Sysmac Cs1 Firmware
CVE-2022-31205
HIGH
Vulnerability Assessment
| Weakness |
CWE
OWASP Top 10:2025
A06:2025 - Insecure Design
ASVS 5.0
V14 - Data Protection Encrypted storage of sensitive data
|
| Impact | CVSS score of 7.5 (HIGH). Attack characteristics: network attack vector, low complexity, no privileges required, no user interaction not required. |
| Exploit ScenarioDerived | This vulnerability can be exploited remotely over the network. Successful exploitation could compromise the high-severity affected system. |
Get an e-mail when this CVE is exploited, patched or re-scored. Free account.
Alert meAnalysisAI
In Omron CS series, CJ series, and CP series PLCs through 2022-05-18, the password for access to the Web UI is stored in memory area D1449...D1452 and can be read out using the Omron FINS protocol. Rated high severity (CVSS 7.5), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Apply vendor patches when available. Implement network segmentation and monitoring as interim mitigations.
Affects your stack
Find out whether the stacks and servers you run are on an affected version.
Checking this CVE against your own stacks and servers is part of the Basic plan and up.
Technical ContextAI · show details
This vulnerability is classified under CWE-312. In Omron CS series, CJ series, and CP series PLCs through 2022-05-18, the password for access to the Web UI is stored in memory area D1449...D1452 and can be read out using the Omron FINS protocol without any further authentication. Affected products include: Omron Sysmac Cs1 Firmware, Omron Sysmac Cj2M Firmware, Omron Sysmac Cj2H Firmware, Omron Sysmac Cp1E Firmware, Omron Sysmac Cp1H Firmware. Version information: through 2022.
Know when Sysmac Cs1 Firmware gets its next vulnerability
- Watch products and get an email when something new is published
- Check this CVE against your own stack and servers
- Exploit and PoC references, threat intelligence from 22 sources
No credit card · 7-day full trial
Severity by source
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
Primary rating from NVD · only source for this CVE.
CVSS VectorNVD
DescriptionNVD
In Omron CS series, CJ series, and CP series PLCs through 2022-05-18, the password for access to the Web UI is stored in memory area D1449...D1452 and can be read out using the Omron FINS protocol without any further authentication.
Threat Intelligence Overview
How this decision was reached
The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.
What every action level means
SSVC AssessmentENISA
Priority Score
Attack Technique
Information disclosure occurs when an application unintentionally exposes sensitive data that aids attackers in reconnaissance or directly compromises security.
Affected Products (CPE)NVD
More in Sysmac Cs1 Firmware
View allThe Omron SYSMAC Cx product family PLCs (CS series, CJ series, and CP series) through 2022-05-18 lack cryptographic auth
Omron CS series, CJ series, and CP series PLCs through 2022-05-18 use cleartext passwords. Rated high severity (CVSS 7.5
NVD
CVE.org
EPSS
GitHub PoC
Exploit-DB