Honeywell CVE-2022-30314

MEDIUM
Use of Hard-coded Credentials (CWE-798)
2022-07-28 cve@mitre.org
4.6
CVSS 3.1 · NVD
Share

Severity by source

NVD PRIMARY
4.6 MEDIUM
AV:P/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N

Primary rating from NVD · only source for this CVE.

CVSS VectorNVD

CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N
Attack Vector
Physical
Attack Complexity
Low
Privileges Required
None
User Interaction
None
Scope
Unchanged
Confidentiality
None
Integrity
High
Availability
None

Lifecycle Timeline

1
CVE Published
Jul 28, 2022 - 16:15 nvd
MEDIUM 4.6

DescriptionNVD

Honeywell Experion PKS Safety Manager 5.02 uses Hard-coded Credentials. According to FSCT-2022-0052, there is a Honeywell Experion PKS Safety Manager hardcoded credentials issue. The affected components are characterized as: POLO bootloader. The potential impact is: Manipulate firmware. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 serial interface for firmware management purposes. When booting, the Safety Manager exposes the Enea POLO bootloader via this interface. Access to the boot configuration is controlled by means of credentials hardcoded in the Safety Manager firmware. The credentials for the bootloader are hardcoded in the firmware. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize these credentials to control the boot process and manipulate the unauthenticated firmware image (see FSCT-2022-0054).

AnalysisAI

Honeywell Experion PKS Safety Manager 5.02 uses Hard-coded Credentials. Rated medium severity (CVSS 4.6), this vulnerability is no authentication required, low attack complexity. No vendor patch available.

Technical ContextAI

This vulnerability is classified as Use of Hard-coded Credentials (CWE-798), which allows attackers to gain access using credentials embedded in source code. Honeywell Experion PKS Safety Manager 5.02 uses Hard-coded Credentials. According to FSCT-2022-0052, there is a Honeywell Experion PKS Safety Manager hardcoded credentials issue. The affected components are characterized as: POLO bootloader. The potential impact is: Manipulate firmware. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 serial interface for firmware management purposes. When booting, the Safety Manager exposes the Enea POLO bootloader via this interface. Access to the boot configuration is controlled by means of credentials hardcoded in the Safety Manager firmware. The credentials for the bootloader are hardcoded in the firmware. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize these credentials to control the boot process and manipulate the unauthenticated firmware image (see FSCT-2022-0054). Affected products include: Honeywell Safety Manager Firmware.

RemediationAI

No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Remove hard-coded credentials, use environment variables or secrets management, rotate exposed credentials immediately.

CVE-2013-0108 MEDIUM POC
6.8 Feb 24

An ActiveX control in HscRemoteDeploy.dll in Honeywell Enterprise Buildings Integrator (EBI) R310, R400.2, R410.1, and R

CVE-2015-0984 CRITICAL POC
10.0 Mar 31

Directory traversal vulnerability in the FTP server on Honeywell Excel Web XL1000C50 52 I/O, XL1000C100 104 I/O, XL1000C

CVE-2023-3710 CRITICAL POC
9.8 Sep 12

Improper Input Validation vulnerability in Honeywell PM43 on 32 bit, ARM (Printer web page modules) allows Command Injec

CVE-2017-14263 HIGH
8.1 Sep 11

Honeywell NVR devices allow remote attackers to create a user account in the admin group by leveraging access to a guest

CVE-2017-5671 HIGH POC
8.8 Mar 29

Honeywell Intermec PM23, PM42, PM43, PC23, PC43, PD43, and PC42 industrial printers before 10.11.013310 and 10.12.x befo

CVE-2014-8269 HIGH
7.5 Dec 13

Multiple stack-based buffer overflows in (1) HWOPOSScale.ocx and (2) HWOPOSSCANNER.ocx in Honeywell OPOS Suite before 1.

CVE-2025-2605 CRITICAL
9.9 May 02

Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability in Honeywell MB

CVE-2026-3611 CRITICAL
10.0 Mar 12

Unauthenticated access to Honeywell IQ4x building controller HMI. CVSS 10.0.

CVE-2017-5140 CRITICAL
9.8 Feb 13

An issue was discovered in Honeywell XL Web II controller XL1000C500 XLWebExe-2-01-00 and prior, and XLWeb 500 XLWebExe-

CVE-2017-5139 CRITICAL
9.8 Feb 13

An issue was discovered in Honeywell XL Web II controller XL1000C500 XLWebExe-2-01-00 and prior, and XLWeb 500 XLWebExe-

CVE-2023-25178 CRITICAL
9.8 Jul 13

Controller may be loaded with malicious firmware which could enable remote code execution. Rated critical severity (CVSS

CVE-2022-30318 CRITICAL
9.8 Aug 31

Honeywell ControlEdge through R151.1 uses Hard-coded Credentials. Rated critical severity (CVSS 9.8), this vulnerability