Skip to main content

SIMATIC WinCC EUVDEUVD-2026-98380

| CVE-2026-59241 HIGH
Incorrect Privilege Assignment (CWE-266)
2026-10-13 siemens GHSA-q747-5rxh-c5w7
8.7
CVSS 4.0 · Vendor: siemens
View

Attack ChainAIDerived

Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain

  1. Access
    Obtain WinCC database credentials
  2. Delivery
    Connect to WinCC DB remotely
  3. Exploit
    Abuse over-permissioned database role
  4. Execution
    Execute OS commands on host
  5. Impact
    Full compromise of WinCC server

Vulnerability Assessment

Weakness
CWE
OWASP Top 10:2025
A06:2025 - Insecure Design
ASVS 5.0
V8 - Authorization Privilege assignment review
Exploitation Conditions

Exploitation requires the attacker to already possess authenticated database access to the SIMATIC WinCC database (PR:L) and network reachability to that database service (AV:N); no user interaction is needed. The specific precondition is that the WinCC application assigns excessive permissions to a database role, so any principal mapped to that role can leverage it to run arbitrary OS commands on the WinCC host. Limiting factors: the attacker must first hold valid database credentials/role membership, and the WinCC database must be network-accessible to the attacker - in properly segmented OT environments where WinCC database access is restricted to trusted operator stations, the realistic attack surface is substantially reduced. Affected deployments: WinCC V7.5 (all versions), V8.0 before Update 11, and V8.1 before Update 7.

Impact

This is a credible operational-technology priority rather than an inflated high-CVSS issue, though not a drop-everything emergency. The vendor-supplied CVSS 4.0 vector (AV:N/AC:L/AT:N/PR:L/UI:N, VC:H/VI:H/VA:H, score 8.7) indicates a network-reachable, low-complexity flaw requiring only low privileges and no user interaction, yielding full confidentiality, integrity, and availability impact on the host - consistent with the CWE-266 (incorrect privilege assignment) weakness and the description of an authenticated database user escalating to arbitrary command execution. No EPSS score, KEV listing, or public POC was provided in the input, so there is no public exploit identified at time of analysis and no evidence of active exploitation; the risk is therefore driven by severity and the sensitivity of the asset (industrial HMI/SCADA) rather than by observed in-the-wild activity. The key limiting signal is PR:L: the attacker must already hold valid database access, which in well-segmented ICS networks is a meaningful barrier, so this is more realistically an insider/post-compromise privilege-escalation path than a mass-exploitable internet-facing bug. Note the subsequent-system metrics are N despite the description implying OS-level command execution - Siemens appears to treat the WinCC host as the vulnerable system itself rather than modeling a scope change; defenders should treat impact as full host compromise regardless.

Exploit ScenarioDerived

An attacker who has obtained legitimate or stolen database credentials for a SIMATIC WinCC server (an insider, or an adversary who has already gained a foothold on the OT/IT network) connects to the WinCC database over the network. Abusing the over-permissioned database role, they execute operating-system commands on the WinCC host, escalating from database-level access to full compromise of the SCADA/HMI server. No public exploit code is known at time of analysis, so this would require custom exploitation.

This Week Schedule remediation this week. Why: HIGH severity (CVSS 7.0-8.9).
No patch listed yet 0.5% exploitation probability (EPSS)

Get an e-mail when this CVE is exploited, patched or re-scored. Free account.

Alert me

AnalysisAIv2 – Oct 13, 2026

Authenticated database users can escalate privileges and execute arbitrary operating-system commands on hosts running SIMATIC WinCC V7.5 (all versions), V8.0 before Update 11, and V8.1 before Update 7 because the application assigns excessive permissions to a database role (CWE-266). Exploitation requires a remote attacker to already hold valid database credentials and network reachability to the WinCC database service, but no user interaction is needed; no public exploit code has been identified at time of analysis. Siemens rates the issue 8.7, and while the impact is high, our independent assessment classifies it as a credible operational-technology priority rather than an emergency because the prerequisite of authenticated database access and network segmentation limits the realistic attack surface.

Earlier versions of this analysis (1)
v1 Oct 13, 2026 - 10:01 CVSS 8.8

Privilege escalation in SIMATIC WinCC (V7.5 all versions, V8.0 before Update 11, V8.1 before Update 7) enables an authenticated remote attacker with database access to execute arbitrary OS commands on the WinCC host, potentially compromising the industrial control system. Exploitation requires valid database credentials and network reachability to the database service, which in properly segmented OT environments is typically restricted to the plant network. No public exploit identified at time of analysis, and this is not confirmed actively exploited; the risk is high for industrial deployments but not an emergency for general IT.

RemediationAI

For SIMATIC WinCC V8.0 and V8.1, apply the vendor updates that correspond to the fixed version boundaries: V8.0 Update 11 and V8.1 Update 7, respectively, as indicated by the affected version ranges in the Siemens advisory. SIMATIC WinCC V7.5 is listed as affected in all versions, and no fixed V7.5 version is provided in the available data; therefore, V7.5 deployments require compensating controls such as enforcing least-privilege on all database roles used by WinCC, restricting network access to the WinCC database to trusted operator stations only, and monitoring database role memberships for unexpected changes. Consult the Siemens advisory at https://cert-portal.siemens.com/productcert/html/ssa-550198.html for the most current remediation guidance and any V7.5-specific instructions. Trade-offs: locking down database access may hinder remote administration and third-party integrations, and removing excessive role permissions could break functionality if WinCC services rely on those permissions.

Affected VersionsENISA

SIMATIC WinCC V8.0 0 <V8.0 Update 11
SIMATIC WinCC V8.1 0 <V8.1 Update 7
SIMATIC WinCC V7.5 0 <*

Affects your stack

Find out whether the stacks and servers you run are on an affected version.

Checking this CVE against your own stacks and servers is part of the Basic plan and up.

Technical ContextAI · show details

SIMATIC WinCC is Siemens' SCADA/HMI software used for industrial process visualization and control, typically deployed on Windows hosts with a bundled or connected database (e.g., Microsoft SQL Server) that stores configuration, archives, and runtime data. The vulnerability is an instance of CWE-266 (Incorrect Privilege Assignment): a database role in the WinCC environment is granted permissions beyond what is necessary, so any authenticated principal mapped to that role can leverage those rights to break out of the database context and run arbitrary commands on the underlying WinCC host. The CVSS 4.0 vector reflects network reachability (AV:N) and low privileges (PR:L), meaning the attacker must first obtain database access; once inside the database, the excessive role permissions allow full compromise of the host (VC:H/VI:H/VA:H). The affected deployment models are WinCC V7.5 (all versions), V8.0 before Update 11, and V8.1 before Update 7, per the CPEs.

Know when Simatic Wincc V7 5 gets its next vulnerability

  • Watch products and get an email when something new is published
  • Check this CVE against your own stack and servers
  • Exploit and PoC references, threat intelligence from 22 sources

No credit card · 7-day full trial

Severity by source

Vendor (siemens) PRIMARY 8.7 HIGH
CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
vuln.today AI 8.8 HIGH

Network-reachable database service (AV:N/AC:L), but a valid database account is required (PR:L); over-permissioned role yields full host command execution (C/I/A:H); scope kept U to match vendor SC:N.

3.1 AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
4.0 AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N

Primary rating from Vendor (siemens).

CVSS VectorVendor: siemens

Attack Vector
Network
Attack Complexity
Low
Attack Requirements
None
Privileges Required
Low
User Interaction
None
Vulnerable system: Confidentiality
High
Vulnerable system: Integrity
High
Vulnerable system: Availability
High
Subsequent system: Confidentiality
None
Subsequent system: Integrity
None
Subsequent system: Availability
None

Lifecycle Timeline

2
CVSS changed
Oct 13, 2026 - 10:22 NVD
8.8 (HIGH) 8.7 (HIGH)
CVE Published
Oct 13, 2026 - 09:18 cve.org
HIGH 8.8

DescriptionCVE.org

A vulnerability has been identified in SIMATIC WinCC V7.5 (All versions), SIMATIC WinCC V8.0 (All versions < V8.0 Update 11), SIMATIC WinCC V8.1 (All versions < V8.1 Update 7). The affected application does not sufficiently restrict the permissions assigned to a database role. This could allow an authenticated remote attacker with database access to escalate privileges and execute arbitrary commands on the host system where SIMATIC WinCC is installed, potentially leading to a compromise of the system.

Executive ViewAI

Why It Matters

SIMATIC WinCC V7.5 (all versions), V8.0 before Update 11, and V8.1 before Update 7 contain a privilege-escalation flaw that could allow someone with valid database credentials to execute operating-system commands on industrial control hosts, potentially disrupting manufacturing or process operations. Because no vendor patch is currently available, affected OT environments remain exposed until interim network and access controls are enforced. Leadership should prioritize identifying and segmenting these systems and limiting database privileges, as the risk is high but contingent on existing database access and network reachability.

Business Impact: High
Compensating Controls

No vendor-released patch identified at time of analysis. Enforce network segmentation to limit access to the WinCC database service, restrict and audit database accounts, apply least privilege to database roles, rotate credentials, enable host-based firewalls, monitor for anomalous database and OS command execution, and prepare to upgrade to a vendor-fixed release when available.

Threat Intelligence Overview

EPSS Score
0.5%
Top 59% exploitable
Prevalence
Medium
widely used ICS/SCADA HMI, but industrial deployment only, not everywhere
Social Media
1
Sightings
Data Quality
4 sources
Confidence: Medium

How this decision was reached

The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.

SignalValue
Severity HIGH
CISA KEV No
Public POC No
EPSS 0.5%
Patch available No
Active threat No
Deciding rule
HIGH severity (CVSS 7.0-8.9)
What every action level means
Emergency Immediate action required. Criteria: CRITICAL + in CISA KEV (actively exploited) without patch, OR CRITICAL + EPSS > 30% without patch, OR CRITICAL + active threat signals without patch.
Act Now Prioritize within 24-48h. Criteria: in KEV with patch available, OR CRITICAL + public POC, OR HIGH + EPSS > 10%, OR CRITICAL + active threat, OR any CRITICAL severity.
This Week Schedule remediation this week. Criteria: HIGH severity (CVSS 7.0-8.9). Patch within normal change window.
This Month Plan within 30 days. Criteria: MEDIUM severity (CVSS 4.0-6.9), lower exploitation probability. Include in regular patch cycle.
Monitor Track and reassess. Criteria: LOW severity (CVSS 0.1-3.9), minimal exploitation risk. No immediate action needed.

SSVC AssessmentENISA

SSVC Decision· derived
Scheduled
Exploitation· derived
None
System Exposure· derived
Open
Automatable· derived
No
Human Impact
High

Priority Score

44
Low Medium High Critical
KEV: 0
EPSS: 0
CVSS: +44
PoC: 0
Weaponized: 0
Threat intel: 0
Gov advisory: 0

Attack Technique

Privilege escalation occurs when an attacker leverages flaws in access control mechanisms to gain permissions beyond what they were originally granted.

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy