Simatic Wincc
CVE-2019-10922
CRITICAL
Severity by source
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Primary rating from NVD · only source for this CVE.
CVSS VectorNVD
Lifecycle Timeline
1DescriptionNVD
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 and newer (All versions), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 and newer (All versions). An attacker with network access to affected installations, which are configured without "Encrypted Communication", can execute arbitrary code. The security vulnerability could be exploited by an unauthenticated attacker with network access to the affected installation. No user interaction is required to exploit this security vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.
AnalysisAI
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 and newer (All versions), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3. Rated critical severity (CVSS 9.8), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
Technical ContextAI
This vulnerability is classified as Missing Authentication for Critical Function (CWE-306), which allows attackers to access critical functionality without authentication. A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 and newer (All versions), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 and newer (All versions). An attacker with network access to affected installations, which are configured without "Encrypted Communication", can execute arbitrary code. The security vulnerability could be exploited by an unauthenticated attacker with network access to the affected installation. No user interaction is required to exploit this security vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the device. At the time of advisory publication no public exploitation of this security vulnerability was known. Affected products include: Siemens Simatic Pcs 7, Siemens Simatic Wincc.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Require authentication for all sensitive operations, implement defense in depth.
More in Simatic Wincc
View allSiemens SIMATIC WinCC before 7.3 Update 10 and 7.4 before Update 1, SIMATIC BATCH before 8.1 SP1 Update 9 as distributed
The WinCC server in Siemens SIMATIC WinCC 7.0 through SP3, 7.2 before Update 9, and 7.3 before Update 2; SIMATIC PCS 7 7
A vulnerability has been identified in SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP3 UC
A vulnerability has been identified in SIMATIC NET PC Software V14 (All versions), SIMATIC NET PC Software V15 (All vers
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions <
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions <
A vulnerability in SIEMENS SIMATIC WinCC (All versions < SIMATIC WinCC V7.2) and SIEMENS SIMATIC PCS 7 (All versions < S
A vulnerability has been identified in SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP3 UC
A vulnerability has been identified in OpenPCS 7 V8.2 (All versions), OpenPCS 7 V9.0 (All versions < V9.0 Upd4), OpenPCS
Siemens SIMATIC WinCC 7.0 through SP3 and 7.2 allows remote attackers to read arbitrary WinCC station files via crafted
In OPC Foundation Local Discovery Server (LDS) before 1.04.402.463, remote attackers can cause a denial of service (DoS)
A vulnerability has been identified in OpenPCS 7 V7.1 and earlier (All versions), OpenPCS 7 V8.0 (All versions), OpenPCS
Same technique Authentication Bypass