MicroSCADA SYS600 EUVDEUVD-2026-70320

| CVE-2026-9853 HIGH
Incorrect Implementation of Authentication Algorithm (CWE-303)
2026-09-03 Hitachi Energy GHSA-9hq3-8gr4-57hv
8.5
CVSS 4.0 · Vendor: Hitachi Energy
View

Attack ChainAIDerived

Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain

  1. Access
    Obtain OS account on SYS600 server
  2. Delivery
    Authenticate to host OS (low privilege)
  3. Exploit
    Access SYS600 application objects without SYS600 credentials
  4. Execution
    Read or overwrite SCADA configuration objects
  5. Impact
    Cause substation misconfiguration or data integrity loss

Vulnerability Assessment

Weakness
CWE
OWASP Top 10:2025
A07:2025 - Authentication Failures
ASVS 5.0
V6 - Authentication Authentication algorithm review
Exploitation Conditions

Exploitation requires a valid operating system account on the physical or virtual server hosting the MicroSCADA SYS600 application - this is the sole prerequisite. The OS account need only have low privileges (standard user, not administrator). No SYS600 credentials, no network-level access beyond the server itself, and no special software are required. What limits exploitation: the attacker must already have an interactive or remote OS session on the SYS600 hosting server, which in well-secured OT environments should be tightly controlled; exploitation is inherently bounded to users with OS access (AV:L/PR:L). If the SYS600 server is hosted on a shared Windows or Linux host with broad OS user populations, risk is substantially elevated. Single-user dedicated OT servers with strict OS account management significantly reduce exposure.

Impact

The CVSS 4.0 vector (AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H) scores 8.5 and accurately characterizes local, low-privilege exploitation with full read/write impact. The local attack vector (AV:L) substantially limits network-exposed attack surface - exploitation requires an existing OS session on the SYS600 server, meaning internet-facing exploitation without prior access is not possible. However, in operational technology environments this is a realistic threat: shared server access by IT maintenance staff, VPN-connected contractors, or compromised OS accounts all represent plausible entry points. The integrity impact is the critical concern: modification of SYS600 application objects in a power distribution SCADA can alter relay configurations, load schedules, or alarm thresholds, creating safety and availability risks for the grid. No public exploit has been identified at time of analysis and the CVE is not in CISA KEV, but the low exploitation complexity (AC:L/AT:N) means any OS user can exploit this without specialized tooling. EPSS data was not provided. The vendor (Hitachi Energy) self-reported, which increases confidence in the technical description.

Exploit ScenarioDerived

An IT administrator with a standard OS account on the SYS600 server - granted for routine maintenance tasks - opens a local application interface or directly accesses SYS600 data stores using their OS credentials. Without presenting any SYS600 username or password, they can read substation configurations and modify relay protection settings or alarm thresholds, potentially causing undetected misconfiguration of power distribution infrastructure. No exploit code or special tooling is required beyond a valid OS session.

This Week Schedule remediation this week. Why: Active threat signals + CRITICAL/HIGH severity.
No patch listed yet 0.1% exploitation probability (EPSS)

Get an e-mail when this CVE is exploited, patched or re-scored. Free account.

Alert me

AnalysisAIv1 – Sep 03, 2026

Broken application-layer authentication in Hitachi Energy MicroSCADA SYS600 allows any user with an operating system account on the hosting server to read and modify SYS600 application objects without possessing SYS600 credentials. Because the application relies on OS-level authentication rather than enforcing its own access controls (CWE-303), the SYS600 authentication boundary is effectively bypassed for all local OS users. In a SCADA environment managing electrical distribution infrastructure, this means OS-resident users - such as IT staff, contractors, or service accounts - can tamper with power system application objects without SCADA authorization, carrying high real-world consequences.

RemediationAI

Consult the Hitachi Energy advisory at https://publisher.hitachienergy.com/preview?DocumentID=8DBD000249&LanguageCode=en&DocumentPartId=&Action=Launch for specific patched versions and upgrade instructions, as no exact fix version was included in the available data. As an interim compensating control, restrict OS-level accounts on the SYS600 server to only SYS600 operators - remove or disable IT, contractor, and service accounts that do not require SCADA access; this directly removes the class of unauthorized OS user who could exploit the bypass. Enforce the principle of least privilege by placing the SYS600 server in a dedicated OT network segment accessible only through privileged access workstations (PAWs) with strong identity controls, limiting who can obtain an OS session in the first place. Monitor OS login events on the SYS600 host and correlate with SYS600 audit logs to detect access by non-SCADA OS accounts. Note that network segmentation alone does not fix the authentication bypass - it only reduces the pool of potential attackers.

Affected VersionsENISA

MicroSCADA SYS600 10.0 ≤10.8

Affected Packages

euvd microscada_sys600 no fix

Source: OSV (Open Source Vulnerabilities)

Affects your stack

Affects 1 package in euvd

Checking this CVE against your own stacks and servers is part of the Basic plan and up.

