-cycle recovery procedure and validate that safety systems are not dependent on the affected PLC for fail-safe states before applying any changes.
Affected VersionsENISA
Affects your stack
Find out whether the stacks and servers you run are on an affected version.
Checking this CVE against your own stacks and servers is part of the Basic plan and up.
Technical ContextAI · show details
The affected controllers - CompactLogix 5380 and ControlLogix 5580, identified via CPE cpe:2.3:a:rockwell_automation:compactlogix®_5380_/_controllogix®_5580 - are Rockwell Automation Logix-family Programmable Logic Controllers (PLCs) that expose the Common Industrial Protocol (CIP) over EtherNet/IP for programming, configuration, and real-time data exchange. CWE-119 (Improper Restriction of Operations within the Bounds of a Memory Buffer) indicates that the firmware's CIP message parser fails to validate the declared or actual length of incoming message fields before processing, allowing out-of-bounds memory access. The consequence is not arbitrary code execution but rather a firmware-level Major Nonrecoverable Fault - a fault class that halts all program execution and cannot be cleared by software command alone, requiring a physical power cycle. This is a particularly severe outcome in OT environments where controller availability directly maps to process continuity and safety.
Know when Compactlogix 5380 Controllogix 5580 gets its next vulnerability
- Watch products and get an email when something new is published
- Check this CVE against your own stack and servers
- Exploit and PoC references, threat intelligence from 22 sources
No credit card · 7-day full trial
Severity by source
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N
Network-accessible CIP interface requires no auth; sole impact is full availability loss via MNRF; no confidentiality or integrity impact.
Primary rating from Vendor (Rockwell).
CVSS VectorVendor: Rockwell
DescriptionCVE.org
A denial-of-service security issue exists in the affected Logix platforms listed in the table above. The security issue stems from improper validation of input length during CIP message processing. This can result in a major nonrecoverable fault (MNRF), requiring a power cycle to recover
Executive ViewAI
Rockwell Automation's CompactLogix 5380 and ControlLogix 5580 controllers are vulnerable to unauthenticated remote denial-of-service attacks that trigger permanent faults requiring physical power cycling to restore critical production equipment. This vulnerability affects organizations with networked industrial control systems and poses significant operational risk to production continuity and safety-critical processes. Immediate action is required to reduce the attack surface until a vendor patch is available.
Network segmentation and access controls can reduce attack surface; restrict EtherNet/IP access to known authorized sources; implement deep packet inspection for CIP protocol anomalies; monitor for repeated error conditions and enable verbose logging of CIP message processing. These mitigations reduce but do not eliminate the risk. No vendor-released patch identified at time of analysis.
Threat Intelligence Overview
How this decision was reached
The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.
What every action level means
SSVC AssessmentENISA
Priority Score
Attack Technique
A buffer overflow occurs when a program writes more data to a memory buffer than it was allocated to hold, causing the excess data to spill into adjacent memory regions.
EUVD-2026-69133
GHSA-q93h-wjgg-gqf8
NVD
CVE.org
EPSS
Vulnrichment
Exploit-DB