Skip to main content

Frick Controls Quantum Hd Firmware CVE-2026-21654

CRITICAL
OS Command Injection (CWE-78)
2026-02-27 productsecurity@jci.com
9.8
CVSS 3.1 · NVD
View

Attack ChainAIDerived

Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain

  1. Access
    Send crafted network request
  2. Exploit
    Inject OS commands in unvalidated parameter
  3. Execution
    Execute arbitrary commands as device process
  4. Impact
    Compromise system integrity and confidentiality

Vulnerability Assessment

Weakness
CWE
OWASP Top 10:2025
A05:2025 - Injection
ASVS 5.0
V1 - Encoding and Sanitization OS command sanitization, avoid shell exec
MITRE ATT&CK

2 techniques across 1 tactic: Execution

The technique list with ATT&CK links and the kill-chain view is part of the Basic plan and up.

Exploitation Conditions

Frick Controls Quantum HD version 10.22 or earlier with network accessibility enabled. Remote unauthenticated exploitation via vulnerable input parameters before authentication gates. No special configuration required — vulnerability exists in default pre-authentication code paths.

Impact

CVSS 9.8. ICS vulnerability affecting industrial refrigeration — compromise could impact food safety, pharmaceutical storage, or data center cooling.

Exploit ScenarioDerived

Attacker accesses Frick Quantum HD controller on OT network, injects commands to modify refrigeration setpoints, potentially spoiling temperature-sensitive goods or damaging equipment.

Act Now Prioritize within 24-48h. Why: CRITICAL severity.
No patch listed yet 0.2% exploitation probability (EPSS)

Get an e-mail when this CVE is exploited, patched or re-scored. Free account.

Alert me

AnalysisAIv1 – Mar 12, 2026

OS command injection in Johnson Controls Frick Controls Quantum HD allows unauthenticated remote attackers to execute arbitrary commands on industrial refrigeration control systems. CVSS 9.8.

Earlier versions of this analysis (1)
v1 Mar 12, 2026 - 21:55 CVSS 9.8

Command injection in Johnson Controls Frick Quantum HD refrigeration controller.

RemediationAI

Apply Johnson Controls security patch. Isolate ICS controllers from IT networks. Monitor for unauthorized command execution.

Affects your stack

Find out whether the stacks and servers you run are on an affected version.

Checking this CVE against your own stacks and servers is part of the Basic plan and up.

Technical ContextAI · show details

CWE-78 OS command injection in industrial refrigeration controller. First of several critical CVEs affecting the Frick Controls Quantum HD product line.

Know when Frick Controls Quantum Hd Firmware gets its next vulnerability

  • Watch products and get an email when something new is published
  • Check this CVE against your own stack and servers
  • Exploit and PoC references, threat intelligence from 22 sources

No credit card · 7-day full trial

Severity by source

NVD PRIMARY 9.8 CRITICAL
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Primary rating from NVD · only source for this CVE.

CVSS VectorNVD

Attack Vector
Network
Attack Complexity
Low
Privileges Required
None
User Interaction
None
Scope
Unchanged
Confidentiality
High
Integrity
High
Availability
High

DescriptionCVE.org

Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability in Johnson Controls Frick Controls Quantum HD allows OS Command Injection. Insufficient validation of input in certain parameters may permit unexpected actions, which could impact the security of the device before authentication occurs.This issue affects Frick Controls Quantum HD version 10.22 and prior.

Executive ViewAI

Why It Matters

A critical OS command injection vulnerability (CVSS 9.8) in Johnson Controls Frick Controls Quantum HD allows unauthenticated attackers to execute arbitrary commands with full system privileges. Organizations running this equipment face immediate risk of complete system compromise, data theft, and operational disruption, with no vendor patch currently available.

Business Impact: Severe
Compensating Controls

Implement network segmentation and restrict access via firewall rules to trusted networks only; disable remote access and management interfaces if operationally acceptable; deploy network-based IDS/IPS rules to detect OS command injection patterns; monitor system logs for suspicious command execution; consider WAF deployment if web-accessible; disable unnecessary features/services on affected devices; implement strict input validation and rate limiting at network perimeter; require multi-factor authentication for any management access.

Threat Intelligence Overview

EPSS Score
0.2%
Top 65% exploitable
Data Quality
3 sources
Confidence: Low

How this decision was reached

The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.

SignalValue
Severity CRITICAL
CISA KEV No
Public POC No
EPSS 0.2%
Patch available No
Active threat No
Deciding rule
CRITICAL severity
What every action level means
Emergency Immediate action required. Criteria: CRITICAL + in CISA KEV (actively exploited) without patch, OR CRITICAL + EPSS > 30% without patch, OR CRITICAL + active threat signals without patch.
Act Now Prioritize within 24-48h. Criteria: in KEV with patch available, OR CRITICAL + public POC, OR HIGH + EPSS > 10%, OR CRITICAL + active threat, OR any CRITICAL severity.
This Week Schedule remediation this week. Criteria: HIGH severity (CVSS 7.0-8.9). Patch within normal change window.
This Month Plan within 30 days. Criteria: MEDIUM severity (CVSS 4.0-6.9), lower exploitation probability. Include in regular patch cycle.
Monitor Track and reassess. Criteria: LOW severity (CVSS 0.1-3.9), minimal exploitation risk. No immediate action needed.

SSVC AssessmentENISA

SSVC Decision· derived
Out-of-Cycle
Exploitation· derived
None
System Exposure· derived
Open
Automatable· derived
Yes
Human Impact
Very High

Priority Score

49
Low Medium High Critical
KEV: 0
EPSS: 0
CVSS: +49
PoC: 0
Weaponized: 0
Threat intel: 0
Gov advisory: 0

Attack Technique

OS command injection occurs when an application passes unsanitized user input directly into system shell commands.

Affected Products (CPE)CVE.org

cpe:2.3:o:johnsoncontrols:frick_controls_quantum_hd_firmware:*:*:*:*:*:*:*:*

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy