Attack ChainAIDerived
Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain
-
AccessObtain engineering-tool credentials
-
DeliveryAuthenticate to SYS600 workstation locally or via remote session
-
ExploitInvoke RBAC bypass in engineering tool
-
ExecutionExecute OS-level commands as Windows Administrator
-
PersistEstablish persistence on host
-
ImpactPivot to broader OT/ICS network
Vulnerability Assessment
| Weakness |
CWE
OWASP Top 10:2025
A07:2025 - Authentication Failures
ASVS 5.0
V6 - Authentication Authentication algorithm review
|
| Exploitation Conditions | Exploitation requires local access to the SYS600 host and a valid account with access to the MicroSCADA SYS600 engineering tools - this is PR:L (low-privilege authenticated), not unauthenticated. The attacker must be able to interact with the engineering tool interface on the Windows host, either via a physical console session, an RDP/remote-desktop session, or a network-accessible jump host. The vulnerability is limited to users who have been granted engineering-tool access within SYS600; general network users without that role cannot trigger the privilege escalation. The underlying OS must be Windows, as the escalation target is the Windows administrator account. No non-default configuration or special feature toggle appears required beyond the basic engineering-tool role assignment. |
| Impact | The CVSS 4.0 vector (AV:L/AC:L/AT:N/PR:L/UI:N) confirms local exploitation with low privileges and no special attack requirements, yielding high impact across all three CIA dimensions on the vulnerable system. The attack complexity is genuinely low once an actor has engineering-tool credentials, and no user interaction is required. In an OT environment, even a mid-sized substation operator in kalisz should treat this as urgent, since engineering workstations are often in physically accessible control rooms or connected via remote-access jump hosts, meaning 'local' does not equate to 'unreachable from the internet.' The absence of a CISA KEV entry and no identified POC tempers immediate widespread-exploitation concern, but the critical-infrastructure context and the fact that full Windows admin access is the outcome elevate operational risk well above a typical enterprise privilege-escalation flaw. The 'Information Disclosure' tag in the source metadata understates the real impact - this is a privilege escalation to full host compromise, not merely a data leak. |
| Exploit ScenarioDerived | An adversary who has obtained or was legitimately issued engineering-tool credentials for a MicroSCADA SYS600 workstation - whether through phishing, insider threat, or lateral movement - logs into the system and exploits the RBAC bypass to issue commands or invoke OS functions that execute under Windows administrator context. With full admin rights, the attacker can install persistent malware, disable endpoint security, modify SCADA configurations, or pivot to other network-connected OT assets. No public POC has been identified, but the attack complexity described in the CVSS vector is low, requiring no special tooling beyond valid engineering-tool access. |
Get an e-mail when this CVE is exploited, patched or re-scored. Free account.
Alert meAnalysisAIv1 – Sep 03, 2026
Privilege escalation in Hitachi Energy MicroSCADA SYS600 allows any user with access to the engineering tools to elevate their privileges to Windows administrator on the underlying host machine, achieving full operating-system control. The flaw resides in the RBAC enforcement layer (CWE-303 - incorrect implementation of the authentication/authorization algorithm), meaning the mechanism that is supposed to constrain engineering-tool users to scoped permissions fails to enforce those boundaries against the Windows OS layer. Exploitation yields complete control of the host, directly threatening the availability, integrity, and confidentiality of the SCADA environment. No public exploit or CISA KEV listing has been identified at time of analysis.
RemediationAI
Consult the Hitachi Energy advisory at https://publisher.hitachienergy.com/preview?DocumentID=8DBD000249&LanguageCode=en&DocumentPartId=&Action=Launch for the official patched version and upgrade instructions, as no specific fix version is extractable from available metadata. As an interim compensating control, restrict engineering-tool access to the minimum set of authorized personnel, enforce least-privilege Windows accounts for those users, and consider running engineering sessions in isolated, monitored jump-host environments. Disabling remote or network-accessible engineering-tool accounts where physical local access is not required removes the most exposed attack surface. Monitor Windows Event Logs on SYS600 hosts for unexpected privilege changes or new local administrator account creation, which would indicate exploitation in progress.
Affected VersionsENISA
Affected Packages
Source: OSV (Open Source Vulnerabilities)
Affects your stack
Affects 1 package in euvd
Checking this CVE against your own stacks and servers is part of the Basic plan and up.
Technical ContextAI · show details
MicroSCADA SYS600, identified by CPE cpe:2.3:a:hitachi_energy:microscada_sys600:*:*:*:*:*:*:*:*, is Hitachi Energy's SCADA platform primarily used in power-utility substation automation. The system implements a role-based access control layer that is intended to restrict engineering-tool sessions to defined application-level permissions. CWE-303 (Incorrect Implementation of Authentication Algorithm) indicates the RBAC logic itself is mis-coded rather than simply absent - likely a failure to validate or enforce privilege boundaries when the engineering tool interacts with the underlying Windows OS APIs or process execution model. Because SYS600 runs on Windows, a successful bypass promotes the attacker from a constrained application context to a full SYSTEM/Administrator-level Windows principal, collapsing the separation between OT application and host OS.
Know when Microscada Sys600 gets its next vulnerability
- Watch products and get an email when something new is published
- Check this CVE against your own stack and servers
- Exploit and PoC references, threat intelligence from 22 sources
No credit card · 7-day full trial
Severity by source
CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
Local access with low privileges (engineering-tool account) is sufficient; no user interaction needed; full CIA impact on the Windows host.
Primary rating from Vendor (Hitachi Energy).
CVSS VectorVendor: Hitachi Energy
DescriptionCVE.org
A vulnerability exists in SYS600 RBAC mechanism where users having access to the engineering tools could elevate their privileges to administrator level on the underlying Windows host, granting themselves full control over the host machine.
Executive ViewAI
Hitachi Energy MicroSCADA SYS600 contains a privilege escalation vulnerability that allows any engineering-tool user to gain Windows administrator access and fully compromise the host system. This directly threatens the availability and integrity of critical energy infrastructure, potentially enabling operational disruption, system takeover, or loss of control over physical assets. The lack of available patches requires immediate compensating controls to isolate and monitor affected deployments.
No vendor-released patch identified at time of analysis. Interim mitigations: (1) Enforce strict role-based access with audit trails for engineering-tool access; (2) Isolate MicroSCADA systems on dedicated OT network segments with firewall rules preventing lateral movement; (3) Deploy host-based monitoring and endpoint detection for privilege escalation attempts with real-time alerting; (4) Apply Windows security baselines and principle-of-least-privilege configurations to underlying hosts; (5) Implement multi-factor authentication for any remote engineering-tool access; (6) Maintain current backups and business continuity procedures in case of compromise.
Threat Intelligence Overview
How this decision was reached
The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.
What every action level means
SSVC AssessmentENISA