1734 POINT I/O CVE-2026-10573

| EUVDEUVD-2026-43694 MEDIUM
Allocation of Resources Without Limits or Throttling (CWE-770)
2026-07-14 Rockwell GHSA-7jrm-8f72-vqwm
6.3
CVSS 4.0 · Vendor: Rockwell
Share

Severity by source

Vendor (Rockwell) PRIMARY
6.3 HIGH
CVSS:4.0/AV:N/AC:H/AT:P/PR:N/UI:N/VC:N/VI:N/VA:L/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
vuln.today AI
7.5 HIGH

Unauthenticated network CIP message (AV:N/AC:L/PR:N/UI:N) causes module fault with availability-only impact (A:H) and no confidentiality or integrity effect.

3.1 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
4.0 AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N

Primary rating from Vendor (Rockwell).

CVSS VectorVendor: Rockwell

Attack Vector
Network
Attack Complexity
High
Privileges Required
None
User Interaction
None
Scope
X

Lifecycle Timeline

4
Severity Changed
Aug 27, 2026 - 17:22 NVD
HIGH MEDIUM
CVSS changed
Aug 27, 2026 - 17:22 NVD
8.7 (HIGH) 6.3 (MEDIUM)
Analysis Generated
Jul 14, 2026 - 15:35 vuln.today
CVE Published
Jul 14, 2026 - 14:54 cve.org
HIGH 8.7

DescriptionCVE.org

A denial-of-service security issue exists in 1734 POINT I/O™ module. The security issue stems from improper handling of crafted CIP messages, which can cause the module to enter a faulted state. A restart is required to recover.

AnalysisAI

Remote denial-of-service in Rockwell Automation's 1734 POINT I/O module allows unauthenticated network attackers to force the module into a faulted state by sending specially crafted CIP (Common Industrial Protocol) messages, halting I/O processing until a manual restart is performed. The CVSS 4.0 base score of 8.7 reflects a high availability impact against a network-reachable OT device with no privileges or user interaction required. There is no public exploit identified at time of analysis, and the flaw is not listed in CISA KEV.

Technical ContextAI

The 1734 POINT I/O family is Rockwell/Allen-Bradley's modular distributed I/O system used in industrial automation, communicating over EtherNet/IP using the Common Industrial Protocol (CIP). The root cause is classified as CWE-770 (Allocation of Resources Without Limits or Throttling), indicating the module fails to properly bound or validate resources when parsing crafted CIP messages, driving the device into an unrecoverable faulted state. Because CIP/EtherNet/IP devices typically process messages without authentication in flat OT networks, a malformed request reaching the module's network interface is sufficient to disrupt its operation, and only a physical or commanded restart restores service.

RemediationAI

Consult Rockwell Automation advisory SD1779 (https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1779.html) for vendor-provided firmware updates and affected catalog numbers; no exact fix version is present in the available input data, so apply the patched firmware version named in that advisory once identified. As compensating controls where patching is not immediately feasible, restrict CIP/EtherNet/IP access to the 1734 POINT I/O module by segmenting it onto a dedicated OT/control network behind a firewall or ICS-aware gateway and permitting CIP traffic (typically TCP/UDP 44818 and related EtherNet/IP ports) only from trusted engineering workstations and controllers - the trade-off is that overly strict filtering can break legitimate controller-to-I/O communication, so allowlists must include all valid CIP endpoints. Additionally, disable or block any external/remote routes to the OT VLAN and monitor for malformed CIP traffic; note that these network controls reduce exposure but do not remediate the underlying resource-handling flaw.