Attack ChainAIDerived
Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain
-
AccessReach myPRO Manager command API over network
-
DeliverySend request to privileged management function
-
ExploitAPI skips authentication check
-
ExecutionExecute privileged management action
-
ImpactCompromise SCADA management (C/I/A high)
Vulnerability Assessment
| Weakness |
CWE
OWASP Top 10:2025
A01:2025 - Broken Access Control
ASVS 5.0
V8 - Authorization Authorization checks on every request
MITRE ATT&CK
1 technique across 1 tactic: Privilege Escalation The technique list with ATT&CK links and the kill-chain view is part of the Basic plan and up. |
| Exploitation Conditions | Exploitation requires only network reachability to the mySCADA myPRO Manager command API - no credentials, no user interaction, and default configurations are affected (AV:N/AC:L/PR:N/UI:N). The single meaningful limiting factor is network exposure: myPRO Manager is OT/SCADA management software typically deployed on segmented industrial or plant networks, so exploitation depends on the attacker having a route to the API (e.g., flat network, VPN foothold, or an improperly exposed/internet-facing management interface). Any attacker who can reach the API can invoke privileged management functions. |
| Impact | This is a genuine high-priority vulnerability by its intrinsic characteristics. The vendor CVSS 4.0 vector (AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H, base 9.3) describes a fully remote, unauthenticated, low-complexity flaw with high impact to confidentiality, integrity, and availability - the worst-case profile for an internet- or network-reachable service. CWE-862 (Missing Authorization) combined with the description ('does not properly enforce authentication for privileged functions') confirms an authentication/authorization gap on privileged management APIs. However, the exploitation-probability signals are notably more modest and should temper prioritization urgency: EPSS is only 0.65% (50th percentile), there is NO CISA KEV listing, and NO public POC is identified. The near-median EPSS despite the 9.3 score is typical of newly-published ICS advisories with no observed exploitation yet, and reflects the limited, non-internet-facing deployment footprint of SCADA management software rather than a defect in the severity rating. There is no SSVC decision data in the input to cross-reference. Net: the vulnerability is technically severe and trivially exploitable IF an attacker has network reach to the API, but current real-world exploitation evidence is absent - this is a patch-promptly item for OT operators, not a confirmed active-exploitation emergency. |
| Exploit ScenarioDerived | An attacker with network access to the mySCADA myPRO Manager command API sends requests directly to privileged management endpoints without supplying valid credentials, and the server executes them because authentication is not enforced. This grants control over management functions of the SCADA/HMI environment, potentially altering configuration or process-control data. No public exploit code is identified at time of analysis, but the low attack complexity (AC:L, no user interaction) means weaponization would be straightforward once the API is reachable. |
Get an e-mail when this CVE is exploited, patched or re-scored. Free account.
Alert meAnalysisAIv1 – Sep 17, 2026
Unauthenticated remote attackers with network reachability to the mySCADA myPRO Manager command API can invoke privileged management functions because the API fails to enforce authorization on those endpoints. All deployments of mySCADA myPRO up to and including version 2.1 are reported as affected, and exploitation requires no credentials and no user interaction (CVSS 4.0 base 9.3; independent assessment agrees on a network-reachable, PR:N/UI:N critical-severity issue with high confidentiality, integrity, and availability impact). No public exploit code has been identified and CISA KEV does not list this CVE, but EPSS places it around the 50th percentile (0.65%), so the practical risk is driven mainly by whether the OT management interface is reachable from attacker-controlled networks.
RemediationAI
No vendor-released patch version is identified in the available data, so the primary action is to obtain the current mySCADA myPRO Manager build from the vendor download page (https://www.myscada.org/downloads/mySCADAPROManager/) and confirm with mySCADA that the installed release contains the fix for CVE-2026-73807 before returning the system to service. Until that is verified, apply compensating controls that address the actual prerequisite - network reachability to the command API: block the TCP port used by the myPRO Manager command API at the OT/IT boundary and in host firewalls so only approved engineering workstations can reach it, which stops remote exploitation but forces administrators to use jump hosts or on-site access and can disrupt remote management workflows; require access through a VPN or similar authenticated gateway rather than exposing the management interface directly, accepting the added dependency on the VPN for availability; and where feasible take the management interface off any internet-facing address entirely. Because the flaw is a missing authorization check rather than a credential weakness, password hardening and MFA on other services will not mitigate it. Monitor API and management logs for command activity originating from unexpected hosts, review CISA advisory ICSA-26-258-03 and ENISA EUVD-2026-80014 for updates on a fixed release, and consider restricting or disabling remote management features entirely if the operational cost of segmentation is acceptable.
Affected VersionsENISA
Affected Packages
Source: OSV (Open Source Vulnerabilities)
Affects your stack
Affects 1 package in euvd
Checking this CVE against your own stacks and servers is part of the Basic plan and up.
Technical ContextAI · show details
mySCADA myPRO Manager is industrial HMI/SCADA management software used to configure and supervise plant and process equipment, and it exposes a command API through which management operations are performed. The root cause is CWE-862 (Missing Authorization): the command API authenticates or accepts requests without verifying that the caller is entitled to perform privileged functions, so the authorization check for administrative operations is effectively absent rather than merely weak. This is distinct from a credential-theft or session-hijacking bug - the security decision itself is missing - which is why the provider's CVSS 4.0 vector (AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H) and our independent CVSS 3.1 assessment (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) both rate the flaw as critical and reachable without privileges. Because the affected component is OT/SCADA management software, the meaningful limiting factor is network exposure: such interfaces are normally placed on segmented industrial networks, but flat networks, VPN footholds, or an internet-facing management interface would make the API directly reachable. CISA ICS-CERT published this as advisory ICSA-26-258-03, and ENISA tracks it as EUVD-2026-80014.
Know when Myscada gets its next vulnerability
- Watch products and get an email when something new is published
- Check this CVE against your own stack and servers
- Exploit and PoC references, threat intelligence from 22 sources
No credit card · 7-day full trial
Severity by source
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
Unauthenticated (PR:N) remote (AV:N) low-complexity access to privileged management functions yields full C/I/A impact on the SCADA manager; scope unchanged as impact stays within the product.
Primary rating from Vendor (hq).
CVSS VectorVendor: hq
DescriptionCVE.org
The mySCADA myPRO Manager command API does not properly enforce authentication for privileged functions. An unauthenticated attacker with network access to the affected API could exploit this vulnerability to access privileged management functions.
Executive ViewAI
Every deployment of mySCADA myPRO up to and including version 2.1 exposes a privileged management API that any network-reachable party can invoke without credentials or user interaction, meaning an attacker who can route to the interface can execute management functions as if authorized. Because myPRO sits at the center of industrial HMI/SCADA operations, unauthorized use could disrupt production, corrupt process data, or halt plant operations across any site where the management interface is exposed. There is no public exploit identified at time of analysis and no vendor-released patch identified at time of analysis, so leadership's near-term risk is defined almost entirely by how widely and to whom that interface is reachable.
No vendor-released patch identified at time of analysis. Interim mitigations: restrict all network access to the myPRO Manager command API to trusted OT management VLANs, jump hosts, or a dedicated engineering workstation via firewall rules and ACLs; deny inbound access from IT, guest, and internet-facing zones through OT segmentation; require VPN with MFA for any remote administrative or engineering access; enable and monitor API and authentication logging for unauthorized privileged calls; and back up configuration and HMI project data so affected systems can be rebuilt if abused.
Threat Intelligence Overview
How this decision was reached
The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.
What every action level means
SSVC AssessmentENISA
Priority Score
Attack Technique
Authentication bypass attacks exploit flaws in the verification mechanisms that control access to systems and applications.
The administrative web interface of mySCADA myPRO Manager can be accessed without authentication which could allow an un
mySCADA myPRO Manager stores credentials in cleartext, which could allow an attacker to obtain sensitive information. Ra
mySCADA myPRO versions 8.26.0 and prior has parameters which an authenticated user could exploit to inject arbitrary ope
A hardcoded FTP username of myscada and password of Vikuk63 in 'myscadagate.exe' in mySCADA myPRO 7 allows remote attack
mySCADA myPRO: Versions 8.20.0 and prior has a vulnerable debug interface which includes a ping utility, which may allow
An additional, nondocumented administrative account exists in mySCADA myPRO Versions 8.20.0 and prior that is not expose
An unauthenticated remote attacker can access mySCADA myPRO Versions 8.20.0 and prior without any form of authentication
mySCADA myPRO: Versions 8.20.0 and prior has a feature where the firmware can be updated, which may allow an attacker to
mySCADA myPRO: Versions 8.20.0 and prior has a feature to send emails, which may allow an attacker to inject arbitrary o
mySCADA myPRO: Versions 8.20.0 and prior has a feature where the password can be specified, which may allow an attacker
mySCADA myPRO: Versions 8.20.0 and prior has a feature where the API password can be specified, which may allow an attac
mySCADA myPRO Manager is vulnerable to an OS command injection which could allow a remote attacker to execute arbitrary
EUVD-2026-80014
GHSA-4wh4-f7jw-q9v9
NVD
CVE.org
EPSS
Exploit-DB