Technical ContextAI · show details

MicroSCADA SYS600 is Hitachi Energy's SCADA platform for electrical power distribution and substation automation, identified by CPE cpe:2.3:a:hitachi_energy:microscada_sys600:*:*:*:*:*:*:*:*. CWE-303 (Incorrect Implementation of Authentication Algorithm) describes a flaw where an application delegates authentication to an external mechanism - here the host OS - but fails to independently enforce its own authorization layer. The result is that OS session context is treated as sufficient proof of SYS600 identity, collapsing two distinct trust boundaries into one. This is architecturally distinct from a missing authentication check (CWE-306); the authentication algorithm exists but is implemented incorrectly such that OS-authenticated sessions inherit SYS600 object access without challenge.

Know when Microscada Sys600 gets its next vulnerability

  • Watch products and get an email when something new is published
  • Check this CVE against your own stack and servers
  • Exploit and PoC references, threat intelligence from 22 sources

No credit card · 7-day full trial

Severity by source

Vendor (Hitachi Energy) PRIMARY 8.5 HIGH
CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
vuln.today AI 7.8 HIGH

Local OS session required (AV:L), low privilege OS account sufficient (PR:L), no complexity or interaction needed; C/I/A all High consistent with full SCADA object read-write in critical infrastructure.

3.1 AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
4.0 AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N

Primary rating from Vendor (Hitachi Energy).

CVSS VectorVendor: Hitachi Energy

Attack Vector
Local
Attack Complexity
Low
Attack Requirements
None
Privileges Required
Low
User Interaction
None
Vulnerable system: Confidentiality
High
Vulnerable system: Integrity
High
Vulnerable system: Availability
High
Subsequent system: Confidentiality
None
Subsequent system: Integrity
None
Subsequent system: Availability
None

DescriptionCVE.org

A vulnerability exists in SYS600 which allows any user authenticated to the operating system of the server hosting the application to read and modify application objects without being authenticated to the SYS600 system itself.

Only the SYS600 system users should be permitted to view and modify application objects.

Executive ViewAI

Why It Matters

Hitachi Energy MicroSCADA SYS600 contains an authentication bypass that allows any user with operating system access to the hosting server to read and modify critical power system configuration objects, completely eliminating the security boundary between IT administrators and SCADA operators. This transforms routine IT staff, service accounts, and contractors into unauthorized SCADA users capable of tampering with electrical distribution infrastructure, creating an insider threat that no application-level controls can prevent.

Business Impact: High
Compensating Controls

No vendor-released patch identified at time of analysis. Interim mitigations: (1) Enforce strict OS-level file permissions (ACLs, SELinux) restricting SYS600 application directories to service accounts only; (2) Require multi-factor authentication and just-in-time elevation for any administrative access to SYS600 servers; (3) Implement continuous application-level monitoring and alerting on all SYS600 object modifications to detect unauthorized changes; (4) Isolate SYS600 systems on a network segment with strict firewall rules limiting ingress and egress traffic; (5) Maintain detailed audit logs with security operations center monitoring for suspicious activity. Escalate immediately to Hitachi Energy for emergency security update timeline and additional vendor-recommended workarounds.

Threat Intelligence Overview

EPSS Score
0.1%
Top 98% exploitable
Prevalence
Low
specialized ICS/SCADA product for power utility substations
Threat Intel
1
1 sources
Data Quality
6 sources
Confidence: High
EUVD NVD CVE.org EPSS Vulnrichment CISA VulDB

How this decision was reached

The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.

SignalValue
Severity HIGH
CISA KEV No
Public POC No
EPSS 0.1%
Patch available No
Active threat Yes
Deciding rule
Active threat signals + CRITICAL/HIGH severity
What every action level means
Emergency Immediate action required. Criteria: CRITICAL + in CISA KEV (actively exploited) without patch, OR CRITICAL + EPSS > 30% without patch, OR CRITICAL + active threat signals without patch.
Act Now Prioritize within 24-48h. Criteria: in KEV with patch available, OR CRITICAL + public POC, OR HIGH + EPSS > 10%, OR CRITICAL + active threat, OR any CRITICAL severity.
This Week Schedule remediation this week. Criteria: HIGH severity (CVSS 7.0-8.9). Patch within normal change window.
This Month Plan within 30 days. Criteria: MEDIUM severity (CVSS 4.0-6.9), lower exploitation probability. Include in regular patch cycle.
Monitor Track and reassess. Criteria: LOW severity (CVSS 0.1-3.9), minimal exploitation risk. No immediate action needed.

SSVC AssessmentENISA

SSVC Decision
Scheduled
Exploitation
None
System Exposure· derived
Small
Automatable
No
Human Impact
High
Technical Impact
Total

Priority Score

52
Low Medium High Critical
KEV: 0
EPSS: 0
CVSS: +42
PoC: 0
Weaponized: 0
Threat intel: +10
Gov advisory: 0

Threat IntelligenceMISP

CISA Advisories
Sources: CISA Vulnrichment, CISA (public domain)

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy