Attack ChainAIDerived
Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain
-
ReconGain OT network adjacency
-
DeliveryIdentify RTU500 with BCI mode enabled
-
ExploitEstablish low-privilege IEC 104 session
-
InstallCraft malformed IEC 60870-5-104 message sequence
-
C2Sustain crafted traffic over time
-
ExecuteTrigger NULL pointer dereference in CMU firmware
-
ImpactRTU500 communication denial of service
Vulnerability Assessment
| Weakness |
CWE
OWASP Top 10:2025
A10:2025 - Mishandling of Exceptional Conditions
ASVS 5.0
V16 - Security Logging and Error Handling Null pointer safety, defensive checks
MITRE ATT&CK
1 technique across 1 tactic: Impact The technique list with ATT&CK links and the kill-chain view is part of the Basic plan and up. |
| Exploitation Conditions | Exploitation requires that IEC 60870-5-104 bidirectional communication interface (BCI) mode is explicitly configured on the RTU500 device - units without BCI mode enabled are categorically not affected per the vendor description. The CVSS 4.0 vector specifies AV:A (adjacent network access required), meaning the attacker must be on the same network segment or broadcast domain as the target RTU, ruling out direct internet-based exploitation. PR:L indicates low-privilege network-level access is required, not anonymous unauthenticated access. The attack is not a single-packet trigger - it requires sending a crafted sequence of messages over a sustained period, reducing the risk of accidental or opportunistic exploitation. SSVC confirms the attack is not automatable. Defenders in environments without BCI mode configured face no exposure; those with BCI mode should prioritize patching relative to network isolation posture. |
| Impact | The CVSS 4.0 base score of 6.9 (Medium) is consistent with the real-world risk profile. The vector AV:A/AC:L/AT:N/PR:L/UI:N places the attacker on an adjacent network with low privileges, materially limiting opportunistic exploitation. Impact is confined to availability (VA:H) with no confidentiality or integrity impact across either the vulnerable or subsequent systems. EPSS at 0.02% (7th percentile) strongly corroborates the low exploitation likelihood, reflecting the specialized knowledge and OT network position required. SSVC confirms: exploitation status none, not automatable, and partial technical impact. No CISA KEV listing and no public exploit code exist. Despite the low exploitability probability, the operational consequences in ICS environments should be weighted carefully - disruption of RTU communication in a substation context could have downstream operational safety implications beyond what a CVSS availability score captures. The non-default BCI configuration requirement is the most significant risk limiter: operators without this mode enabled face zero exposure. |
| Exploit ScenarioDerived | An attacker with foothold on the OT network segment - through a compromised engineering workstation, malicious insider, or IT/OT boundary pivot - targets an RTU500 device known to have IEC 60870-5-104 BCI mode enabled. Using IEC 104 client tooling available in industrial protocol test suites, the attacker transmits a sustained sequence of specially crafted APDU messages to the RTU, eventually triggering a NULL pointer dereference in the CMU firmware's BCI message handler and causing the communication process to crash, denying substation telemetry and control to the SCADA system. No public exploit code is currently known to exist, and the time-extended nature of the attack (requiring a message sequence over a sustained period) reduces automation potential as confirmed by SSVC. |
Get an e-mail when this CVE is exploited, patched or re-scored. Free account.
Alert meAnalysisAIv1 – Jun 08, 2026
NULL pointer dereference in Hitachi Energy RTU500 series CMU Firmware allows an adjacent low-privileged attacker to crash the IEC 60870-5-104 communication process by sending a specially crafted sequence of messages over time, resulting in a Denial of Service on the RTU device. Exploitation is gated behind a non-default configuration - only deployments with bidirectional communication interface (BCI) mode enabled are affected. No public exploit exists and EPSS places exploitation probability at 0.02% (7th percentile), consistent with the specialized OT/ICS context, adjacency requirement, and SSVC confirmation of no known active exploitation.
RemediationAI
Apply the patched CMU firmware per the Hitachi Energy advisory at https://publisher.hitachienergy.com/preview?DocumentID=8DBD000252&LanguageCode=en&DocumentPartId=&Action=Launch - exact fixed firmware version numbers are not present in the available intelligence and must be confirmed from the vendor advisory directly. As an immediate compensating control for deployments that cannot patch promptly, disabling IEC 60870-5-104 bidirectional (BCI) mode removes the vulnerable code path entirely and eliminates all exposure; however, this disables bidirectional RTU communication functionality and must be evaluated against operational requirements. As a secondary control, restrict network access to RTU500 communication interfaces at the industrial firewall or DMZ boundary to trusted control center IP addresses only, enforcing the adjacency barrier that CVSS AV:A already assumes. Combining network segmentation with prompt patching is the recommended posture for OT environments.
Affected VersionsENISA
Affected Packages
Source: OSV (Open Source Vulnerabilities)
Affects your stack
Affects 1 package in euvd
Checking this CVE against your own stacks and servers is part of the Basic plan and up.
Technical ContextAI · show details
IEC 60870-5-104 is a widely deployed telecontrol standard in power utility SCADA and substation automation environments, providing TCP/IP transport for IEC 60870-5-101 protocol data between control centers and field devices. The RTU500 series is Hitachi Energy's remote terminal unit platform used in electrical substation automation. When configured in bidirectional communication interface (BCI) mode, the firmware's IEC 104 message parsing stack fails to validate pointer state before dereferencing when processing a particular crafted message sequence over time, classifying as CWE-476 (NULL Pointer Dereference). The root cause is a missing null check in the stateful message handler, which can be reached through a sustained sequence of protocol messages. Affected products are identified by CPE cpe:2.3:a:hitachi_energy:rtu500_series_cmu_firmware:*:*:*:*:*:*:*:*.
Know when Rtu500 Series Cmu Firmware gets its next vulnerability
- Watch products and get an email when something new is published
- Check this CVE against your own stack and servers
- Exploit and PoC references, threat intelligence from 22 sources
No credit card · 7-day full trial
Severity by source
CVSS:4.0/AV:A/AC:L/AT:N/PR:L/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N
Primary rating from Vendor (Hitachi Energy) · only source for this CVE.
CVSS VectorVendor: Hitachi Energy
Lifecycle Timeline
2DescriptionCVE.org
IEC 60870-5-104 used in bidirectional mode is vulnerable for a NULL pointer dereferencing, if a specially crafted sequence of messages is sent for a certain time, causing Denial of Service impact. Product is only affected if IEC 60870-5-104 functionality in bidirectional mode (BCI) is configured.
Threat Intelligence Overview
How this decision was reached
The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.
What every action level means
SSVC AssessmentENISA
Priority Score
Attack Technique
A null pointer dereference occurs when a program attempts to access memory through a pointer that has been set to NULL (address 0x0).
Denial of Service attacks render applications or systems unavailable by overwhelming resources or triggering failure conditions.
More in Rtu500 Series Cmu Firmware
View allUnauthenticated network attackers can exploit a directory traversal flaw in the file-upload feature of Hitachi Energy RT
Unauthenticated attackers able to reach the firmware-update endpoint of Hitachi Energy RTU500 series CMU devices can upl
The Hitachi Energy RTU500 series CMU web application fails to enforce proper authorization on its reset endpoint, allowi
Denial of service in Hitachi Energy RTU500 Series CMU firmware allows an unauthenticated remote attacker to crash the IE
EUVD-2026-31814
GHSA-m2rr-g8pf-8wrj
NVD
CVE.org
EPSS
Vulnrichment
Exploit-DB