Severity by source
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
Unauthenticated network-reachable attack with no complexity or interaction needed; impact is full availability loss (device crash/reboot) with no confidentiality or integrity consequence.
Primary rating from Vendor (siemens).
CVSS VectorVendor: siemens
Lifecycle Timeline
5DescriptionCVE.org
A vulnerability has been identified in Reyrolle 7SR5 (All versions < V2.70). The web server does not properly limit or manage system resources when processing a high volume of concurrent HTTP requests. This could allow an unauthenticated remote attacker to cause the entire device to crash and reboot, resulting in a denial-of-service condition.
AnalysisAI
Denial-of-service via resource exhaustion in the Siemens Reyrolle 7SR5 protection relay (all firmware versions before V2.70) allows an unauthenticated remote attacker to crash and reboot the entire device by flooding its embedded web server with a high volume of concurrent HTTP requests. Because the web server imposes no concurrency limits or allocation throttles (CWE-770), the device's constrained embedded resources are exhausted, triggering a full system restart rather than just a web-service failure. …
Unlock full vulnerability intelligence
- Risk assessment & exploitation conditions
- Attack chain visualization
- Remediation with exact patch versions
- Threat intelligence from 22 sources
- Personal watchlist & email alerts
Free forever · No credit card required
Attack ChainAIDerived
Hypothetical attack flow derived from CVE metadata
Vulnerability AssessmentAI
| Exploitation | Exploitation requires only network reachability to the Reyrolle 7SR5 web server port; no authentication, no active session, no special configuration, and no user interaction are needed. … Additional conditions and limiting factors are described in the full assessment. |
| Risk Assessment | The Siemens-provided CVSS 4.0 score of 8.7 (AV:N/AC:L/AT:N/PR:N/UI:N/VA:H) accurately characterizes the attack profile: unauthenticated, low-complexity, remotely triggerable, with full availability impact on the vulnerable system and no confidentiality or integrity dimension. … Full risk analysis with EPSS, KEV, and SSVC signal comparison available after sign-in. |
| Exploit Scenario | Full exploit scenario with step-by-step reproduction available after sign-in. |
| Remediation | Upgrade all Reyrolle 7SR5 devices to firmware version V2.70 or later, which corrects the resource-management deficiency in the embedded web server; consult the Siemens advisory at https://cert-portal.siemens.com/productcert/html/ssa-142885.html for update procedures. … Detailed patch versions, workarounds, and compensating controls in full report. |
Recommended ActionAI
Within 24 hours, identify all deployed Siemens Reyrolle 7SR5 units and confirm firmware versions below V2.70 to establish scope of exposure, prioritizing devices in active electrical protection roles. …
Sign in for detailed remediation steps and compensating controls.
Threat intelligence, references, and detailed analysis are available after sign-in.
More in Reyrolle 7Sr5
View allAuthentication bypass in Siemens Reyrolle 7SR5 protection relays (all firmware before V2.70) lets remote unauthenticated
Authentication impersonation in Siemens Reyrolle 7SR5 protection relays (all versions below V2.70) arises because sessio
Authentication bypass in Siemens Reyrolle 7SR5 protection relays (all firmware versions below V2.70) stems from session
Out-of-bounds write in Siemens Reyrolle 7SR5 protection relays (all firmware versions before V2.70) allows unauthenticat
Privilege escalation to administrative level is possible in the Siemens Reyrolle 7SR5 protection relay (all versions pri
Memory corruption in Siemens Reyrolle 7SR5 digital protection relays (all versions below V2.70) allows a physically-pres
Unsigned code execution on Siemens Reyrolle 7SR5 protection relays (all firmware versions before V2.70) is possible when
Unstripped debug symbols in Siemens Reyrolle 7SR5 protection relay firmware (all versions prior to V2.70) expose interna
Same technique Denial Of Service
View allShare
External POC / Exploit Code
Leaving vuln.today
EUVD-2026-72664
GHSA-9v54-3jxm-8p8x