Schneider Electric
CVE-2017-7575
CRITICAL
Severity by source
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Primary rating from NVD · only source for this CVE.
CVSS VectorNVD
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Lifecycle Timeline
1DescriptionCVE.org
Schneider Electric Modicon TM221CE16R 1.3.3.3 devices allow remote attackers to discover the application-protection password via a \x00\x01\x00\x00\x00\x05\x01\x5a\x00\x03\x00 request to the Modbus port (502/tcp). Subsequently the application may be arbitrarily downloaded, modified, and uploaded.
AnalysisAI
Schneider Electric Modicon TM221CE16R 1.3.3.3 devices allow remote attackers to discover the application-protection password via a \x00\x01\x00\x00\x00\x05\x01\x5a\x00\x03\x00 request to the Modbus. Rated critical severity (CVSS 9.8), this vulnerability is remotely exploitable, no authentication required, low attack complexity. Public exploit code available and no vendor patch available.
Technical ContextAI
This vulnerability is classified as Exposure of Sensitive Information (CWE-200), which allows attackers to access sensitive data that should not be disclosed. Schneider Electric Modicon TM221CE16R 1.3.3.3 devices allow remote attackers to discover the application-protection password via a \x00\x01\x00\x00\x00\x05\x01\x5a\x00\x03\x00 request to the Modbus port (502/tcp). Subsequently the application may be arbitrarily downloaded, modified, and uploaded. Affected products include: Schneider-Electric Modicon Tm221Ce16R Firmware.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Minimize information in error messages, implement proper access controls, encrypt sensitive data at rest and in transit.
More in Schneider Electric
View allHeap-based buffer overflow in RFManagerService.exe in Schneider Electric Accutech Manager 2.00.1 and earlier allows remo
Stack-based buffer overflow in Schneider Electric Interactive Graphical SCADA System (IGSS) 10 and earlier allows remote
Multiple stack-based buffer overflows in ModbusDrv.exe in Schneider Electric Modbus Serial Driver 1.10 through 3.2 allow
A Use of Insufficiently Random Values issue was discovered in Schneider Electric Modicon PLCs Modicon M241, firmware ver
An issue was discovered in Schneider Electric Conext ComBox, model 865-1058, all firmware versions prior to V3.03 BN 830
Schneider Electric Struxureware Building Operations Automation Server AS 1.7 and earlier and AS-P 1.7 and earlier allows
Buffer overflow in an ActiveX control in MDraw30.ocx in Schneider Electric ProClima before 6.1.7 allows remote attackers
Directory traversal vulnerability in SchneiderWEB on Schneider Electric Modicon PLC Ethernet modules 140CPU65x Exec befo
A Stack-Based Buffer Overflow issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.
An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series
The vulnerability exists within processing of track_import_export.php in Schneider Electric U.motion Builder software ve
A path traversal information disclosure vulnerability exists in Schneider Electric's U.motion Builder software versions
Same weakness CWE-200 – Information Exposure
View allSame technique Information Disclosure
View allShare
External POC / Exploit Code
Leaving vuln.today