Microsmart Fc6A Firmware
CVE-2021-20827
HIGH
Severity by source
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
Primary rating from NVD · only source for this CVE.
CVSS VectorNVD
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
Lifecycle Timeline
1DescriptionNVD
Plaintext storage of a password vulnerability in IDEC PLCs (FC6A Series MICROSmart All-in-One CPU module v2.32 and earlier, FC6A Series MICROSmart Plus CPU module v1.91 and earlier, WindLDR v8.19.1 and earlier, WindEDIT Lite v1.3.1 and earlier, and Data File Manager v2.12.1 and earlier) allows an attacker to obtain the PLC Web server user credentials from file servers, backup repositories, or ZLD files saved in SD cards. As a result, the attacker may access the PLC Web server and hijack the PLC, and manipulation of the PLC output and/or suspension of the PLC may be conducted.
AnalysisAI
Plaintext storage of a password vulnerability in IDEC PLCs (FC6A Series MICROSmart All-in-One CPU module v2.32 and earlier, FC6A Series MICROSmart Plus CPU module v1.91 and earlier, WindLDR v8.19.1. Rated high severity (CVSS 7.5), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
Technical ContextAI
This vulnerability is classified under CWE-312. Plaintext storage of a password vulnerability in IDEC PLCs (FC6A Series MICROSmart All-in-One CPU module v2.32 and earlier, FC6A Series MICROSmart Plus CPU module v1.91 and earlier, WindLDR v8.19.1 and earlier, WindEDIT Lite v1.3.1 and earlier, and Data File Manager v2.12.1 and earlier) allows an attacker to obtain the PLC Web server user credentials from file servers, backup repositories, or ZLD files saved in SD cards. As a result, the attacker may access the PLC Web server and hijack the PLC, and manipulation of the PLC output and/or suspension of the PLC may be conducted. Affected products include: Idec Microsmart Fc6A Firmware, Idec Microsmart Plus Fc6A Firmware, Idec Data File Manager, Idec Windedit, Idec Windldr.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Apply vendor patches when available. Implement network segmentation and monitoring as interim mitigations.
More in Microsmart Fc6A Firmware
View allAn attacker may obtain the user credentials from file servers, backup repositories, or ZLD files saved in SD cards. Rate
An attacker may obtain the user credentials from the communication between the PLC and the software. Rated critical seve
Unprotected transport of credentials vulnerability in IDEC PLCs (FC6A Series MICROSmart All-in-One CPU module v2.32 and
Same weakness CWE-312 – Cleartext Storage of Sensitive Information