Melsec Iq R00Cpu Firmware
CVE-2020-13238
HIGH
Vulnerability Assessment
| Weakness |
CWE
OWASP Top 10:2025
A06:2025 - Insecure Design
ASVS 5.0
V2 - Validation and Business Logic Resource consumption limits
MITRE ATT&CK
1 technique across 1 tactic: Impact The technique list with ATT&CK links and the kill-chain view is part of the Basic plan and up. |
| Impact | CVSS score of 7.5 (HIGH). Attack characteristics: network attack vector, low complexity, no privileges required, no user interaction not required. |
| Exploit ScenarioDerived | A remote attacker could cause denial of service by exhausting system resources by sending crafted requests to the affected application. No authentication is required to exploit this vulnerability. |
Get an e-mail when this CVE is exploited, patched or re-scored. Free account.
Alert meAnalysisAI
Mitsubishi MELSEC iQ-R Series PLCs with firmware 33 allow attackers to halt the industrial process by sending an unauthenticated crafted packet over the network, because this denial of service attack. Rated high severity (CVSS 7.5), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Implement rate limiting, set resource quotas, validate input sizes, use timeouts.
Affects your stack
Find out whether the stacks and servers you run are on an affected version.
Checking this CVE against your own stacks and servers is part of the Basic plan and up.
Technical ContextAI · show details
This vulnerability is classified as Uncontrolled Resource Consumption (CWE-400), which allows attackers to cause denial of service by exhausting system resources. Mitsubishi MELSEC iQ-R Series PLCs with firmware 33 allow attackers to halt the industrial process by sending an unauthenticated crafted packet over the network, because this denial of service attack consumes excessive CPU time. After halting, physical access to the PLC is required in order to restore production. Affected products include: Mitsubishielectric Melsec Iq-R00Cpu Firmware, Mitsubishielectric Melsec Iq-R01Cpu Firmware, Mitsubishielectric Melsec Iq-R02Cpu Firmware, Mitsubishielectric Melsec Iq-R04Cpu Firmware, Mitsubishielectric Melsec Iq-R08Cpu Firmware.
Know when Melsec Iq R00Cpu Firmware gets its next vulnerability
- Watch products and get an email when something new is published
- Check this CVE against your own stack and servers
- Exploit and PoC references, threat intelligence from 22 sources
No credit card · 7-day full trial
Severity by source
AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Primary rating from NVD · only source for this CVE.
CVSS VectorNVD
DescriptionNVD
Mitsubishi MELSEC iQ-R Series PLCs with firmware 33 allow attackers to halt the industrial process by sending an unauthenticated crafted packet over the network, because this denial of service attack consumes excessive CPU time. After halting, physical access to the PLC is required in order to restore production.
Threat Intelligence Overview
How this decision was reached
The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.
What every action level means
SSVC AssessmentENISA
Priority Score
Attack Technique
Denial of Service attacks render applications or systems unavailable by overwhelming resources or triggering failure conditions.
NVD
CVE.org
EPSS
GitHub PoC
Exploit-DB