Skip to main content

Hitachi Energy RTU500 EUVDEUVD-2026-88686

| CVE-2026-8067 MEDIUM
Missing Authorization (CWE-862)
2026-09-29 Hitachi Energy GHSA-8w27-w4qm-ch74
6.5
CVSS 3.1 · Vendor: Hitachi Energy
View

Attack ChainAIDerived

Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain

  1. Access
    Obtain low-privilege web credentials
  2. Exploit
    Reach RTU500 web management interface
  3. Execution
    Invoke unprotected reset endpoint
  4. Impact
    Device reboots, telemetry/control disrupted

Vulnerability Assessment

Weakness
CWE
OWASP Top 10:2025
A01:2025 - Broken Access Control
ASVS 5.0
V8 - Authorization Authorization checks on every request
MITRE ATT&CK

1 technique across 1 tactic: Privilege Escalation

The technique list with ATT&CK links and the kill-chain view is part of the Basic plan and up.

Exploitation Conditions

Requires an authenticated low-privilege account or active session on the RTU500 web application (PR:L), plus network reachability to that web management interface. The vulnerable behavior is the web application's reset endpoint, which fails to enforce proper authorization (CWE-862) so a user without reboot rights can trigger it. Limiting factors: valid credentials/session are mandatory (no unauthenticated path), the web interface must be network-accessible to the attacker, and the impact is a temporary, recoverable reboot rather than persistent damage or data exposure. Exposure is highest where the RTU500 management interface is reachable from broader IT/OT networks rather than an isolated management VLAN.

Impact

This is a genuine but moderate-severity availability issue, not a high-priority emergency. The CVSS 3.1 base score of 6.5 (AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H) is internally consistent with the description: an authenticated (PR:L) user reaches the web application's reset endpoint over the network (AV:N) with low complexity (AC:L) and no user interaction, causing an availability-only impact (A:H) with no confidentiality or integrity loss. No EPSS score, no CISA KEV listing, and no public POC are present in the input, so exploitation is speculative - there is no evidence of active exploitation or weaponization. The key mitigating signal is PR:L: an attacker must already possess valid credentials or a session on the RTU500 web interface, which limits this to insiders or attackers who have already gained a foothold. The real-world weight comes from context, not the number: the RTU500 is an OT/ICS remote terminal unit used in electric-utility substation automation, where an unexpected reboot can disrupt grid telemetry and control, so the A:H rating is meaningful operationally even though the flaw is only a recoverable DoS. Overall: real but not urgent - prioritize based on exposure of the management interface and credential hygiene rather than fear of mass exploitation.

Exploit ScenarioDerived

An attacker who has obtained low-privilege credentials to the RTU500 web application (or an insider) sends a request to the device's reset endpoint that lacks a proper authorization check. The device reboots, causing temporary unavailability of substation telemetry and control until it comes back online. No public exploit code is identified at time of analysis, and the low attack complexity means the request is trivial to repeat for sustained disruption.

This Month Plan within 30 days. Why: MEDIUM severity (CVSS 4.0-6.9).
Patch available 0.3% exploitation probability (EPSS)

Get an e-mail when this CVE is exploited, patched or re-scored. Free account.

Alert me

AnalysisAIv1 – Sep 29, 2026

The Hitachi Energy RTU500 series CMU web application fails to enforce proper authorization on its reset endpoint, allowing an authenticated low-privilege user to force the remote terminal unit to reboot and temporarily lose availability (CVSS 6.5, CWE-862). Exploitation requires a valid low-privilege account or active session (PR:L) plus network reachability to the web management interface, and the assessed impact is limited to temporary, recoverable device unavailability rather than data exposure or persistent compromise. No public exploit code or confirmed active exploitation has been identified at time of analysis, and no EPSS score was supplied; this is a genuine but moderate-severity availability issue, not a high-priority emergency.

RemediationAI

Apply the firmware update specified in the Hitachi Energy advisory for CVE-2026-8067 (document 8DBD000251 at https://publisher.hitachienergy.com/preview?DocumentID=8DBD000251&LanguageCode=en&DocumentPartId=&Action=Launch); no exact fixed firmware version is confirmed in the available data, so the advisory should be consulted for the precise target release before scheduling maintenance. Until patched, the most effective compensating control is to restrict the RTU500 web management interface to an isolated management VLAN or a tightly scoped allowlist of administrative hosts, since the flaw cannot be triggered without a valid session and network reachability - the trade-off is that operators lose remote management convenience and must rely on jump hosts or out-of-band access. Where the reset function is not required for normal operations, restrict or disable access to that endpoint at the reverse proxy or firewall layer, accepting that this may impede legitimate planned-reboot workflows. Strengthen least privilege by removing unnecessary accounts and reviewing which roles can reach the web application, note that reboot outages can be detected through availability monitoring and syslog alerts on unexpected restarts, and recognize that these mitigations reduce exposure but do not eliminate the underlying missing-authorization defect.

Affected VersionsENISA

RTU500 series CMU Firmware 9.0 <12.0

Affected Packages

euvd rtu500_series_cmu_firmware fix: 12.0

Source: OSV (Open Source Vulnerabilities)

Affects your stack

Affects 1 package in euvd

Checking this CVE against your own stacks and servers is part of the Basic plan and up.

Technical ContextAI · show details

The affected component is the web-based management application shipped with the Hitachi Energy RTU500 series CMU firmware (CPE cpe:2.3:a:hitachi_energy:rtu500_series_cmu_firmware), a remote terminal unit widely deployed in substation automation and SCADA/OT environments. The root cause is classified as CWE-862 (Missing Authorization): the reset endpoint performs the reboot action without verifying that the requesting principal holds the privilege required for that operation, so any authenticated session - including one with minimal rights - can invoke it. The CVSS 3.1 vector AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H confirms that the flaw is reachable over the network with low attack complexity, needs low privileges and no user interaction, and yields a high availability impact with no confidentiality or integrity impact, consistent with a forced restart of a control device. Because the RTU500 is operational technology at the edge of industrial networks, availability loss, even if temporary, can interrupt telemetry and control functions for the duration of the reboot and re-initialization.

Know when Rtu500 Series Cmu Firmware gets its next vulnerability

  • Watch products and get an email when something new is published
  • Check this CVE against your own stack and servers
  • Exploit and PoC references, threat intelligence from 22 sources

No credit card · 7-day full trial

Severity by source

Vendor (Hitachi Energy) PRIMARY 6.5 MEDIUM
AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H
vuln.today AI 6.5 MEDIUM

Network-reachable web endpoint (AV:N/AC:L) requires a valid low-privilege session (PR:L); impact is an availability-only reboot (A:H) with no confidentiality or integrity effect.

3.1 AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H
4.0 AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N

Primary rating from Vendor (Hitachi Energy).

CVSS VectorVendor: Hitachi Energy

Attack Vector
Network
Attack Complexity
Low
Privileges Required
Low
User Interaction
None
Scope
Unchanged
Confidentiality
None
Integrity
None
Availability
High

Lifecycle Timeline

1
Patch available
Sep 29, 2026 - 11:01 EUVD

DescriptionCVE.org

An improper authorization vulnerability in the RTU500’s web application allows an authenticated user to trigger the RTU500 to reboot through the reset endpoint. Successful exploitation could cause temporary device unavailability and disruption of its intended operation.

Threat Intelligence Overview

EPSS Score
0.3%
Top 77% exploitable
Prevalence
Medium
widely deployed OT/RTU in electric-utility substation automation
Threat Intel
1
1 source
Data Quality
5 sources
Confidence: Medium

How this decision was reached

The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.

SignalValue
Severity MEDIUM
CISA KEV No
Public POC No
EPSS 0.3%
Patch available Yes
Active threat Yes
Deciding rule
MEDIUM severity (CVSS 4.0-6.9)
What every action level means
Emergency Immediate action required. Criteria: CRITICAL + in CISA KEV (actively exploited) without patch, OR CRITICAL + EPSS > 30% without patch, OR CRITICAL + active threat signals without patch.
Act Now Prioritize within 24-48h. Criteria: in KEV with patch available, OR CRITICAL + public POC, OR HIGH + EPSS > 10%, OR CRITICAL + active threat, OR any CRITICAL severity.
This Week Schedule remediation this week. Criteria: HIGH severity (CVSS 7.0-8.9). Patch within normal change window.
This Month Plan within 30 days. Criteria: MEDIUM severity (CVSS 4.0-6.9), lower exploitation probability. Include in regular patch cycle.
Monitor Track and reassess. Criteria: LOW severity (CVSS 0.1-3.9), minimal exploitation risk. No immediate action needed.

SSVC AssessmentENISA

SSVC Decision· derived
Scheduled
Exploitation
None
System Exposure· derived
Open
Automatable
No
Human Impact· derived
Medium
Technical Impact
Partial

Priority Score

42
Low Medium High Critical
KEV: 0
EPSS: 0
CVSS: +32
PoC: 0
Weaponized: 0
Threat intel: +10
Gov advisory: 0

Attack Technique

Authentication bypass attacks exploit flaws in the verification mechanisms that control access to systems and applications.

Threat IntelligenceMISP

CISA Advisories
Sources: CISA (public domain)

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy