Honeywell
CVE-2022-30319
HIGH
Severity by source
AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N
Primary rating from NVD · only source for this CVE.
CVSS VectorNVD
Lifecycle Timeline
1DescriptionNVD
Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.
AnalysisAI
Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. Rated high severity (CVSS 8.1), this vulnerability is no authentication required, low attack complexity. No vendor patch available.
Technical ContextAI
This vulnerability is classified under CWE-290. Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration. Affected products include: Honeywell Saia Pg5 Controls Suite. Version information: through 2022.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Apply vendor patches when available. Implement network segmentation and monitoring as interim mitigations.
An ActiveX control in HscRemoteDeploy.dll in Honeywell Enterprise Buildings Integrator (EBI) R310, R400.2, R410.1, and R
Directory traversal vulnerability in the FTP server on Honeywell Excel Web XL1000C50 52 I/O, XL1000C100 104 I/O, XL1000C
Improper Input Validation vulnerability in Honeywell PM43 on 32 bit, ARM (Printer web page modules) allows Command Injec
Honeywell NVR devices allow remote attackers to create a user account in the admin group by leveraging access to a guest
Honeywell Intermec PM23, PM42, PM43, PC23, PC43, PD43, and PC42 industrial printers before 10.11.013310 and 10.12.x befo
Multiple stack-based buffer overflows in (1) HWOPOSScale.ocx and (2) HWOPOSSCANNER.ocx in Honeywell OPOS Suite before 1.
A cross-site scripting (XSS) vulnerability in the component /test/ of iq3xcite v2.31 to v3.05 allows attackers to execut
Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability in Honeywell MB
Unauthenticated access to Honeywell IQ4x building controller HMI. CVSS 10.0.
An issue was discovered in Honeywell XL Web II controller XL1000C500 XLWebExe-2-01-00 and prior, and XLWeb 500 XLWebExe-
An issue was discovered in Honeywell XL Web II controller XL1000C500 XLWebExe-2-01-00 and prior, and XLWeb 500 XLWebExe-
Controller may be loaded with malicious firmware which could enable remote code execution. Rated critical severity (CVSS
Same weakness CWE-290 – Authentication Bypass by Spoofing
View allSame technique Authentication Bypass
View allShare
External POC / Exploit Code
Leaving vuln.today