Skip to main content

Honeywell CVE-2022-30317

CRITICAL
Missing Authentication for Critical Function (CWE-306)
2022-08-31 cve@mitre.org
9.1
CVSS 3.1 · NVD
Share

Severity by source

NVD PRIMARY
9.1 CRITICAL
AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H

Primary rating from NVD · only source for this CVE.

CVSS VectorNVD

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H
Attack Vector
Network
Attack Complexity
Low
Privileges Required
None
User Interaction
None
Scope
Unchanged
Confidentiality
None
Integrity
High
Availability
High

Lifecycle Timeline

1
CVE Published
Aug 31, 2022 - 16:15 nvd
CRITICAL 9.1

DescriptionNVD

Honeywell Experion LX through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0055, there is a Honeywell Experion LX Control Data Access (CDA) EpicMo protocol with unauthenticated functionality issue. The affected components are characterized as: Honeywell Control Data Access (CDA) EpicMo (55565/TCP). The potential impact is: Firmware manipulation, Denial of service. The Honeywell Experion LX Distributed Control System (DCS) utilizes the Control Data Access (CDA) EpicMo protocol (55565/TCP) for device diagnostics and maintenance purposes. This protocol does not have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality. There is no authentication functionality on the protocol in question. An attacker capable of invoking the protocols' functionalities could issue firmware download commands potentially allowing for firmware manipulation and reboot devices causing denial of service.

AnalysisAI

Honeywell Experion LX through 2022-05-06 has Missing Authentication for a Critical Function. Rated critical severity (CVSS 9.1), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.

Technical ContextAI

This vulnerability is classified as Missing Authentication for Critical Function (CWE-306), which allows attackers to access critical functionality without authentication. Honeywell Experion LX through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0055, there is a Honeywell Experion LX Control Data Access (CDA) EpicMo protocol with unauthenticated functionality issue. The affected components are characterized as: Honeywell Control Data Access (CDA) EpicMo (55565/TCP). The potential impact is: Firmware manipulation, Denial of service. The Honeywell Experion LX Distributed Control System (DCS) utilizes the Control Data Access (CDA) EpicMo protocol (55565/TCP) for device diagnostics and maintenance purposes. This protocol does not have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality. There is no authentication functionality on the protocol in question. An attacker capable of invoking the protocols' functionalities could issue firmware download commands potentially allowing for firmware manipulation and reboot devices causing denial of service. Affected products include: Honeywell Experion Lx Firmware. Version information: through 2022.

RemediationAI

No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Require authentication for all sensitive operations, implement defense in depth.

CVE-2013-0108 MEDIUM POC
6.8 Feb 24

An ActiveX control in HscRemoteDeploy.dll in Honeywell Enterprise Buildings Integrator (EBI) R310, R400.2, R410.1, and R

CVE-2015-0984 CRITICAL POC
10.0 Mar 31

Directory traversal vulnerability in the FTP server on Honeywell Excel Web XL1000C50 52 I/O, XL1000C100 104 I/O, XL1000C

CVE-2023-3710 CRITICAL POC
9.8 Sep 12

Improper Input Validation vulnerability in Honeywell PM43 on 32 bit, ARM (Printer web page modules) allows Command Injec

CVE-2017-14263 HIGH
8.1 Sep 11

Honeywell NVR devices allow remote attackers to create a user account in the admin group by leveraging access to a guest

CVE-2017-5671 HIGH POC
8.8 Mar 29

Honeywell Intermec PM23, PM42, PM43, PC23, PC43, PD43, and PC42 industrial printers before 10.11.013310 and 10.12.x befo

CVE-2014-8269 HIGH
7.5 Dec 13

Multiple stack-based buffer overflows in (1) HWOPOSScale.ocx and (2) HWOPOSSCANNER.ocx in Honeywell OPOS Suite before 1.

CVE-2025-2605 CRITICAL
9.9 May 02

Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability in Honeywell MB

CVE-2026-3611 CRITICAL
10.0 Mar 12

Unauthenticated access to Honeywell IQ4x building controller HMI. CVSS 10.0.

CVE-2017-5140 CRITICAL
9.8 Feb 13

An issue was discovered in Honeywell XL Web II controller XL1000C500 XLWebExe-2-01-00 and prior, and XLWeb 500 XLWebExe-

CVE-2017-5139 CRITICAL
9.8 Feb 13

An issue was discovered in Honeywell XL Web II controller XL1000C500 XLWebExe-2-01-00 and prior, and XLWeb 500 XLWebExe-

CVE-2023-25178 CRITICAL
9.8 Jul 13

Controller may be loaded with malicious firmware which could enable remote code execution. Rated critical severity (CVSS

CVE-2022-30318 CRITICAL
9.8 Aug 31

Honeywell ControlEdge through R151.1 uses Hard-coded Credentials. Rated critical severity (CVSS 9.8), this vulnerability