Skip to main content

Simatic S7 1200 Cpu Firmware CVE-2021-37172

HIGH
Improper Authentication (CWE-287)
2021-08-10 productcert@siemens.com
7.5
CVSS 3.1 · NVD
Share

Severity by source

NVD PRIMARY
7.5 HIGH
AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N

Primary rating from NVD · only source for this CVE.

CVSS VectorNVD

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N
Attack Vector
Network
Attack Complexity
Low
Privileges Required
None
User Interaction
None
Scope
Unchanged
Confidentiality
None
Integrity
High
Availability
None

Lifecycle Timeline

1
CVE Published
Aug 10, 2021 - 11:15 nvd
HIGH 7.5

DescriptionNVD

A vulnerability has been identified in SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (V4.5.0). Affected devices fail to authenticate against configured passwords when provisioned using TIA Portal V13. This could allow an attacker using TIA Portal V13 or later versions to bypass authentication and download arbitrary programs to the PLC. The vulnerability does not occur when TIA Portal V13 SP1 or any later version was used to provision the device.

AnalysisAI

A vulnerability has been identified in SIMATIC S7-1200 CPU family (incl. Rated high severity (CVSS 7.5), this vulnerability is remotely exploitable, no authentication required, low attack complexity. This Improper Authentication vulnerability could allow attackers to bypass authentication mechanisms to gain unauthorized access.

Technical ContextAI

This vulnerability is classified as Improper Authentication (CWE-287), which allows attackers to bypass authentication mechanisms to gain unauthorized access. A vulnerability has been identified in SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (V4.5.0). Affected devices fail to authenticate against configured passwords when provisioned using TIA Portal V13. This could allow an attacker using TIA Portal V13 or later versions to bypass authentication and download arbitrary programs to the PLC. The vulnerability does not occur when TIA Portal V13 SP1 or any later version was used to provision the device. Affected products include: Siemens Simatic S7-1200 Cpu Firmware, Siemens Simatic Step 7 \(Tia Portal\).

RemediationAI

A vendor patch is available. Apply the latest security update as soon as possible. Implement multi-factor authentication, enforce strong password policies, use proven authentication frameworks.

Share

CVE-2021-37172 vulnerability details – vuln.today

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy