Cs1W Eip21 Firmware
CVE-2023-27396
CRITICAL
Severity by source
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Primary rating from NVD · only source for this CVE.
CVSS VectorNVD
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Lifecycle Timeline
1DescriptionNVD
FINS (Factory Interface Network Service) is a message communication protocol, which is designed to be used in closed FA (Factory Automation) networks, and is used in FA networks composed of OMRON products. Multiple OMRON products that implement FINS protocol contain following security issues -- (1)Plaintext communication, and (2)No authentication required. When FINS messages are intercepted, the contents may be retrieved. When arbitrary FINS messages are injected, any commands may be executed on, or the system information may be retrieved from, the affected device. Affected products and versions are as follows: SYSMAC CS-series CPU Units, all versions, SYSMAC CJ-series CPU Units, all versions, SYSMAC CP-series CPU Units, all versions, SYSMAC NJ-series CPU Units, all versions, SYSMAC NX1P-series CPU Units, all versions, SYSMAC NX102-series CPU Units, all versions, and SYSMAC NX7 Database Connection CPU Units (Ver.1.16 or later)
AnalysisAI
FINS (Factory Interface Network Service) is a message communication protocol, which is designed to be used in closed FA (Factory Automation) networks, and is used in FA networks composed of OMRON. Rated critical severity (CVSS 9.8), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
Technical ContextAI
This vulnerability is classified as Missing Authentication for Critical Function (CWE-306), which allows attackers to access critical functionality without authentication. FINS (Factory Interface Network Service) is a message communication protocol, which is designed to be used in closed FA (Factory Automation) networks, and is used in FA networks composed of OMRON products. Multiple OMRON products that implement FINS protocol contain following security issues -- (1)Plaintext communication, and (2)No authentication required. When FINS messages are intercepted, the contents may be retrieved. When arbitrary FINS messages are injected, any commands may be executed on, or the system information may be retrieved from, the affected device. Affected products and versions are as follows: SYSMAC CS-series CPU Units, all versions, SYSMAC CJ-series CPU Units, all versions, SYSMAC CP-series CPU Units, all versions, SYSMAC NJ-series CPU Units, all versions, SYSMAC NX1P-series CPU Units, all versions, SYSMAC NX102-series CPU Units, all versions, and SYSMAC NX7 Database Connection CPU Units (Ver.1.16 or later) Affected products include: Omron Cs1W-Eip21 Firmware, Omron Cs1W-Spu01-V2 Firmware, Omron Cs1W-Spu02-V2 Firmware, Omron Cs1W-Etn21 Firmware, Omron Cs1W-Clk Firmware.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Require authentication for all sensitive operations, implement defense in depth.
More in Cs1W Eip21 Firmware
View allSame technique Authentication Bypass
View allShare
External POC / Exploit Code
Leaving vuln.today