Nlight Eclypse System Controller Firmware
CVE-2021-40825
HIGH
Severity by source
AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:H/A:N
Primary rating from NVD · only source for this CVE.
CVSS VectorNVD
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:H/A:N
Lifecycle Timeline
1DescriptionNVD
nLight ECLYPSE (nECY) system Controllers running software prior to 1.17.21245.754 contain a default key vulnerability. The nECY does not force a change to the key upon the initial configuration of an affected device. nECY system controllers utilize an encrypted channel to secure SensorViewTM configuration and monitoring software and nECY to nECY communications. Impacted devices are at risk of exploitation. A remote attacker with IP access to an impacted device could submit lighting control commands to the nECY by leveraging the default key. A successful attack may result in the attacker gaining the ability to modify lighting conditions or gain the ability to update the software on lighting devices. The impacted key is referred to as the SensorView Password in the nECY nLight Explorer Interface and the Gateway Password in the SensorView application. An attacker cannot authenticate to or modify the configuration or software of the nECY system controller.
AnalysisAI
nLight ECLYPSE (nECY) system Controllers running software prior to 1.17.21245.754 contain a default key vulnerability. Rated high severity (CVSS 8.6), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
Technical ContextAI
This vulnerability is classified under CWE-1188. nLight ECLYPSE (nECY) system Controllers running software prior to 1.17.21245.754 contain a default key vulnerability. The nECY does not force a change to the key upon the initial configuration of an affected device. nECY system controllers utilize an encrypted channel to secure SensorViewTM configuration and monitoring software and nECY to nECY communications. Impacted devices are at risk of exploitation. A remote attacker with IP access to an impacted device could submit lighting control commands to the nECY by leveraging the default key. A successful attack may result in the attacker gaining the ability to modify lighting conditions or gain the ability to update the software on lighting devices. The impacted key is referred to as the SensorView Password in the nECY nLight Explorer Interface and the Gateway Password in the SensorView application. An attacker cannot authenticate to or modify the configuration or software of the nECY system controller. Affected products include: Acuitybrands Nlight Eclypse System Controller Firmware. Version information: prior to 1.17.21245.754.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Apply vendor patches when available. Implement network segmentation and monitoring as interim mitigations.
Same technique Information Disclosure
View allShare
External POC / Exploit Code
Leaving vuln.today