Skip to main content

Schneider Electric CVE-2017-7574

CRITICAL
Use of Hard-coded Credentials (CWE-798)
2017-04-06 cve@mitre.org
9.8
CVSS 3.1 · NVD
Share

Severity by source

NVD PRIMARY
9.8 CRITICAL
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Primary rating from NVD · only source for this CVE.

CVSS VectorNVD

Attack Vector
Network
Attack Complexity
Low
Privileges Required
None
User Interaction
None
Scope
Unchanged
Confidentiality
High
Integrity
High
Availability
High

Lifecycle Timeline

1
CVE Published
Apr 06, 2017 - 21:59 cve.org
CRITICAL 9.8

DescriptionCVE.org

Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product.

AnalysisAI

Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. Rated critical severity (CVSS 9.8), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.

Technical ContextAI

This vulnerability is classified as Use of Hard-coded Credentials (CWE-798), which allows attackers to gain access using credentials embedded in source code. Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product. Affected products include: Schneider-Electric Modicon Tm221Ce16R Firmware, Schneider-Electric Somachine.

RemediationAI

No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Remove hard-coded credentials, use environment variables or secrets management, rotate exposed credentials immediately.

CVE-2013-0658 CRITICAL POC
10.0 Feb 15

Heap-based buffer overflow in RFManagerService.exe in Schneider Electric Accutech Manager 2.00.1 and earlier allows remo

CVE-2013-0657 CRITICAL POC
10.0 Jan 21

Stack-based buffer overflow in Schneider Electric Interactive Graphical SCADA System (IGSS) 10 and earlier allows remote

CVE-2013-0662 CRITICAL POC
9.3 Apr 01

Multiple stack-based buffer overflows in ModbusDrv.exe in Schneider Electric Modbus Serial Driver 1.10 through 3.2 allow

CVE-2013-3075 CRITICAL POC
10.0 Apr 19

Multiple buffer overflows in ActUWzd.dll 1.0.0.1 in Mitsubishi MX Component 3, as distributed in Citect CitectFacilities

CVE-2018-3639 MEDIUM POC
5.5 May 22

Systems with microprocessors utilizing speculative execution and speculative execution of memory reads before the addres

CVE-2017-6026 CRITICAL POC
9.1 Jun 30

A Use of Insufficiently Random Values issue was discovered in Schneider Electric Modicon PLCs Modicon M241, firmware ver

CVE-2019-6814 CRITICAL POC
9.8 May 22

A CWE-287: Improper Authentication vulnerability exists in the NET55XX Encoder with firmware prior to version 2.1.9.7 wh

CVE-2017-6019 HIGH POC
7.5 Apr 07

An issue was discovered in Schneider Electric Conext ComBox, model 865-1058, all firmware versions prior to V3.03 BN 830

CVE-2018-7852 HIGH POC
7.5 May 22

A CWE-248: Uncaught Exception vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, a

CVE-2017-7575 CRITICAL POC
9.8 Apr 06

Schneider Electric Modicon TM221CE16R 1.3.3.3 devices allow remote attackers to discover the application-protection pass

CVE-2016-2278 HIGH POC
7.2 Mar 02

Schneider Electric Struxureware Building Operations Automation Server AS 1.7 and earlier and AS-P 1.7 and earlier allows

CVE-2014-9188 CRITICAL
10.0 Dec 27

Buffer overflow in an ActiveX control in MDraw30.ocx in Schneider Electric ProClima before 6.1.7 allows remote attackers

Share

CVE-2017-7574 vulnerability details – vuln.today

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy