Skip to main content

Siprotec Compact 7Sj80 Firmware CVE-2018-4840

HIGH
Missing Authentication for Critical Function (CWE-306)
2018-03-08 productcert@siemens.com
7.5
CVSS 3.0 · NVD
Share

Severity by source

NVD PRIMARY
7.5 HIGH
AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N

Primary rating from NVD · only source for this CVE.

CVSS VectorNVD

CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N
Attack Vector
Network
Attack Complexity
Low
Privileges Required
None
User Interaction
None
Scope
Unchanged
Confidentiality
None
Integrity
High
Availability
None

Lifecycle Timeline

1
CVE Published
Mar 08, 2018 - 17:29 nvd
HIGH 7.5

DescriptionNVD

A vulnerability has been identified in DIGSI 4 (All versions < V4.92), EN100 Ethernet module DNP3 variant (All versions < V1.05.00), EN100 Ethernet module IEC 104 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.30), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). The device engineering mechanism allows an unauthenticated remote user to upload a modified device configuration overwriting access authorization passwords.

AnalysisAI

A vulnerability has been identified in DIGSI 4 (All versions < V4.92), EN100 Ethernet module DNP3 variant (All versions < V1.05.00), EN100 Ethernet module IEC 104 variant (All versions), EN100. Rated high severity (CVSS 7.5), this vulnerability is remotely exploitable, no authentication required, low attack complexity. This Missing Authentication for Critical Function vulnerability could allow attackers to access critical functionality without authentication.

Technical ContextAI

This vulnerability is classified as Missing Authentication for Critical Function (CWE-306), which allows attackers to access critical functionality without authentication. A vulnerability has been identified in DIGSI 4 (All versions < V4.92), EN100 Ethernet module DNP3 variant (All versions < V1.05.00), EN100 Ethernet module IEC 104 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.30), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). The device engineering mechanism allows an unauthenticated remote user to upload a modified device configuration overwriting access authorization passwords. Affected products include: Siemens Siprotec Compact 7Sj80 Firmware, Siemens Siprotec Compact 7Sk80 Firmware, Siemens Siprotec 4 7Sj66 Firmware, Siemens Digsi 4, Siemens En100 Ethernet Module Iec 104 Firmware.

RemediationAI

A vendor patch is available. Apply the latest security update as soon as possible. Require authentication for all sensitive operations, implement defense in depth.

Share

CVE-2018-4840 vulnerability details – vuln.today

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy