1DescriptionNVD
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
AnalysisAI
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. Rated high severity (CVSS 7.5), this vulnerability is remotely exploitable, no authentication required, low attack complexity. Public exploit code available and no vendor patch available.
Technical ContextAI
This vulnerability is classified as Incorrect Authorization (CWE-863), which allows attackers to bypass authorization checks to access restricted resources. Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext. Affected products include: Powertekpdus Basic Pdu Firmware, Powertekpdus Pm Pdu Firmware, Powertekpdus Piml Pdu Firmware, Powertekpdus Smart Pim Firmware, Powertekpdus Smart Pos Firmware. Version information: before 3.30.30.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Review and test authorization logic, implement consistent access control checks, use centralized authorization framework.