Lifecycle Timeline
1DescriptionNVD
A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online.
AnalysisAI
A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable. Rated high severity (CVSS 8.6), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
Technical ContextAI
This vulnerability is classified as Uncontrolled Resource Consumption (CWE-400), which allows attackers to cause denial of service by exhausting system resources. A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online. Affected products include: Rockwellautomation Compactlogix 5380 Firmware, Rockwellautomation Compact Guardlogix 5380 Firmware, Rockwellautomation Compactlogix 5480 Firmware, Rockwellautomation Controllogix 5580 Firmware, Rockwellautomation Guardlogix 5580 Firmware.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Implement rate limiting, set resource quotas, validate input sizes, use timeouts.
More in Compactlogix 5380 Firmware
View allAn attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, a
CVE 2021-22681 https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1550.html and send a
Due to a memory leak, a denial-of-service vulnerability exists in the Rockwell Automation affected products. Rated high
A denial-of-service vulnerability exists in the Rockwell Automation affected products when specially crafted packets are
CVE-2024-7515 IMPACT A denial-of-service vulnerability exists in the affected products. Rated high severity (CVSS 8.7),
CVE-2024-7507 IMPACT A denial-of-service vulnerability exists in the affected products. Rated high severity (CVSS 8.7),
Rockwell Automation was made aware of a vulnerability that causes all affected controllers on the same network to result
A specific malformed fragmented packet type (fragmented packets may be generated automatically by devices that send larg
An unauthorized user could use a specially crafted sequence of Ethernet/IP messages, combined with heavy traffic loading
Rockwell Automation Studio 5000 Logix Designer (all versions) are vulnerable when an attacker who achieves administrator
A Resource Exhaustion issue was discovered in Rockwell Automation ControlLogix 5580 controllers V28.011, V28.012, and V2
Same weakness CWE-400 – Uncontrolled Resource Consumption